| Plan Review Notes For Permit 18100677 |
| Permit Number |
18100677 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-02-16 11:42:23 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. SEE PREVIOUS LIST. THIS APPEARS TO BE LOCATED IN | | | EXPOSURE D, REVISE OR HAVE ENGINEER SEND AN EMAIL TO | | | EXPLAIN RATIONALE FOR EXPOSURE C, FBC B 1609. | | | | | | 2. THE PRODUCT APPROVAL IS TO BE REVIEWED BY DESIGNER | | | OF RECORD, FBC 107. IT IS EXPIRED (2014 RATHER THAN | | | 2017 CODE), FBC B 1609. |
|