Plan Review Notes
Plan Review Notes For Permit 18100795
Permit Number 18100795
Review Stop B
Sequence Number 1
Notes
Date Text
2018-12-05 15:02:58****CORRECTIONS****
 W.P.B. PERMIT: 18100795
 REVIEWED: DECEMBER 5, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC R301.2.1.2]INDICATE MODEL OF CASEMENT WINDOW
 AND IMPACT LEVEL BY UPLOADING FLORIDA PRODUCT APPROVAL.
 LOOK IN FL-13145 AND SELECT THE APPLICABLE ONE FOR YOUR
 WINDOWS.
  
 2. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVALS FOR
 FIXED WINDOWS, AND FRENCH DOORS, OR INDICATE THAT YOU
 WOULD LIKE THEM DEFERED.
 THE CCL THAT IS UPLOADED DOESN'T PROVIDE IMPACT
 INFORMATION.
 PLEASE UPLOAD ALL PRODUCT APPROVALS SPECIFIED ON A4.01
 DOOR AND WOINDOW SCHEDULE.
  
 3. [FBC R308.3]HUMAN IMPACT LOADS.
 PROVIDE CATEGORY AND LOADS FOR GLASS GUARD TO COMPLY
 WITH ON SHEET A3.05, OR INDICATE THAT IT WILL BE A
 DEFERRED SUBMITTAL.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  