| 2018-12-04 09:12:38 | 1ST REVIEW: |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. RE: PLAN SHEET E-1, SANITARY RISER DIAGRAM |
| | A) MASTER BATH; THE DRY VENTS AT THE SHOWER AND THE TWO |
| | LAVATORIES EXTEND HORIZONTALLY BEFORE RISING |
| | VERTICALLY. THIS IS PROHIBITED PER FBC RES P3104.3. |
| | B) MASTER BATH; THE FIXTURE DRAINS FOR THE SHOWER AND |
| | BOTH LAVATORIES RISE VERTICALLY ABOVE THE VENT BEFORE |
| | CONNECTING TO THE TRAP. THIS IS PROHIBITED PER FBC RES |
| | P3105.2 AND P3201.5.3. |
| | C) BATH #2; THE FIXTURE DRAIN FOR THE SHOWER RISES |
| | VERTICALLY ABOVE THE VENT BEFORE CONNECTING TO THE |
| | TRAP. THIS IS PROHIBITED PER FBC RES P3105.2 AND |
| | P3201.5.3. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |