2021-08-24 17:08:58BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 18100540
 550 N. QUADRILLE BLVD.
 BUILDING PERMIT 30 STORY BLDG W/ TWO TOWERS
 CONSTRUCTION TYPE: 1A, SPRINKLERED
 MIXED OCCUPANCY: B, R-1, R-2, A-2, A4, S-2, M, E
  
 1 ST REVIEW: APRIL 18, 2019 - DYLAN BATTLES
 2 ND REVIEW: MARCH 2, 2020 - DYLAN BATTLES
 3 RD REVIEW: JANUARY 13, 2021 - ROBERT MCDOUGAL
 4 TH REVIEW: JUNE 10, 2021 - ROBERT MCDOUGAL
 5 TH REVIEW: AUGUST 23, 2021 - ROBERT MCDOUGAL
  
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 FLORIDA BUILDING CODE,5TH EDITION (2014)
 FBC[AMENDED] = 2014 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
  
 BUILDING REVIEW COMMENTS:
  
 1) RESOLVED.
  
 A) RESOLVED.
  
 B) RESOLVED.
  
 C) RESOLVED.
  
 D) RESOLVED.
  
 E) RESOLVED.
  
 F) RESOLVED.
  
 G) RESOLVED.
  
 H) RESOLVED.
  
 2) RESOLVED.
  
 3) RESOLVED.
  
 4) RESOLVED.
  
 5) RESOLVED.
  
 6) RESOLVED.
  
 FAIRHOUSING REVIEW:
  
 7) RESOLVED.
  
 A) RESOLVED.
  
 B) RESOLVED.
  
 C) RESOLVED.
  
 D) RESOLVED.
  
 E) RESOLVED.
  
 F) RESOLVED.
  
 LIFE SAFETY:
  
 8) RESOLVED.
  
 9) RESOLVED.
  
 10) RESOLVED.
  
 11) RESOLVED.
  
 12) RESOLVED.
  
 13) RESOLVED.
  
 14) RESOLVED.
  
 15) RESOLVED.
  
 16) NOT COMPLETELY RESOLVED. [RAMP 4 STILL DOES NOT
 COMPLY.] [ RAMP 4 ON A1.228 IS REQUIRED TO HAVE A
 LANDING WITH 60" X 60" CLEAR SPACE AT THE CHANGE IN
 DIRECTION. RAMP 8 ON 5.123 REQUIRES A 60" (5') CLEAR
 LANDING AND THE DRAWING HAS 59" (4'-11"). FBC-A 405.7]
 THERE ARE SEVERAL RAMPS SHOWN ON THE PLANS. PLEASE
 IDENTIFY EACH WITH AN ID TAG AND PROVIDE DETAILS FOR
 EACH OF THEM TO SHOW THAT THEY MEET THE ACCESSIBILITY
 REQUIREMENTS FOR RAMPS. FBC ACCESSIBILITY 405. 1003.5
 FBC[B] ELEVATION CHANGE. DOES EXIT FROM RESIDENT LOBBY
 TO STAIR 2 HAVE STEPS? PLEASE REVIEW
 -HOW DO STEPS WORK AT EGRESS FROM RESIDENT LOUNGE TO
 STAIR ST2? PLEASE REVIEW 1003.5 FOR CHANGE IN ELEVATION
 IN PATH OF EGRESS.
  
 17) RESOLVED.
  
 18) RESOLVED.
  
 19) RESOLVED.
  
 20) RESOLVED.
  
 DEFERRED SUBMITTALS
 21) RESOLVED. SEE SHEET A0.001 FOR LIST OF DEFERRED
 ITEMS.
  
 22) DEFERRED.
  
 23) RESOLVED.
  
 ACCESSIBILITY REVIEW:
  
 24) RESOLVED.
  
 25) RESOLVED.
  
 26) RESOLVED. THE POOL DRAWINGS 13.001-SP.001 THRU
 13.033-SP.750 ARE NOT LISTED IN THE INDEX OF PLANS.
 SEPARATE POOL/SPA PERMITS WILL BE REQUIRED FOR THE (3)
 POOLS/SPAS.
  
 27) RESOLVED.
  
 CHAPTER 4 - HIGHRISE:
  
 28) RESOLVED.
  
 29) RESOLVED.
  
 30) RESOLVED. BUILDING IS LESS THAN 420 FEET IN HEIGHT.
  
 NEW COMMENTS:
  
 31) RESOLVED.
  
 32) RESOLVED.
  
 33) RESOLVED.
  
 34) RESOLVED.
  
 35) NOT RESOLVED. [THE EXITS STILL DO NOT COMPLY.] [
 BASED ON THE NUMBERS THAT YOU HAVE PROVIDED (487 OCC.)
 THE CAPACITY OF THE TWO EXISTS THAT ARE PROVIDED ARE
 NOT ADEQUATE FOR THE OCCUPANT LOAD OF THIS AREA. SEE
 FBC SECTIONS 1004, 1005 AND 1006. FBC 1005.5
 DISTRIBUTION OF EGRESS CAPACITY WHERE MORE THAN ONE
 EXIT, OR ACCESS TO MORE THAN ONE EXIT, IS REQUIRED, THE
 MEANS OF EGRESS SHALL BE CONFIGURED SUCH THAT THE LOSS
 OF ANY ONE EXIT, OR ACCESS TO ONE EXIT, SHALL NOT
 REDUCE THE AVAILABLE CAPACITY TO LESS THAN 50 PERCENT
 OF THE REQUIRED CAPACITY. CHECK THE AREA AND OCCUPANT
 LOAD AND PROVIDE CODE COMPLIANT EGRESS. ]
 ON PAGE 04.024 -ALS1.109, SHOW THE TOTAL OCCUPANT LOAD
 OF THE TERRACE AND PICKLE BALL COURTS, THE LOADS AT
 EACH EXIT DOOR AND THE COMBINED LOADS AT THE HOTEL AND
 RESIDENT EXIT STAIRWAYS. FBC 1004
  
 36) RESOLVED.
  
 37) RESOLVED.
  
 38) RESOLVED.
  
 39) RESOLVED.
  
 40) RESOLVED.
  
 41) RESOLVED.
  
 42) RESOLVED.
  
 43) DEFERRED. PER THE DESIGNER THE SALES AND SERVICE
 COUNTERS DRAWINGS AND DETAILS WILL BE PROVIDED FOR
 APPROVAL AT A LATER DATE. NOT RESOLVED. [THE ONLY PLAN
 SHEET I SAW WAS ID7.010 SUBMITTED AS AN ATTACHED
 SUPPLEMENTAL DOCUMENT. IT ONLY HAS THE RECEPTION DESKS
 FOR THE HOTEL AND THE RESIDENTIAL UNITS. SALES AND
 SERVICE COUNTERS ARE REQUIRED TO COMPLY WITH
 FBC-ACCESSIBILITY 904.4 SALES COUNTERS AND SERVICE
 COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2. THE
 ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND THE
 SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP. THE
 SHEET IS NOT SIGNED AND SEALED. WHAT ABOUT THE OTHER
 COMMON AREA ITEMS?] I DID NOT SEE THE
 DETAILS/ELEVATIONS OF BUILT-IN ITEMS IN THE COMMON USE
 AREAS, SUCH AS RECEPTION DESKS, SERVICE COUNTERS, BREAK
 ROOM KITCHENS, ETC. THAT ARE REQUIRED TO BE ACCESSIBLE
 PER FBC ACCESSIBILITY CHAPTERS 8 AND 9. PLEASE INDICATE
 SHEETS THEY ARE ON OR PROVIDE SHEETS WITH DETAILS AND
 ELEVATIONS FOR THESE ITEMS.
  
 44) NOTE: ADDITIONAL COMMENTS MAY RESULT FROM THE
 RESPONSES TO THESE PLAN REVIEW COMMENTS.
  
 -PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW EACH
 COMMENT IS BEING ADDRESSED.
 -FEEL FREE TO CONTACT ME AT 561-805-6714 (M-F 8-5) TO
 DISCUSS COMMENTS, OR E-MAIL ANYTIME [email protected]
  
 NOTE: SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES)
 ARE REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS AND SPAS
 GENERATORS
 ALL OTHER ITEMS OTHER THAN BMEP
  
  
  
  
  
  
  
  
  
  
  
  