| Date |
Text |
| 2018-12-05 14:33:45 | ALEX SUBMITTED RAS 117 CALCULATIONS VIA E-MAIL. | | | | | | INFORMATION SUBMITTED DOESN'T ADDRESS PREVIOUS | | | COMMENTS. SEE COPY OF COMMENTS BELOW. CONTACT ME TO | | | COORDINATE. | | | | | | | | | ORIGINAL COMMENT: | | | 1- FLAT ROOF RAS 117 CALCULATIONS SUBMITTED. | | | CALCULATIONS FOR CORNER AREAS IS INCORRECT. THE | | | SPECIFIED DESIGN-PRESSURES ARE -132.6 PSF BUT MAX. | | | FASTENER SPACING CALCULATIONS ARE DONE FOR 110.7 PSF. | | | REVISE AS REQUIRED. REVISE NUMBER OF REQUIRED ROWS | | | ACCORDINGLY. SEC. R301.1 FBC-RESIDENTIAL. | | | | | | RESPONSE: | | | THE CALCULATIONS WERE REVISED, BUT THE BASE SHEET | | | FASTENING INFORMATION WAS NOT REVISED. THE NUMBER OF | | | ROWS NEED TO BE REVISED ALSO. SEC. R301.1 | | | FBC-RESIDENTIAL. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|