| 2018-11-19 05:33:02 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. INITAL PERMIT FEE SUBMITTED WAS $20000. CONTRACTOR |
| | WAS ASKED FOR SIGNED CONTRACT. SCOPE OF WORK PROVIDED |
| | IN CONTRACT DOES NOT MATCH SCOPE OF WORK ON PLANS. |
| | PROVIDE ACCURATE PLANS AND AN UP TO DATE CONTRACT. |
| | CONTRACT SAYS SA- X10, SB X2 |
| | |
| | PLANS SAY SB X1, SA X5, CA X10. FBC 107.2.1 |
| | |
| | 2. NO LOAD CALCULATION PROVIDED, NO OCP PROVIDED FOR |
| | PANEL FEEDING SITE LIGHTS., ACCURATE LOAD CALCULATION |
| | INCLUDING ALL LOADS. NEC 220, FBC 107.2.1 |
| | |
| | 3. PROVIDE EXTERIOR AUTOMATIC LIGHTING CONTROL FOR SITE |
| | LIGHTING AS PER FBC CE 405.2.4 MUST BE ASTRONOMICAL |
| | TIME CLOCK WITH 10/HR BATTERY BACKUP. A NOTE ON DRAWING |
| | WILL SUFFICE. |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |