2018-11-28 18:04:41MECHANICAL PROVISO:
 11/28/18
  
 PRIOR TO FINAL INSPECTION, SUBMIT REVISED PLANS THAT
 ADDRESS THE ITEMS LISTED BELOW.
  
 1) RELOCATE THE DISHWASHER EXHAUST FAN FROM ABOVE THE
 WALK-IN COOLER OR PROVIDE DOCUMENTATION THAT THE COOLER
 CAN BE USED AS A SERVICE PLATFORM.
  
 2) VERIFY COMPLIANCE WITH SECTION 508.1.1 FBC M: MAKEUP
 AIR TEMPERATURE.
  
 3) SUBMIT THE MIAMI-DADE NOA'S FOR THE EXHAUST AND
 MAKEUP AIR FANS.
  
  