| 2021-01-27 08:36:20 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | PAGE E.502A |
| | 1) NO SIZES OF CONDUCTORS FROM THE PANELS TO THE |
| | TRANSFORMERS AND THEN AGAIN ON THE SECONDARY SIDE. |
| | |
| | 2) GROUNDING SHOWN AT TRANSFORMERS PLEASE INDICATE WHAT |
| | THEY ARE TO TIE INTO FOR GROUNDING. |
| | |
| | 3) FEEDERS TO THE FOLLOWING SHOW NOT SIZES AS WELL |
| | N2A1, SWB3, SWBC, SWBH4, SWBH1, SWBH3, KITCHEN PANEL, |
| | POOL PANEL, HOTEL POOL PANEL, GYM PANEL, AND N4H8B. |
| | |
| | PAGE E.502B |
| | 1) NO SIZES OF CONDUCTORS FROM THE PANELS TO THE |
| | TRANSFORMERS AND THEN AGAIN ON THE SECONDARY SIDE. |
| | |
| | 2) NO FEEDER SIZES TO CH, CWH |
| | |
| | PAGE E503 |
| | 1) GENERATOR 1 HAS 800A FEEDER WITH OVERCURRENT |
| | PROTECTION GOING TO FIRE PUMP, BUT IT HAS A 1600A |
| | FEEDER WITH NO OVER CURRENT PROTECTION AT THE GENERATOR |
| | WHAT SECTION ALLOWS THIS AND IF IT DOES THE CONDUCTORS |
| | WILL HAVE TO BE 115% PER 445.13 |
| | |
| | 2) PANEL DQ4H5 SHOWS NO OVERCURRENT PROTECTION SIZES |
| | AND APPEARS TO HAVE 3 SPARES? |
| | |
| | 3) PANEL DE4H5 SAME AS ABOVE |
| | |
| | 4) PANEL DQ4HRB NO WIRE SIZES FROM PANEL TO TRANSFORMER |
| | AND THEN AGAIN ON THE SECONDARY SIDE OF THE |
| | TRANSFORMER. |
| | |
| | PAGE E504 |
| | 1) WIRE SIZES FROM PANELS TO TRANSFORMER AND THEN AGAIN |
| | ON THE SECONDARY SIDE. |
| | |
| | 2) SWBNRR NO SIZES ON OVERCURRENT PROTECTION 5 SPARES? |
| | |
| | 3) DN4PR1 NO OVERCURRENT SIZES ON BREAKERS. |
| | |
| | |
| | PAGE E505 |
| | 1) PANELS DQ4RRA, DE4RR, AND DQ4RRB HAVE NO OVERCURRENT |
| | PROTECTION SHOWN ON BREAKERS AND IF THERE ARE SPARES. |
| | |
| | 2) WIRE SIZES FROM PANELS TO TRANSFORMERS AND ON THE |
| | SECONDARY SIDE ARE NOT SHOWN. |
| | |
| | PLANS ARE GENERALY GOOD PLANS BUT THE RISER HAS YOU |
| | LOOKING IN SEVERAL PLACES TO COME UP WITH THE SIZES OF |
| | CONDUCTORS AND OVERCURRENT PROTECTION ON PRIMARIES AND |
| | SECONDARIES OF THE TRANSFORMERS. IT WOULD BE A BENEFIT |
| | TO HAVE THE WIRE SIZES AND OVERCURRENT PROTECTION ON |
| | THE RISER MAYBE WITH A TABLE SHOWING THE WIRES AND |
| | OCPS. |
| | |
| | SMOKE ALARMS IN RESIDENTIAL UNITS NEEDS TO BE LOOKED AT |
| | IN REFERENCE TO LOCATIONS OF THE SMOKE ALARMS OR |
| | DETECTORS. NFPA 72 GIVES LOCATIONS FOR SMOKE ALARMS |
| | NEAR BATHROOM DOORS AND COOKING APPLIANCES THAT SEEMED |
| | TO HAVE BEEN OVERLOOKED. SEE NFPA 72 SECTIONS |
| | 29.8.3.4(4), AND (6) FOR COOKING APPLIABCES AND |
| | BATHROOM LOCATIONS. |