| 2018-12-03 13:58:11 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18100634 |
| | REVIEWED: NOVEMBER 30, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC A = FBC ACCESSIBILITY |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. [FBC 107.3.5.3]PROVIDE SEDIMENT CONTROL TO KEEP |
| | CONSTRUCTION DEBRIS FROM ENTERING ADJACENT PROPERTIES |
| | AND STORM DRAINS DURING CONSTRUCTION. |
| | YOU CAN JUST ADD SILT FENCE DETAIL AND HOW DRAINS ARE |
| | PROTECTED TO THE DRAINAGE PLAN. |
| | SOME ENGINEERING STANDARD DETAILS CAN BE USED FROM WPB |
| | WEBSITE-POLLUTION CONTROL. |
| | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS |
| | /FORMS,-PERMITS-APPLICATIONS |
| | |
| | 2. [FBC 107.5][FBC 110.9][FBC R401.3][PROVIDE SITE |
| | DRAINAGE PLAN. |
| | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| | DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN |
| | SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE |
| | SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE |
| | FIRST 10 FEET (3048 MM). |
| | EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| | PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL |
| | WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE |
| | CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. |
| | IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE |
| | BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 |
| | PERCENT AWAY FROM THE BUILDING. |
| | THIS CAN BE SHOWN ON THE SITE PLAN THAT IS REQUESTED |
| | FROM |
| | |
| | 3. [FBC R807]CO-ORDINATE ATTIC ACCESS SHOWN ON SHEET A1 |
| | WITH TRUSS LAYOUT ON SHEET S2. SHEET A1 SHOWS ACCESS |
| | CENTERED IN RROM, BUT SHEET S2 SHOWN TRUSS DOWN THE |
| | CENTER OF ROOM. |
| | |
| | 4. [FBC R806.5]UNVENTED ATTIC AND UNVENTED ENCLOSED |
| | RAFTER |
| | ASSEMBLIES. UNVENTED ATTICS AND UNVENTED ENCLOSED ROOF |
| | FRAMING ASSEMBLIES CREATED BY CEILINGS THAT ARE APPLIED |
| | DIRECTLY TO THE UNDERSIDE OF THE ROOF FRAMING MEMBERS |
| | AND |
| | STRUCTURAL ROOF SHEATHING APPLIED DIRECTLY TO THE TOP |
| | OF THE ROOF |
| | FRAMING MEMBERS/RAFTERS, SHALL BE PERMITTED WHERE ALL |
| | THE FOLLOWING |
| | CONDITIONS ARE MET: |
| | A. THE UNVENTED ATTIC SPACE IS COMPLETELY WITHIN THE |
| | BUILDING THERMAL ENVELOPE. |
| | SHEET A-3 NOTE SAYS FOAM INSULATION AND NO VENTS. IF NO |
| | VENTS THE ATTIC SPACE NEEDS TO BE IN THE THERMAL |
| | ENVELOPE. ICYNENE OR EQUIVALENT WOULD BE APPLIED UNDER |
| | ROOF DECK. |
| | IF IT IS TO BE ON THE ATTIC BOTTOM CHORD PROVIDE VENT |
| | CALCULATIONS FOR THE ATTIC SPACE. |
| | |
| | 5. [FBC R302.10]PROVIDE CUT SHEET FOR ICYNENE(ICC-ES |
| | REPORT OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH |
| | THICKNESS NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD |
| | INDEX AND SMOKE DEVELOPED INDEX. |
| | |
| | 6. [FBC R316.5.3]IF MECHANICAL EQUIPMENT IN THE ATTIC |
| | SPACE THAN IT REQUIRES IGNITION BARRIER. IF AIR HANDLER |
| | WILL BE IN ATTIC ADD NOTE FOR IGNITION BARRIER. |
| | |
| | 7. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVAL FOR |
| | WINDOW MULL TO GO WITH SINGLE HUNG WINDOW NOA |
| | 17-0630.08 |
| | |
| | 8. [FBC AMENDED 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS TO |
| | THE BUILDING INSPECTOR PRIOR TO INSTALLATION. |
| | THIS WILL BE A PROVISO ITEM THAT DOES NOT NEED TO BE |
| | ADDRESSED. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | |