| 2019-04-01 13:19:14 | ELECTRICAL PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2ND REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. SMOKE DETECTORS ARE RECIEVING POWER FROM TWO |
| | SEPERATE SERVICE PANELS, CIRCUT 36 ON PANEL (N) K AND |
| | CIRCUT 5 ON PANEL (E) NP. |
| | R314.4 INTERCONNECTION. |
| | WHERE MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE |
| | INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT IN |
| | ACCORDANCE WITH SECTION R314.3, THE ALARM DEVICES SHALL |
| | BE INTERCONNECTED IN SUCH A MANNER THAT THE ACTUATION |
| | OF ONE ALARM WILL ACTIVATE ALL OF THE ALARMS IN THE |
| | INDIVIDUAL DWELLING UNIT. PHYSICAL INTERCONNECTION OF |
| | SMOKE ALARMS SHALL NOT BE REQUIRED WHERE LISTED |
| | WIRELESS ALARMS ARE INSTALLED AND ALL ALARMS SOUND UPON |
| | ACTIVATION OF ONE ALARM. |
| | |
| | 2. IT APPEARS SOME SMALL APPLIANCES ARE NOT INCLUDED IN |
| | LOAD CALCULATION. |
| | PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. |
| | NEC 220; FBC RE E3602.2. |
| | |
| | 3. COMPACTOR ON PANEL K IS NOT INCLUDED IN LOAD |
| | CALCULATION. LOADS NOT INCLUDED IN SQ. FTG. CALC. SHALL |
| | BE LISTED ON PANEL SCHEDULE. |
| | PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING |
| | AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS |
| | ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2. |
| | |
| | 4. WALL OVEN IS NOT INCLUDED IN LOAD CALC. |
| | PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. |
| | NEC 220; FBC RE E3602.2. |
| | |
| | 5. PROVIDE PANEL LOAD CALCULATIONS FOR NEW PANEL K. |
| | PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. |
| | NEC 220; FBC RE E3602.2. |
| | |
| | 6. PROVIDE REVISED LOAD CALCULATIONS FOR MAIN SERVICE |
| | PANEL H BASED ON THE ADJUSTMENTS MADE, (SEE ABOVE). |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |
| | |