| 2018-10-31 08:24:03 | 11/01/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE INDICATE ON PLANS WHAT CODE CYCLE IS BEING |
| | USE (E.G. 2017 FBC FUEL GAS 6TH EDITION) |
| | 2. SHOW ALL PIPE SIZES FOR EACH PIPE SIZE, WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | 3. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANK-LESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS, WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 4. SUBMIT MANUFACTURES SPECIFICATIONS FOR THE GRILL, |
| | TANK-LESS WATER HEATER AND DRYER. 2017 FBC-RES. |
| | SEC.G2408.1. |
| | 5. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION, 2017 FBC FUEL GAS RES. SEC. G2421.1. |
| | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| | (CLOTHES DRYERS), 2017 FBC FUEL GAS RES. SEC. G2407.1 |
| | AND G2439.4 (CLOTHES DRYERS). |
| | 7. SHOW UNIONS FOR REGULATORS ON ISOMETRIC DRAWING, |
| | 2017 FBC FUEL GAS RES SECS. G2413.4.1, G2413.4.2 |
| | 8. REGULATOR NOT DRAWN IN ON ISOMETRIC FOR FIRST HOT |
| | WATER TANK-LESS, SHOW THE LOCATION OF ALL (STEP-DOWN) |
| | REGULATORS. A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH REGULATOR, 2017 FBC FUEL GAS |
| | RES. SEC. G2420.4. |
| | 9. A SUB GAS PERMIT IS REQUIRED, WPB AMENDMENTS TO THE |
| | FBC SEC. 105. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6720 |
| | |