| 2019-03-26 14:32:01 | GAS 3RD REVIEW**DENIED**? |
| | |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS & |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | 1) SHT. P1.01 AND P1.02 ARE STILL NOT SIGNED |
| | ELECTRONICALLY AS PER F.A.C RULE 61G1-16.005 |
| | |
| | 2) PROVIDE A GAS ISOMETRIC DRAWING. FBC 107.3.5.SUBMIT |
| | AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH OF |
| | ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL GAS, SECS. |
| | 402.4.1, 402.4.2. OR 2017 FBC-RES SEC. G2413.4.1, |
| | G2413.4.2. |
| | |
| | 3) PROVIDE SIZING CHART FOR GAS PIPING AFTER THE |
| | PRESSURE REGULATOR FOR THE 1/2LB SYSTEM AND SHOW |
| | DISTANCE.) SUBMIT TWO COPIES OF THE APPLICABLE SIZING |
| | TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON |
| | THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) |
| | FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN |
| | THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 |
| | FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES |
| | 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC. |
| | G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3 |
| | |
| | 4) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC. |
| | G2421.1. |
| | |
| | 5) PROVIDE GAS COOK TOP MANUFACTURE INSTALLATION MANUAL |
| | SHOWING IT IS LISTED AND LABELED. FBC-R G2404.3 |
| | |
| | 6) GAS FLAT DRAWING SHOW'S GAS METER AS HAVING 3 OULET |
| | PORTS. PER GAS PROVIDER THERE IS NOT SUCH METER ON THE |
| | MARKET AND IT ONLY HAS 1 INLET AND 1 OUTLET. PROVIDE A |
| | CORRECT FLAT DRAWING SHOWING CORRECT PIPING |
| | ORIENTATIONS AND PIPE SIZE'S AND MATERIAL FROM THE |
| | METER TO THE NEW GAS COOK TOP. 2017 FBC-FUEL GAS, SECS. |
| | 402.4.1, 402.4.2. OR 2017 FBC-RES SEC. G2413.4.1, |
| | G2413.4.2. |
| | |
| | |
| | PLEASE FEEL FREE TO CONTRACT THIS PLAN REVIEW SO THAT I |
| | CAN ASSIST YOU IN COMPLYING |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER |
| | BUILDING DIVISION |
| | CITY OF WEST PALM BEACH |
| | 401 CLEMATIS STREET, 1ST FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | 561-248-2703 |
| | [email protected] |
| | |
| | |