2018-11-19 12:04:43BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- MISSING EXIT SIGN BETWEEN THE OPEN OFFICE AREA AND
 BREAK ROOM. SEC. 1013.1 FBC
  
 2- CLARIFY DIRECTION OF EGRESS DOOR LOCATED ON THE EAST
 SIDE BY THE STAIRWAY. ACCORDING TO APPROVED PERMIT
 #12030212 THE DOOR SWING OF THIS DOOR WAS IN THE
 DIRECTION OF TRAVEL (OUT SWING). REVISE AS REQUIRED.
 SEC. 1010.1.2.1 FBC.
  
 3- PROVIDE THE OCCUPANT LOAD FOR TENANT SPACE LOCATED
 IN THE SOUTH WEST CORNER TO VERIFY COMPLIANCE WITH THE
 SWING OF THE DOUBLE EGRESS DOOR. SEC. 1010.1.2.1 FBC.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
  