Plan Review Notes
Plan Review Notes For Permit 18100540
Permit Number 18100540
Review Stop P-GREASE
Sequence Number 4
Notes
Date Text
2021-06-21 15:54:54ON SHEET 804, DETAIL #2 OF NOTE TWO HAS SPECIFIED A
 SCHIER 250 GALLONS. WHY IS THIS SPECIFIED? HOW DID YOU
 DETERMINE THE USAGE OF THE RESTAURANT UNITS WITH
 RESPECT TO THE RESTAURANT CAPACITY? HOW IS THIS
 INFORMATION PROVIDED? IF SCHIER PROVIDED THESE
 CALCULATIONS OR WILL ASSIST IN SIZING, PLEASE NOTE IN
 DETAIL TWO HOW THE ENGINEERED SYSTEM IS TO COMPLY.
 PLEASE PUT A NOTE RESPONSE OF P100 ON P 804 DETAIL 2. I
 SPOKE TO SCHIER'S REP, AND THEY ARE WILLING TO HELP IN
 ALL CALCULATION ASSISTANCE REQUIRED; IF HE NEEDS TO
 CONTACT YOU, MAY LEE @ 561 632-3123, FYI.