2018-11-13 09:04:056.2.2.2* THIS PROTECTION SHALL BE PERMITTED TO BE
 ACCOMPLISHED
 BY THE INSTALLATION OF A STEEL OR STAINLESS STEEL
 BAFFLE
 PLATE BETWEEN THE HEAT SOURCE AND THE GREASE REMOVAL
 DEVICE.
 6.2.2.3 THE BAFFLE PLATE SHALL BE SIZED AND LOCATED SO
 THAT
 FLAMES OR COMBUSTION GASES TRAVEL A DISTANCE NOT LESS
 THAN
 457 MM (18 IN.) FROM THE HEAT SOURCE TO THE GREASE
 REMOVAL
 DEVICE.
 6.2.2.4 THE BAFFLE SHALL BE LOCATED NOT LESS THAN 152
 MM (6 IN.)
 FROM THE GREASE REMOVAL DEVICE.
  
  
 FINAL REVIEW AND TESTING SUBJECT TO FIELD INSPECTION