| 2021-06-21 15:48:10 | 06/21/21 4TH GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | |
| | 1. DONE. |
| | |
| | 2. DONE. |
| | |
| | 3. DONE. |
| | |
| | 4. DONE. |
| | |
| | 5. DONE. |
| | |
| | 6. DONE. |
| | |
| | 7. DONE. |
| | |
| | 8. THERE IS CLOUD AND NO INFORMATION, SO PLEASE |
| | CORRECT. SHEET P.700, KEYNOTE #3 - IDENTIFY THIS FUTURE |
| | LINE/SYSTEM ON THE GAS RISER PER THE WPB AMENDMENTS TO |
| | FBC SEC. 107.2.1. |
| | |
| | 9. DONE. |
| | |
| | 10. DONE. |
| | |
| | 11. THIS COMMENT HAS NOT BEEN ADDRESSED, AND BOTH |
| | SHEETS DO NOT MATCH; SHEET P.700 - KEYNOTE #14 SHOWS |
| | THE GAS LINE WITH 579 CFH AND SHT. P.700A, DETAIL #2 |
| | SHOWS 500 CFH. CLARIFY. |
| | |
| | 12. DONE. |
| | |
| | 13. ON SHEET 700A DETAIL #6, THE LONGEST RUN IS NOT |
| | CLEAR THE LONGEST RUN. IS TO THE PRV REGULATOR OR THE |
| | BOILER. THIS NEEDS TO BE KNOWN AS THE LONGEST RUN |
| | DETERMINE THE SIZE CALCULATION, SO PLEASE CLARIFY PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 14. ON SHEET 700A DETAIL #5, SIZE THE SHORT SECTION OF |
| | THE GAS MAIN LINE BETWEEN THE 4 INCH LINE AND THE 2 ? |
| | INCH LINE NEEDS A SIZE FIELD CLARIFICATION, PLEASE |
| | PROVIDE PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 15. DONE. |
| | |
| | 16. DONE. |
| | |
| | 17. DONE. |
| | |
| | 18. DONE. |
| | |
| | 19. DONE. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |
| | |