| 2019-01-11 06:16:39 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NO SPECS OR LISTING PROVIDED FOR ACUTAL ELEVATOR |
| | UNIT ITSELF. PROVIDE LISTING/CERTIFICATIONS MODEL |
| | NUMBER ETC, FBC 107.2.1 NEC 90.7 110.2 |
| | |
| | 2. REBUTTAL COMMENT STATING MASTER DRAWING IS BEING |
| | "REVISED" WILL NOT SUFFICE. PROVIDE SIGNED ELECTRICAL |
| | DRAWING SHOWING CONDUIT SIZE/WIRING METHODS, WIRE SIZE, |
| | OVER CURRENT PROTECTION OF CIRCUIT, LOCATION OF |
| | RECEPTACLE IN HOME FOR ELEVATOR, LOCATION OF ELEVATOR |
| | ETC. FBC 107.2.1 FS 481.229; WPB FBC 107.3.5.1.2 |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |