| | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18100809 |
| | 11/20/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET AFS-5: VERIFY KEF-1 & 2 OUTLETS ARE LOCATED |
| | NOT LESS THAN 10' ABOVE THE ADJOINING GRADE, AND FROM |
| | AIR INTAKES INTO THE BUILDING.- SECTION 506.3.1.3.3 FBC |
| | M. |
| | |
| | 2) AFS-5: A LEVEL WORKING SPACE NOT LESS THAN 30 INCHES |
| | DEEP AND 30 INCHES WIDE SHALL BE PROVIDED AT THE |
| | LOCATIONS OF KEF 1 & 2, AND DWEF-1- SECTION 306.1 FBC |
| | M. CLARIFY IF THE ROOF OF THE WALK-IN COOLER WILL BE |
| | USED AS A SERVICE PLATFORM FOR DWEF-1, AND IF SO, |
| | CLARIFY IF IT HAS BEEN DESIGNED TO CARRY LIVE LOADS. |
| | |
| | 3) AFS-6: CLARIFY HOW ACCESS WILL BE PROVIDED TO THE |
| | GREASE EXHAUST DUCT CLEANOUTS- SECTION 506.3.8 FBC M. |
| | |
| | 4) VERIFY COMPLIANCE WITH SECTION 508.1.1 508.1.1 |
| | MAKEUP AIR TEMPERATURE. |
| | THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE |
| | AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F |
| | (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS |
| | OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE |
| | HVAC SYSTEM. |
| | |
| | 5) SUBMIT THE MIAMI-DADE NOA'S FOR THE EXHAUST AND |
| | MAKEUP AIR FANS- RULE 9N-3 FAC. |
| | |
| | 6) THE PERMIT VALUE OF $13,385.00 APPEARS LOW FOR THE |
| | SCOPE OF THE PROJECT. PLEASE PROVIDE ESTIMATES AND/OR |
| | SIGNED CONTRACTS FOR THE ENTIRE KITCHEN EXHAUST HOODS |
| | PROJECT INCLUDING LABOR, MATERIALS, AND EQUIPMENT- |
| | SECTION 109.3 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |