Plan Review Notes
Plan Review Notes For Permit 18100795
Permit Number 18100795
Review Stop P
Sequence Number 3
Notes
Date Text
2019-03-26 14:39:44PLUMBING 3RD REVIEW**DENIED**
  
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS &
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1) PLUMBING SHEETS P1.01 AND P1.02 ARE STILL NOT SIGNED
 DIIGITALLY SIGNED AS STATED IN F.A.C RULE 61G1-16.005
  
 2) POWER BATHROOM FITTING APPEAR TO BE BACKWARDS.
 FITTING MUST BE INSTALLED IN DIRECTION OF FLOW. FBC
 706.3
  
 3) THE POWER BATH TOILET IS NOT PERMITTED TO BE WET
 VENTED INTO THE BUILDING DRAIN. ONLY OTHER BATHROOM
 FIXTURES UP TO 2 AND ON THE SAME SAME FLOOR ARE
 PERMITTED TO DRAIN INTO THE BATHROOM WET VENT
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
  
  