| 2021-06-21 15:54:24 | 06/21/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. NO RESPONSE TO THIS?SHEET C.03 SHOWS A 15-INCH PVC |
| | RWL NEAR THE PROPERTY'S SOUTHWEST CORNER NEAR THE BUS |
| | STOP. THE LINE IS NOT SHOWN ON SHT. P100 (NEAR COLUMN |
| | LINE #1). CLARIFY. |
| | |
| | 2. DONE. |
| | |
| | 3. DONE. |
| | |
| | 4. DONE. |
| | |
| | 5. DONE. |
| | |
| | 6. SHEET A1.502A - DETAIL #2 DOES NOT SHOW A SEAT IN |
| | THE SHOWER, AND DETAIL #3 SHOWS A SEAT. CLARIFY. |
| | |
| | THE SEAT DRAWN IN IS A SIDE SEAT, AND THE ONE ON THE |
| | ADA FUTURE IS THE BACK SEAT. PLEASE CORRECT AS BACKING |
| | DETAIL IS REQUIRED AND PROVIDED PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 7. DONE. |
| | |
| | 8. DONE. |
| | |
| | 9. DONE. |
| | |
| | 10. THIS ITEM HAS NOT BEEN ADDRESSED, SHEET A1.600 - |
| | DETAIL #1 - WOMEN'S RESTROOM - THE PLAN STATES A CLEAR |
| | FLOOR SPACE OF 60 INCHES WIDE FOR THE ACCESSIBLE STALL, |
| | BUT THE PLAN ALSO SHOWS THE CLEAR INSIDE WIDTH 4 FEET |
| | 11 1/2 INCHES. IF THIS IS A ROUGH DIMENSION, THEN THIS |
| | STALL WILL NOT BE WIDE ENOUGH AFTER THE FINISH. COMPLY |
| | WITH FBC-ACCESS. SEC.604.3.1.2ND REQUEST. CLARIFY. |
| | |
| | 11. THIS ITEM HAS NOT BEEN ADDRESSED, SHEET A1.600 |
| | DETAIL #1 - MEN'S RESTROOM - ONE OF THE URINALS IS |
| | SHOWN AS 1 FOOT 2 INCHES FROM A WALL TO THE CENTERLINE |
| | OF THE URINAL. A MINIMUM OF 15 INCHES FROM A WALL TO |
| | THE CENTER OF THE URINAL IS REQUIRED. FBC-PLUMBING |
| | SEC.405.3.1. 2ND REQUEST. |
| | |
| | 12. THIS ITEM HAS NOT BEEN ADDRESSED, SHEET A1.600 - |
| | GROUND LEVEL BATHROOM #0132- IS THIS A UNISEX TOILET |
| | ROOM OR GENDER-SPECIFIC? CLARIFY. 2ND REQUEST, IT SEEMS |
| | AS THERE SHOULD BE A V3 SHEET. |
| | |
| | 13. DONE. |
| | |
| | 14. DONE. |
| | |
| | 15. DONE. |
| | |
| | 16. DONE. |
| | |
| | 17. DONE BUT NEW COMMENT; |
| | |
| | ON SHEET 606 FHA; |
| | |
| | A. DETAIL #3, DOOR IS SWINGING INTO THE CLEAR FLOOR |
| | SPACE OF THE LAVE, AND THE CLEAR FLOOR SPACE IS NOT |
| | SHOWN FOR THE TUB. PLEASE NOTE THAT THE DISTANCE FROM |
| | THE DOOR OPENING TO THE TUB MAY BE ENCROACHING IN THE |
| | FLOOR SPACE. |
| | |
| | B. DETAIL #9 UNIT D1 SHOWS CLEAR FLOOR SPACE BUT NOT AN |
| | FHA UNIT; PLEASE REMOVE OR CLARIFY STATUS. |
| | |
| | ON SHEET 607 FHA; |
| | A. DETAIL #2, THE CLEAR FLOOR SPACE FOR TUB AND LAV NOT |
| | SHOWN. |
| | |
| | B. DETAIL # 3 AND #6, MASTER TUB CLEAR FLOOR SPACE NOT |
| | SHOWN. |
| | |
| | C. DETAIL # 7, LAV AND SHOW CLEAR FLOOR SPACE NOT |
| | SHOWN. |
| | |
| | ON SHEET 608 FHA; |
| | |
| | A. DETAIL #1, #4, AND 6, THE CLEAR FLOOR SPACE FOR TUB |
| | NOT SHOWN. |
| | |
| | B. DETAIL #3 UNIT B4 SHOWS CLEAR FLOOR SPACE BUT NOT AN |
| | FHA UNIT; PLEASE REMOVE OR CLARIFY STATUS. |
| | |
| | C. DETAIL #10 UNIT C1 SHOWS BACKING ON TUB AND TOILET. |
| | IS THIS AN FHA UNIT; PLEASE CLARIFY? |
| | |
| | ON SHEET 609 FHA; |
| | |
| | A. DETAIL #1, #3, AND #8, MASTER TUB CLEAR FLOOR SPACE |
| | NOT SHOWN. |
| | |
| | B. DETAIL #5 UNIT D1 SHOWS BACKING. IS THIS AN FHA |
| | UNIT; PLEASE CLARIFY? |
| | |
| | C. DETAIL #6 UNIT D3, LAV, AND TUB CLEAR FLOOR SPACE |
| | NOT SHOWN. |
| | |
| | D. DETAIL #7 UNIT D3 BATHROOM 2 & 3 SHOWS BACKING AND |
| | TOILET CLEAR FLOOR SPACE; IS THIS AN FHA? PLEASE |
| | CLARIFY. |
| | |
| | E. DETAIL 9 UNIT D4 SHOWS BACKING. IS THIS AN FHA UNIT; |
| | PLEASE CLARIFY? |
| | |
| | 18. DONE. |
| | |
| | 19. DONE. |
| | |
| | 20. DONE. |
| | |
| | 21. DONE. |
| | |
| | 22. DONE. |
| | |
| | 23. DONE. |
| | |
| | 24. DONE. |
| | |
| | 25. DONE. |
| | |
| | 26. DONE. |
| | |
| | 27. DONE. |
| | |
| | 28. THE PAGE FOR V5 DOES NOT COINCIDE WITH THE PRIOR |
| | VERSION, SHEET A1.610 - DETAIL # 2 - CLEAN UP THIS |
| | PLAN. THE LAVATORY IS SHOWN LOCATED PARTIALLY IN THE |
| | WALL. |
| | |
| | 29. THE PAGE FOR V5 DOES NOT COINCIDE WITH THE PRIOR |
| | VERSION, SHEET A1.610 - DETAIL #1 - THE FLOOR PLAN |
| | SHOWS THE DOOR SWINGING INTO THE SHOWER AND THE TOILET |
| | COMPARTMENT. THE INSWING DOOR IMPEDES ACCESS TO THE |
| | SHOWER CONTROLS AND THE TOILET AND DOES NOT COMPLY WITH |
| | FAIR HOUSING. REVERSE THE SWING OF THE DOOR. |
| | |
| | 30. THE PAGE FOR V5 DOES NOT COINCIDE WITH THE PRIOR |
| | VERSION, SHEET A1.610 - DETAIL #3 - THE NOTES AND |
| | DETAILS FOR THE GRAB BAR REINFORCEMENT DON'T MAKE |
| | SENSE. CORRECT THE DEFICIENCIES. IF THIS IS SUPPOSED TO |
| | BE AN FHA-COMPLIANT BATHROOM, SHOW ALL CLEAR FLOOR |
| | SPACES AND THE FHA BATHROOM TYPE ON THE PLAN. THE |
| | LAVATORY APPEARS TO ENCROACH INTO THE REQUIRED CLEAR |
| | FLOOR SPACE FOR THE SHOWER. PLEASE CLARIFY. |
| | |
| | 31. THE PAGE FOR V5 DOES NOT COINCIDE WITH THE PRIOR |
| | VERSION, SHEET A1.610 - DETAIL # 6 - IF THIS IS THE |
| | FHA-COMPLIANT BATHROOM, PLACE THE TYPE OF FHA BATHROOM |
| | ON THE PLAN AND CORRECT THE OVERLAY OF THE UNIT NUMBER |
| | ON THE FLOOR PLAN. PLEASE CORRECT THE OVERLAY ON DETAIL |
| | #5 ALSO. |
| | |
| | 32. THE PAGE FOR V5 DOES NOT COINCIDE WITH THE PRIOR |
| | VERSION, SHEET A1.610 - DETAIL #7 - CORRECT THIS |
| | DETAIL. THE LOCATION OF REINFORCEMENT AND CLEAR FLOOR |
| | SPACES ARE OUT OF WHACK. CONTROLS ARE CALLED OUT ON THE |
| | LAVATORY. THE BATHROOM FLOOR PLAN IS CUT OFF AND |
| | INCOMPLETE. PLEASE CLARIFY. |
| | |
| | 33. DONE. |
| | |
| | 34. THIS ITEM SEEMS TO HAVE A PIPE THAT IS NOT CLEAR TO |
| | WHERE THEY GO OR ARE ON SHEET P100. IF POSSIBLE, EXPAND |
| | THE PIPING LAYOUT FOR THE SANITARY AND VENT LINES AND |
| | TAG THE RISERS AT THE TOILET ROOMS BY ELEVATORS P03, |
| | P04, & P05 ON COLUMN LINE H. |
| | |
| | 35. DONE. |
| | |
| | 36. DONE. |
| | |
| | 38. THIS IS NOT CORRECTED; SHEET P.101B SHOWS AN 8-INCH |
| | SANITARY LINE WITHIN STAIRWAY # 4 AND A 4 INCH GW LINE |
| | IN STAIRWAY #10. THE LINE IS NOT PERMITTED WITHIN THE |
| | STAIRWAY PER FBC-BUILDING SEC.1023.5. THERE IS A CIRCLE |
| | WITH A LINE IN THIS AND ANOTHER ELEVATOR THAT WILL NEED |
| | TO BE REMOVED OR RELATED OUT OF THE STAIRWAY TO MOVE |
| | FORWARD TO A FINAL REVIEW, SO PLEASE DO YOUR BEST TO |
| | CORRECT THESE ITEMS. |
| | |
| | 39. DONE. |
| | |
| | 40. DONE. |
| | |
| | 41. THE RISER TAGS FOR THE LW R2 P 7XX RISERS ARE |
| | MISSING THE DRAWING LOCATIONS ON THE RISER TAGS. PLEASE |
| | CLARIFY PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1. |
| | PLEASE ALSO CLARIFY ANY ABOVE FLOORS IN POD C AND ANY |
| | OTHERS ON THIS PLAN TO PREVENT A DELAY IN YOUR REVIEW. |
| | |
| | 42. NEW COMMENT; ON SHEET 103C UNIT IN GRID J/12, THE |
| | PIPES FOR SANITARY P702 AND P 7XX ARE IN THE WRONG |
| | LOCATION, AND THE ARROW IS NOT POINTED TO THEM AND |
| | PLEASE CORRECT OTHER UNITS BESIDE P709 AND P702A PER |
| | THE WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3. |
| | |
| | 43. NEW COMMENT; ON SHEET 104C UNIT IN GRID J/12, THE |
| | PIPES FOR SANITARY P702 AND P 7XX ARE IN THE WRONG |
| | LOCATION, AND THE ARROW IS NOT POINTED TO THEM AND |
| | PLEASE CORRECT OTHER UNITS BESIDE P709 AND P702A PER |
| | THE WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3. |
| | |
| | 44. NEW COMMENT; ON SHEET 105C UNIT IN GRID J/12, THE |
| | PIPES FOR SANITARY P702 AND P 7XX ARE IN THE WRONG |
| | LOCATION, AND THE ARROW IS NOT POINTED TO THEM AND |
| | PLEASE CORRECT OTHER UNITS BESIDE P709 AND P702A PER |
| | THE WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3. |
| | |
| | 45. NEW COMMENT; ON SHEET 106C UNIT IN GRID J/12, THE |
| | PIPES FOR SANITARY BELOW TO THE LABELS BELOW ARE NOT |
| | CLEAR OR ARE MISSED LABELED; PLEASE TRY TO CLARIFY AND |
| | CORRECT AS THEY ARE TOO MANY TO MENTION PER THE WPB |
| | AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3. |
| | |
| | 46. DONE. |
| | |
| | 47. DONE. |
| | |
| | 48. DONE. |
| | |
| | 49. DONE. |
| | |
| | 50. DONE. |
| | |
| | 51. DONE. |
| | |
| | 52. DONE. |
| | |
| | 53. DONE. |
| | |
| | 54. DONE. |
| | |
| | 55. DONE. |
| | |
| | 56. DONE. |
| | |
| | 57. DONE. |
| | |
| | 58. DONE. |
| | |
| | 59. DONE. |
| | |
| | 60. DONE. |
| | |
| | 61. DONE. |
| | |
| | 62. DONE. |
| | |
| | 63. DONE. |
| | |
| | 64. DONE. |
| | |
| | 65. DONE. |
| | |
| | 66. DONE. |
| | |
| | 67. DONE. |
| | |
| | 68. DONE. |
| | |
| | 68 A. NEW COMMENT, ON SHEET 702A AND 702 B, FROM WATER |
| | SERVICE TO PUMPS, THE CW HAS TOO LIGHT LABELS; PLEASE |
| | CORRECT BY DARKENING THEM PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 69. DONE. |
| | |
| | 70. DONE. |
| | |
| | 71. DONE. |
| | |
| | 72. DONE. |
| | |
| | 73. PARTLY DONE, BUT ON SHEET 704, TAG SS/R8 AND SS/R9 |
| | ARE MISSING PXXX DESTINATION. PLEASE CORRECT PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. PLEASE NOTE THE SHEET 704 AND |
| | CONTINUING PAGES HAVE A TABLE THAT REFERS TO THE 2014 |
| | CODE FOR TABLE 710.1(2), AND IT SHOULD BE THE 2017 FBC |
| | P TABLE 710.2 CODE, SO PLEASE CORRECT ALL PAGES TO |
| | PREVENT FURTHER DELAYS PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 74. DONE. |
| | |
| | 75. THERE ARE TAGS ON LEVELS EIGHT AND ELEVEN THAT ARE |
| | NOT LABELED ON SHEET. P.704B - RISER TAGS ARE MISSING |
| | THE DRAWING LOCATION NUMBERS ON THE RISER TAGS. ENSURE |
| | ALL RISER TAGS ARE COMPLETE. |
| | |
| | 76. DONE. |
| | |
| | 76. A. PLEASE NOTE THE SHEET 705, 705 A, 706, AND |
| | CONTINUING PAGES HAVE A TABLE THAT REFERS TO THE 2014 |
| | CODE FOR TABLE 709.1. IT SHOULD BE THE 2017 FBC P TABLE |
| | 709.1 CODE, SO PLEASE CORRECT ALL PAGES TO PREVENT |
| | FURTHER DELAYS PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 77. DONE. |
| | |
| | 78. DONE. |
| | |
| | 79. DONE. |
| | |
| | 80. DONE. |
| | |
| | 81. DONE. |
| | |
| | 82. DONE. |
| | |
| | 83. DONE. |
| | |
| | 84. DONE. |
| | |
| | 85. DONE. |
| | |
| | 86. DONE. |
| | |
| | 87. DONE. |
| | |
| | 88. DONE. |
| | |
| | 89. ON SHEET P.711, DETAIL #6, THE RISER TAG |
| | INFORMATION FOR DOMESTIC WATER RISER IS SO LIGHT IT IS |
| | ILLEGIBLE. PLEASE CORRECT. |
| | |
| | 90. DONE. |
| | |
| | 91. ON SHEET P.712 DETAIL #6 ? |
| | |
| | A. THE MEN'S AND WOMEN'S ROOMS REQUIRE SHUT-OFF VALVES |
| | AT HOSE BIBBS PER THE FBC-PLUMBING SEC. 606.2. |
| | |
| | B. THE WATER COOLER REQUIRES A HAMMER ARRESTOR PER THE |
| | 2017 FBC P 604.9 WATER HAMMER. |
| | |
| | 92. ON SHEET P.712, DETAILS #3, #4 (SS/0#), - THE RISER |
| | TAGS MISS THE RISER INFORMATION. ENSURE ALL RISER TAGS |
| | ARE COMPLETE. |
| | |
| | 93. ON SHEET P.712, THE WATER RISER FOR THE OFFICE |
| | TOWER-MEN?S OFFICE TOWER MEN?S TOILET ROOM LEVEL 17 IS |
| | MISSING AIR ARRESTORS AND SHUT-OFF VALES PER THE 2017 |
| | FBC P 604.9 AND 606.1. OFFICE TOWER-MEN?S TOILET IS |
| | ONLY MISSING AIR ARRESTORS. |
| | |
| | 94. INCOMPLETE, ON SHEET P.720 ? THE IDENTIFIED RISER |
| | TAGS INFO FIXTURE UNIT LOADS FOR SS/P60 HAS P7XX; |
| | PLEASE ADD CORRESPONDING NUMBERS. AND SS/P1 DOES NOT |
| | HAVE A STACK NUMBER. PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO FBC SEC. 107.2.1, 107.3.5.1.3. |
| | |
| | 95. DONE BUT OVERLAPPING; PLEASE CORRECT. ON SHEET |
| | P.730 - IDENTIFY ALL RISERS WITH RISER TAGS COMPLETE |
| | WITH ALL RISER TAG INFO AND THE GPM'S DRAINING INTO |
| | EACH RISER. WPB AMEND. TO FBC SEC. 107.2.1, |
| | 107.3.5.1.3. |
| | |
| | 96. ON SHEET P.731 - THE DRAWING HAS A FLOATING FITTING |
| | AND DRAINS WITH SECTIONS OF PIPE ARE MISSING, PIPE |
| | SIZES ARE NOT CONNECTED, RISER TAGS ALL OVER THE PLACE |
| | AND NOT DIRECTED OR POINTED TO A REFERENCE POINT, |
| | SECTIONS OF THE PIPING SYSTEM ARE CONGESTED AND |
| | DIFFICULT TO REVIEW ON THE TOP PART. PLEASE CORRECT PER |
| | THE WPB AMENDMENTS TO FBC SEC. 107.2.1, 107.3.5.1.3. |
| | |
| | 97. ON SHEET P.732 - THE RISER SHOWS THE SQUARE FOOTAGE |
| | AREA BEING DRAINED BUT NO GPM'S WITH 2014 FBC-PLUMBING |
| | SEC. TABLE 1106.3, AND THE CODE THAT SHOULD BE USED AND |
| | REFERENCED IS 2017 FBC SEC. TABLE 1106.2, SO PLEASE |
| | CLARIFY AND OR RECALCULATE. THIS IN ALL OTHER SECTION |
| | OF THIS PLUMBING FOR SANITARY HAS 2014, PLEASE CORRECT |
| | AND CLARIFY IF NEED BE, |
| | |
| | 98. ON SHEET. P.733, SECOND REQUEST, SEVERAL RISER TAGS |
| | ARE MISSING THE DRAWING LOCATION INFORMATION. PLEASE |
| | ENSURE ALL RISER TAGS ARE COMPLETE. |
| | |
| | 99. ON SHEET. P.734, SECOND REQUEST, SEVERAL RISER TAGS |
| | ARE MISSING THE DRAWING LOCATION INFORMATION. PLEASE |
| | ENSURE ALL RISER TAGS ARE COMPLETE. |
| | |
| | 100. DONE. |
| | |
| | 101. ON THE SHEET, P.803 - DETAIL #3 SHOWS JOINTS UNDER |
| | THE SLAB - PLUMBING SPECIFICATIONS SEC. 22 1110 - PART |
| | 2 - 2.02 STATES THAT "ENTRANCE PIPING TO THE BUILDING |
| | TO TERMINATE ABOVE GRADE." THE DETAIL ON P.803 SHOWS |
| | FLANGED FITTINGS UNDER THE SLAB. CLARIFY. IF THIS |
| | PIPING ARRANGEMENT IS TO REMAIN, SUBMIT DETAILS ON |
| | FITTING RESTRAINTS AND THRUST BLOCK INFORMATION. WPB |
| | AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3. 2ND REQUEST |
| | AND THE THERE IS NO NEW DRAWING, AND THE RESPONSE SAYS |
| | DETAIL HAS BEEN UPDATED PLEASE CLARIFY PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 102. RIGID SUPPORT SWAY BRACING SHALL BE PROVIDED AT |
| | CHANGES IN A DIRECTION MORE SIGNIFICANT THAN 45 DEGREES |
| | FOR PIPE SIZES 4 INCHES AND LARGER PER FBC-PLUMBING |
| | SEC. 308.6. SUBMIT DETAILS FOR THE BRACING. 2ND |
| | REQUEST, NO DETAIL FOUND PER RESPOND ?#3 HAS BEEN |
| | UPDATED. REFER TO REVISED SHEET P803?. |
| | |
| | 103. DONE. |
| | |
| | 104. DONE. |
| | |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |