Plan Review Notes
Plan Review Notes For Permit 18100747
Permit Number 18100747
Review Stop G
Sequence Number 1
Notes
Date Text
2018-10-31 08:24:0311/01/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE INDICATE ON PLANS WHAT CODE CYCLE IS BEING
 USE (E.G. 2017 FBC FUEL GAS 6TH EDITION)
 2. SHOW ALL PIPE SIZES FOR EACH PIPE SIZE, WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 3. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANK-LESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS, WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
 4. SUBMIT MANUFACTURES SPECIFICATIONS FOR THE GRILL,
 TANK-LESS WATER HEATER AND DRYER. 2017 FBC-RES.
 SEC.G2408.1.
 5. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION, 2017 FBC FUEL GAS RES. SEC. G2421.1.
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 (CLOTHES DRYERS), 2017 FBC FUEL GAS RES. SEC. G2407.1
 AND G2439.4 (CLOTHES DRYERS).
 7. SHOW UNIONS FOR REGULATORS ON ISOMETRIC DRAWING,
 2017 FBC FUEL GAS RES SECS. G2413.4.1, G2413.4.2
 8. REGULATOR NOT DRAWN IN ON ISOMETRIC FOR FIRST HOT
 WATER TANK-LESS, SHOW THE LOCATION OF ALL (STEP-DOWN)
 REGULATORS. A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH REGULATOR, 2017 FBC FUEL GAS
 RES. SEC. G2420.4.
 9. A SUB GAS PERMIT IS REQUIRED, WPB AMENDMENTS TO THE
 FBC SEC. 105.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  