| 2018-12-10 15:20:22 | 12/10/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. CSST 2 LBS TABLE WAS NOT SUPPLIED ON P-2 NOTES. WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE. THE SIZE ON THE EHD CSST MUST BE |
| | LABELED AND AT THIS MOMENT IT MAY NOT BE PROPERLY |
| | SIZED. WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 4. SECOND REQUEST, SUBMIT MANUFACTURES SPECIFICATIONS |
| | FOR THE GRILL, TANK-LESS WATER HEATER AND DRYER. 2017 |
| | FBC-RES. SEC.G2408.1. |
| | 5. SECOND REQUEST, SUBMIT MANUFACTURER?S SPECIFICATIONS |
| | FOR THE PRESSURE REGULATORS. REGULATORS INSTALLED ON |
| | THE EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR |
| | OUTDOOR INSTALLATION, 2017 FBC FUEL GAS RES. SEC. |
| | G2421.1. |
| | 6. SECOND REQUEST, SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR PER THE (CLOTHES DRYERS), 2017 FBC FUEL GAS RES. |
| | SEC. G2407.1 AND G2439.4 (CLOTHES DRYERS). |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |