Plan Review Notes
Plan Review Notes For Permit 18100540
Permit Number 18100540
Review Stop P
Sequence Number 4
Notes
Date Text
2021-06-21 15:54:2406/21/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. NO RESPONSE TO THIS?SHEET C.03 SHOWS A 15-INCH PVC
 RWL NEAR THE PROPERTY'S SOUTHWEST CORNER NEAR THE BUS
 STOP. THE LINE IS NOT SHOWN ON SHT. P100 (NEAR COLUMN
 LINE #1). CLARIFY.
  
 2. DONE.
  
 3. DONE.
  
 4. DONE.
  
 5. DONE.
  
 6. SHEET A1.502A - DETAIL #2 DOES NOT SHOW A SEAT IN
 THE SHOWER, AND DETAIL #3 SHOWS A SEAT. CLARIFY.
  
 THE SEAT DRAWN IN IS A SIDE SEAT, AND THE ONE ON THE
 ADA FUTURE IS THE BACK SEAT. PLEASE CORRECT AS BACKING
 DETAIL IS REQUIRED AND PROVIDED PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 7. DONE.
  
 8. DONE.
  
 9. DONE.
  
 10. THIS ITEM HAS NOT BEEN ADDRESSED, SHEET A1.600 -
 DETAIL #1 - WOMEN'S RESTROOM - THE PLAN STATES A CLEAR
 FLOOR SPACE OF 60 INCHES WIDE FOR THE ACCESSIBLE STALL,
 BUT THE PLAN ALSO SHOWS THE CLEAR INSIDE WIDTH 4 FEET
 11 1/2 INCHES. IF THIS IS A ROUGH DIMENSION, THEN THIS
 STALL WILL NOT BE WIDE ENOUGH AFTER THE FINISH. COMPLY
 WITH FBC-ACCESS. SEC.604.3.1.2ND REQUEST. CLARIFY.
  
 11. THIS ITEM HAS NOT BEEN ADDRESSED, SHEET A1.600
 DETAIL #1 - MEN'S RESTROOM - ONE OF THE URINALS IS
 SHOWN AS 1 FOOT 2 INCHES FROM A WALL TO THE CENTERLINE
 OF THE URINAL. A MINIMUM OF 15 INCHES FROM A WALL TO
 THE CENTER OF THE URINAL IS REQUIRED. FBC-PLUMBING
 SEC.405.3.1. 2ND REQUEST.
  
 12. THIS ITEM HAS NOT BEEN ADDRESSED, SHEET A1.600 -
 GROUND LEVEL BATHROOM #0132- IS THIS A UNISEX TOILET
 ROOM OR GENDER-SPECIFIC? CLARIFY. 2ND REQUEST, IT SEEMS
 AS THERE SHOULD BE A V3 SHEET.
  
 13. DONE.
  
 14. DONE.
  
 15. DONE.
  
 16. DONE.
  
 17. DONE BUT NEW COMMENT;
  
 ON SHEET 606 FHA;
  
 A. DETAIL #3, DOOR IS SWINGING INTO THE CLEAR FLOOR
 SPACE OF THE LAVE, AND THE CLEAR FLOOR SPACE IS NOT
 SHOWN FOR THE TUB. PLEASE NOTE THAT THE DISTANCE FROM
 THE DOOR OPENING TO THE TUB MAY BE ENCROACHING IN THE
 FLOOR SPACE.
  
 B. DETAIL #9 UNIT D1 SHOWS CLEAR FLOOR SPACE BUT NOT AN
 FHA UNIT; PLEASE REMOVE OR CLARIFY STATUS.
  
 ON SHEET 607 FHA;
 A. DETAIL #2, THE CLEAR FLOOR SPACE FOR TUB AND LAV NOT
 SHOWN.
  
 B. DETAIL # 3 AND #6, MASTER TUB CLEAR FLOOR SPACE NOT
 SHOWN.
  
 C. DETAIL # 7, LAV AND SHOW CLEAR FLOOR SPACE NOT
 SHOWN.
  
 ON SHEET 608 FHA;
  
 A. DETAIL #1, #4, AND 6, THE CLEAR FLOOR SPACE FOR TUB
 NOT SHOWN.
  
 B. DETAIL #3 UNIT B4 SHOWS CLEAR FLOOR SPACE BUT NOT AN
 FHA UNIT; PLEASE REMOVE OR CLARIFY STATUS.
  
 C. DETAIL #10 UNIT C1 SHOWS BACKING ON TUB AND TOILET.
 IS THIS AN FHA UNIT; PLEASE CLARIFY?
  
 ON SHEET 609 FHA;
  
 A. DETAIL #1, #3, AND #8, MASTER TUB CLEAR FLOOR SPACE
 NOT SHOWN.
  
 B. DETAIL #5 UNIT D1 SHOWS BACKING. IS THIS AN FHA
 UNIT; PLEASE CLARIFY?
  
 C. DETAIL #6 UNIT D3, LAV, AND TUB CLEAR FLOOR SPACE
 NOT SHOWN.
  
 D. DETAIL #7 UNIT D3 BATHROOM 2 & 3 SHOWS BACKING AND
 TOILET CLEAR FLOOR SPACE; IS THIS AN FHA? PLEASE
 CLARIFY.
  
 E. DETAIL 9 UNIT D4 SHOWS BACKING. IS THIS AN FHA UNIT;
 PLEASE CLARIFY?
  
 18. DONE.
  
 19. DONE.
  
 20. DONE.
  
 21. DONE.
  
 22. DONE.
  
 23. DONE.
  
 24. DONE.
  
 25. DONE.
  
 26. DONE.
  
 27. DONE.
  
 28. THE PAGE FOR V5 DOES NOT COINCIDE WITH THE PRIOR
 VERSION, SHEET A1.610 - DETAIL # 2 - CLEAN UP THIS
 PLAN. THE LAVATORY IS SHOWN LOCATED PARTIALLY IN THE
 WALL.
  
 29. THE PAGE FOR V5 DOES NOT COINCIDE WITH THE PRIOR
 VERSION, SHEET A1.610 - DETAIL #1 - THE FLOOR PLAN
 SHOWS THE DOOR SWINGING INTO THE SHOWER AND THE TOILET
 COMPARTMENT. THE INSWING DOOR IMPEDES ACCESS TO THE
 SHOWER CONTROLS AND THE TOILET AND DOES NOT COMPLY WITH
 FAIR HOUSING. REVERSE THE SWING OF THE DOOR.
  
 30. THE PAGE FOR V5 DOES NOT COINCIDE WITH THE PRIOR
 VERSION, SHEET A1.610 - DETAIL #3 - THE NOTES AND
 DETAILS FOR THE GRAB BAR REINFORCEMENT DON'T MAKE
 SENSE. CORRECT THE DEFICIENCIES. IF THIS IS SUPPOSED TO
 BE AN FHA-COMPLIANT BATHROOM, SHOW ALL CLEAR FLOOR
 SPACES AND THE FHA BATHROOM TYPE ON THE PLAN. THE
 LAVATORY APPEARS TO ENCROACH INTO THE REQUIRED CLEAR
 FLOOR SPACE FOR THE SHOWER. PLEASE CLARIFY.
  
 31. THE PAGE FOR V5 DOES NOT COINCIDE WITH THE PRIOR
 VERSION, SHEET A1.610 - DETAIL # 6 - IF THIS IS THE
 FHA-COMPLIANT BATHROOM, PLACE THE TYPE OF FHA BATHROOM
 ON THE PLAN AND CORRECT THE OVERLAY OF THE UNIT NUMBER
 ON THE FLOOR PLAN. PLEASE CORRECT THE OVERLAY ON DETAIL
 #5 ALSO.
  
 32. THE PAGE FOR V5 DOES NOT COINCIDE WITH THE PRIOR
 VERSION, SHEET A1.610 - DETAIL #7 - CORRECT THIS
 DETAIL. THE LOCATION OF REINFORCEMENT AND CLEAR FLOOR
 SPACES ARE OUT OF WHACK. CONTROLS ARE CALLED OUT ON THE
 LAVATORY. THE BATHROOM FLOOR PLAN IS CUT OFF AND
 INCOMPLETE. PLEASE CLARIFY.
  
 33. DONE.
  
 34. THIS ITEM SEEMS TO HAVE A PIPE THAT IS NOT CLEAR TO
 WHERE THEY GO OR ARE ON SHEET P100. IF POSSIBLE, EXPAND
 THE PIPING LAYOUT FOR THE SANITARY AND VENT LINES AND
 TAG THE RISERS AT THE TOILET ROOMS BY ELEVATORS P03,
 P04, & P05 ON COLUMN LINE H.
  
 35. DONE.
  
 36. DONE.
  
 38. THIS IS NOT CORRECTED; SHEET P.101B SHOWS AN 8-INCH
 SANITARY LINE WITHIN STAIRWAY # 4 AND A 4 INCH GW LINE
 IN STAIRWAY #10. THE LINE IS NOT PERMITTED WITHIN THE
 STAIRWAY PER FBC-BUILDING SEC.1023.5. THERE IS A CIRCLE
 WITH A LINE IN THIS AND ANOTHER ELEVATOR THAT WILL NEED
 TO BE REMOVED OR RELATED OUT OF THE STAIRWAY TO MOVE
 FORWARD TO A FINAL REVIEW, SO PLEASE DO YOUR BEST TO
 CORRECT THESE ITEMS.
  
 39. DONE.
  
 40. DONE.
  
 41. THE RISER TAGS FOR THE LW R2 P 7XX RISERS ARE
 MISSING THE DRAWING LOCATIONS ON THE RISER TAGS. PLEASE
 CLARIFY PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
 PLEASE ALSO CLARIFY ANY ABOVE FLOORS IN POD C AND ANY
 OTHERS ON THIS PLAN TO PREVENT A DELAY IN YOUR REVIEW.
  
 42. NEW COMMENT; ON SHEET 103C UNIT IN GRID J/12, THE
 PIPES FOR SANITARY P702 AND P 7XX ARE IN THE WRONG
 LOCATION, AND THE ARROW IS NOT POINTED TO THEM AND
 PLEASE CORRECT OTHER UNITS BESIDE P709 AND P702A PER
 THE WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.
  
 43. NEW COMMENT; ON SHEET 104C UNIT IN GRID J/12, THE
 PIPES FOR SANITARY P702 AND P 7XX ARE IN THE WRONG
 LOCATION, AND THE ARROW IS NOT POINTED TO THEM AND
 PLEASE CORRECT OTHER UNITS BESIDE P709 AND P702A PER
 THE WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.
  
 44. NEW COMMENT; ON SHEET 105C UNIT IN GRID J/12, THE
 PIPES FOR SANITARY P702 AND P 7XX ARE IN THE WRONG
 LOCATION, AND THE ARROW IS NOT POINTED TO THEM AND
 PLEASE CORRECT OTHER UNITS BESIDE P709 AND P702A PER
 THE WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.
  
 45. NEW COMMENT; ON SHEET 106C UNIT IN GRID J/12, THE
 PIPES FOR SANITARY BELOW TO THE LABELS BELOW ARE NOT
 CLEAR OR ARE MISSED LABELED; PLEASE TRY TO CLARIFY AND
 CORRECT AS THEY ARE TOO MANY TO MENTION PER THE WPB
 AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.
  
 46. DONE.
  
 47. DONE.
  
 48. DONE.
  
 49. DONE.
  
 50. DONE.
  
 51. DONE.
  
 52. DONE.
  
 53. DONE.
  
 54. DONE.
  
 55. DONE.
  
 56. DONE.
  
 57. DONE.
  
 58. DONE.
  
 59. DONE.
  
 60. DONE.
  
 61. DONE.
  
 62. DONE.
  
 63. DONE.
  
 64. DONE.
  
 65. DONE.
  
 66. DONE.
  
 67. DONE.
  
 68. DONE.
  
 68 A. NEW COMMENT, ON SHEET 702A AND 702 B, FROM WATER
 SERVICE TO PUMPS, THE CW HAS TOO LIGHT LABELS; PLEASE
 CORRECT BY DARKENING THEM PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 69. DONE.
  
 70. DONE.
  
 71. DONE.
  
 72. DONE.
  
 73. PARTLY DONE, BUT ON SHEET 704, TAG SS/R8 AND SS/R9
 ARE MISSING PXXX DESTINATION. PLEASE CORRECT PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. PLEASE NOTE THE SHEET 704 AND
 CONTINUING PAGES HAVE A TABLE THAT REFERS TO THE 2014
 CODE FOR TABLE 710.1(2), AND IT SHOULD BE THE 2017 FBC
 P TABLE 710.2 CODE, SO PLEASE CORRECT ALL PAGES TO
 PREVENT FURTHER DELAYS PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 74. DONE.
  
 75. THERE ARE TAGS ON LEVELS EIGHT AND ELEVEN THAT ARE
 NOT LABELED ON SHEET. P.704B - RISER TAGS ARE MISSING
 THE DRAWING LOCATION NUMBERS ON THE RISER TAGS. ENSURE
 ALL RISER TAGS ARE COMPLETE.
  
 76. DONE.
  
 76. A. PLEASE NOTE THE SHEET 705, 705 A, 706, AND
 CONTINUING PAGES HAVE A TABLE THAT REFERS TO THE 2014
 CODE FOR TABLE 709.1. IT SHOULD BE THE 2017 FBC P TABLE
 709.1 CODE, SO PLEASE CORRECT ALL PAGES TO PREVENT
 FURTHER DELAYS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 77. DONE.
  
 78. DONE.
  
 79. DONE.
  
 80. DONE.
  
 81. DONE.
  
 82. DONE.
  
 83. DONE.
  
 84. DONE.
  
 85. DONE.
  
 86. DONE.
  
 87. DONE.
  
 88. DONE.
  
 89. ON SHEET P.711, DETAIL #6, THE RISER TAG
 INFORMATION FOR DOMESTIC WATER RISER IS SO LIGHT IT IS
 ILLEGIBLE. PLEASE CORRECT.
  
 90. DONE.
  
 91. ON SHEET P.712 DETAIL #6 ?
  
 A. THE MEN'S AND WOMEN'S ROOMS REQUIRE SHUT-OFF VALVES
 AT HOSE BIBBS PER THE FBC-PLUMBING SEC. 606.2.
  
 B. THE WATER COOLER REQUIRES A HAMMER ARRESTOR PER THE
 2017 FBC P 604.9 WATER HAMMER.
  
 92. ON SHEET P.712, DETAILS #3, #4 (SS/0#), - THE RISER
 TAGS MISS THE RISER INFORMATION. ENSURE ALL RISER TAGS
 ARE COMPLETE.
  
 93. ON SHEET P.712, THE WATER RISER FOR THE OFFICE
 TOWER-MEN?S OFFICE TOWER MEN?S TOILET ROOM LEVEL 17 IS
 MISSING AIR ARRESTORS AND SHUT-OFF VALES PER THE 2017
 FBC P 604.9 AND 606.1. OFFICE TOWER-MEN?S TOILET IS
 ONLY MISSING AIR ARRESTORS.
  
 94. INCOMPLETE, ON SHEET P.720 ? THE IDENTIFIED RISER
 TAGS INFO FIXTURE UNIT LOADS FOR SS/P60 HAS P7XX;
 PLEASE ADD CORRESPONDING NUMBERS. AND SS/P1 DOES NOT
 HAVE A STACK NUMBER. PLEASE CORRECT PER THE WPB
 AMENDMENTS TO FBC SEC. 107.2.1, 107.3.5.1.3.
  
 95. DONE BUT OVERLAPPING; PLEASE CORRECT. ON SHEET
 P.730 - IDENTIFY ALL RISERS WITH RISER TAGS COMPLETE
 WITH ALL RISER TAG INFO AND THE GPM'S DRAINING INTO
 EACH RISER. WPB AMEND. TO FBC SEC. 107.2.1,
 107.3.5.1.3.
  
 96. ON SHEET P.731 - THE DRAWING HAS A FLOATING FITTING
 AND DRAINS WITH SECTIONS OF PIPE ARE MISSING, PIPE
 SIZES ARE NOT CONNECTED, RISER TAGS ALL OVER THE PLACE
 AND NOT DIRECTED OR POINTED TO A REFERENCE POINT,
 SECTIONS OF THE PIPING SYSTEM ARE CONGESTED AND
 DIFFICULT TO REVIEW ON THE TOP PART. PLEASE CORRECT PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1, 107.3.5.1.3.
  
 97. ON SHEET P.732 - THE RISER SHOWS THE SQUARE FOOTAGE
 AREA BEING DRAINED BUT NO GPM'S WITH 2014 FBC-PLUMBING
 SEC. TABLE 1106.3, AND THE CODE THAT SHOULD BE USED AND
 REFERENCED IS 2017 FBC SEC. TABLE 1106.2, SO PLEASE
 CLARIFY AND OR RECALCULATE. THIS IN ALL OTHER SECTION
 OF THIS PLUMBING FOR SANITARY HAS 2014, PLEASE CORRECT
 AND CLARIFY IF NEED BE,
  
 98. ON SHEET. P.733, SECOND REQUEST, SEVERAL RISER TAGS
 ARE MISSING THE DRAWING LOCATION INFORMATION. PLEASE
 ENSURE ALL RISER TAGS ARE COMPLETE.
  
 99. ON SHEET. P.734, SECOND REQUEST, SEVERAL RISER TAGS
 ARE MISSING THE DRAWING LOCATION INFORMATION. PLEASE
 ENSURE ALL RISER TAGS ARE COMPLETE.
  
 100. DONE.
  
 101. ON THE SHEET, P.803 - DETAIL #3 SHOWS JOINTS UNDER
 THE SLAB - PLUMBING SPECIFICATIONS SEC. 22 1110 - PART
 2 - 2.02 STATES THAT "ENTRANCE PIPING TO THE BUILDING
 TO TERMINATE ABOVE GRADE." THE DETAIL ON P.803 SHOWS
 FLANGED FITTINGS UNDER THE SLAB. CLARIFY. IF THIS
 PIPING ARRANGEMENT IS TO REMAIN, SUBMIT DETAILS ON
 FITTING RESTRAINTS AND THRUST BLOCK INFORMATION. WPB
 AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3. 2ND REQUEST
 AND THE THERE IS NO NEW DRAWING, AND THE RESPONSE SAYS
 DETAIL HAS BEEN UPDATED PLEASE CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 102. RIGID SUPPORT SWAY BRACING SHALL BE PROVIDED AT
 CHANGES IN A DIRECTION MORE SIGNIFICANT THAN 45 DEGREES
 FOR PIPE SIZES 4 INCHES AND LARGER PER FBC-PLUMBING
 SEC. 308.6. SUBMIT DETAILS FOR THE BRACING. 2ND
 REQUEST, NO DETAIL FOUND PER RESPOND ?#3 HAS BEEN
 UPDATED. REFER TO REVISED SHEET P803?.
  
 103. DONE.
  
 104. DONE.
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  