2018-11-08 10:22:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW: DENIED
 COMMENTS:
 1. RE: SANITARY RISER DIAGRAM
 A) LIBERTY #404 DRAIN PUMP IS SHOWN IN THE CEILING.
 THERE IS A NEW 2" GRAVITY DRAIN CONNECTING THE SINK TO
 EXISTING SANITARY. THE NEW VENT RISES AND CONNECTS TO
 THE DRAIN PUMP, THEN CONNECTS FROM DRAIN PUMP TO
 EXISTING VENT. THERE IS A 2" (DRAIN/DISCHARGE?)
 INTERSECTING WITH THE GRAVITY DRAIN, TRAPPED FIXTURE
 DRAIN AND VENT. IT SHOULD BE NOTED THAT THE DRAIN PUMP
 IS DESIGNED TO RECEIVE WASTE BY GRAVITY FROM FIXTURES
 AND THEN DISCHARGE TO A GRAVITY DRAIN IN ACCORDANCE
 WITH REQUIREMENTS OF FBC PL SECTION 712 AND FBC PL
 906.5.1. PLEASE CLARIFY.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
  
  