| Date |
Text |
| 2018-11-21 09:10:23 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 18100677 |
| | ADD: 3901 S FLAGLER DR. SUITE: 401 |
| | CONT: PM WRIGHT CONSTRUCTION (CBC058843) |
| | TEL: 561-863-5088 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. NOV. 21/2018 |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION AND FLOOR PLAN A-1 BOTH |
| | INDICATE THE REMOVAL AND INSTALLATION OF A NEW EXTERIOR |
| | DOOR AND FRAME. THE PLANS ARE SILENT AS TO THE BUILDING |
| | HEIGHT, NOR DOES THE PLANS SHOW THIS UNIT IN REGARDS TO |
| | THE OVERALL FLOOR PLAN FOR THE BUILDING. THIS BUILDING |
| | IS A 10 STORY HIGH-RISE AND THE BUILDING (TENANT UNIT) |
| | MAYBE LOCATED IN EXPOSURE D. WE NEED THE FLOORPLAN OF |
| | THE BUILDING IDENTIFYING THE UNIT TO SEE IF THE |
| | LOCATION WILL BE EXPOSURE D AND TO SEE IF THE DOOR IS |
| | LOCATED IN A WALL ZONE 5. |
| | |
| | SINCE THIS IS A 10 STORY HIGH-RISE THE WIND LOADS ON |
| | EVERY BUILDING SHALL BE DETERMINED IN ACCORDANCE WITH |
| | CHAPTER 30 OF ASCE7-10. THE PRESSURES WILL NEED TO BE |
| | CALCULATED BY A STRUCTURAL ENGINEER, NOT THE |
| | CONTRACTOR. |
| | |
| | PLEASE SHOW COMPLIANCE WITH: 2017 FBC-B 1603.1.4 WIND |
| | DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | |
| | 1.2. RISK CATEGORY. |
| | |
| | 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. |
| | |
| | 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | |
| | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |