2019-01-02 14:34:49MECHANICAL PLAN REVIEW PASS WITH PROVISO (SEE PLANS)
  
 R303.10REQUIRED HEATING.WHERE THE WINTER DESIGN
 TEMPERATURE IN TABLE R301.2(1) IS BELOW 60?F (16?C),
 EVERY DWELLING UNIT SHALL BE PROVIDED WITH HEATING
 FACILITIES CAPABLE OF MAINTAINING A ROOM TEMPERATURE OF
 NOT LESS THAN 68?F (20?C) AT A POINT 3 FEET (914 MM)
 ABOVE THE FLOOR AND 2 FEET (610 MM) FROM EXTERIOR WALLS
 IN HABITABLE ROOMS AT THE DESIGN TEMPERATURE. THE
 INSTALLATION OF ONE OR MORE PORTABLE SPACE HEATERS
 SHALL NOT BE USED TO ACHIEVE COMPLIANCE WITH THIS
 SECTION.
  
  