| 2019-01-23 15:45:42 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | |
| | NOTE: |
| | THERE ARE SOME PRODUCT APPROVALS THAT WERE CHANGED FROM |
| | PREVIOUS REVIEWS. I TOLD DAVID BOWDEN TO TAKE BACK ALL |
| | PRODUCT APPROVALS AND RESUBMIT ONLY THE ONES THAT ARE |
| | GOING TO BE INSTALLED TO AVOID CONFLICTS/DELAYS. ALSO, |
| | I TOLD HIM TO IDENTIFY ON ALL PRODUCT APPROVALS THE |
| | LOCATION OF PRODUCT APPROVALS SUBMITTED. FOR EXAMPLE, |
| | ENTRY DOOR, STAIRWAY WINDOWS, ETC. |
| | |
| | 1-PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: |
| | |
| | A) BALCONY UNDERLAYMENT THAT IS DESIGNED TO BE |
| | INSTALLED WITH FINISH FLOOR SPECIFIED ON PLANS. NOTE: |
| | FLINTASTIC MODIFIED BITUMEN ROOF SYSTEM PRODUCT |
| | APPROVAL FL16709-R4 SPECIFIED ON BALCONY FLOOR |
| | CONSTRUCTION DETAIL ON SHEET A-010 IS NOT GOOD FOR |
| | CERAMIC TILE. |
| | |
| | B) SLIDING GLASS DOORS WITH TRANSOM ABOVE AS SHOWN ON |
| | PLANS/ELEVATIONS. |
| | |
| | C) CASEMENT WINDOWS SIZE AS SPECIFIED ON WINDOW |
| | SCHEDULE. SEE PLANS/ELEVATIONS. |
| | |
| | D)OUTSWING ENTRY DOORS WITH SIDELITES AS SHOWN ON |
| | PLANS/ELEVATIONS. |
| | |
| | E) WINDOW MULLIONS AS SHOWN ON PLANS. REQUIRED: CLEARLY |
| | SPECIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE |
| | WITH THE CALCULATED DESIGN PRESSURES. |
| | |
| | 2) DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 3- ENERGY CALCULATIONS SUBMITTED (RESCHECK): |
| | A) LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND |
| | SHGC FACTOR IS REQUIRED. |
| | B) BLOWER DOOR TEST WILL BE REQUIRED. |