| 2020-03-19 16:13:50 | 1. SHEET A0.102 LIST BUILDING FOOTPRINT REQUIREMENT AS |
| | MINIMUM PERCENTAGE, IT IS A MAXIMUM PERCENTAGE. PLEASE |
| | CORRECT DATA TO ACCURATELY REFLECT REQUIREMENT. |
| | 2. SHEET A0.102 STILL LIST 328 RESIDENTIAL UNITS WITHIN |
| | THE PROJECT DESCRIPTION AND THE REQUIRED PARKING DATA. |
| | PLEASE ADJUST TO THE CURRENT PROPOSAL OF 230 UNITS. |
| | TABLE IN THE SAME SHEET LIST 202 REGULAR RESIDENTIAL |
| | UNITS AND 23 MICRO UNITS FOR A TOTAL OF 205 NOT THE NEW |
| | 230 LISTED. PLEASE CORRECT AND ADJUST ALL RELATED |
| | CALCULATIONS. |
| | 3. IN SHEET A1.500, THE HOTEL UNITS DESCRIPTION AND |
| | AREAS SUITE 1.3C AND 1.3W UNIT AREA IS NOT LISTED. |
| | PLEASE UPDATE TABLE AND INCLUDE INFORMATION TO CONFIRM |
| | COMPLIANCE WITH MINIMUM 350SF UNITS SIZE. |
| | 4. PLEASE PROVIDE INFORMATION TO CONFIRM THAT REGULAR |
| | RESIDENTIAL UNITS COMPLY WITH THE AVERAGE 800SF UNIT |
| | SIZE. |
| | 5. PLEASE SUBMIT COLORED ELEVATIONS WITH CALL OUT |
| | MATERIALS. |
| | 6. PLEASE SUBMIT THE FAR DETAIL INFORMATION PER FLOOR |
| | AS SUBMITTED FOR SITE PLAN APPROVAL. |
| | 7. PLEASE EXPLAIN HOW THE PLANTS PROPOSED FOR THE |
| | GARAGE SCREENING WILL GROW AND STILL MAINTAIN THE AIR |
| | FLOW REQUIRED FOR GARAGE VENTILATION. |
| | 8. PLEASE CONFIRM THE GLASS UTILIZED FOR THIS PROJECT |
| | AT THE GROUND FLOOR IS NOT DARK TINTED OR REFLECTIVE TO |
| | THE POINT THAT THE INTERIOR IS NOT VISIBLE FROM |
| | OUTSIDE. |
| | 9. FURTHER DISCUSSION IS NECESSARY FOR THE SELECTION OF |
| | THE LANDSCAPE MATERIAL TO BE LOCATED ON THE QUADRILLE |
| | BLVD MEDIAN. |
| | 10. PLEASE CONFIRM PALM TRAM APPROVED THE RELOCATION OF |
| | THE EXISTING SHELTER TO THE PROPOSED LOCATION. |
| | 11. DUE TO THE PROPOSED MICROUNITS PROJECT IS REQUIRED |
| | TO PROVIDE 1 CAR SHARING STATION PER EVERY 13 |
| | MICROUNITS. IF PARKING IS PROVIDED FOR THE MICROUNITS |
| | THERE MUST BE AT LEAST ONE CAR SHARING STATION ON SITE. |
| | PLEASE IDENTIFY LOCATION OF CAR SHARING STATION INSIDE |
| | PARKING GARAGE. |
| | 12. DUE TO THE PROPOSED MICROUNITS, PROJECT IS REQUIRED |
| | TO CONTRIBUTE A FEE INTO THE TROLLEY OPERATION FUND. |
| | FEE IS EQUAL TO $10 PER UNIT/MONTH. AN AGREEMENT WILL |
| | BE REQUIRED WITH THE PROPERTY OWNER BEFORE FINAL CO. |
| | 13. PLEASE IDENTIFY THE LOCATION FOR MICRO-MOBILITY |
| | STATION WITHIN THE PROJECT PUBLIC REALM AREA. |
| | 14. MINIMUM ACTIVE USE REQUIREMENT ALONG DIXIE HWAY IS |
| | 80% NOT 79%. PLEASE ADJUST TO CONFIRM COMPLIANCE. |
| | 15. THE VARIANCE APPROVED BY THE DAC TO REDUCE ACTIVE |
| | USES ABOVE THE FIRST FLOOR ALONG QUADRILLE BLVD ALLOWED |
| | A REDUCTION FROM 60% TO 47%. PROPOSED PROJECT LISTS |
| | ACTIVE USES ONLY ALONG 31.9%. PLEASE INCREASE AMOUNT OF |
| | ACTIVE USES TO COMPLY WITH VARIANCE APPROVED. |
| | 16.PLEASE PROVIDE A PEDESTRIAN CROSSING ACROSS DIXIE |
| | HWAY FROM THE SE CORNER OF THE PROJECT. |
| | 17. PLEASE RELOCATE AT LEAST 3 BIKE RACKS CLOSER TO THE |
| | OFFICE TOWER OPEN SPACE, AND RELOCATE AT LEAST 2 BIKE |
| | RACKS TO THE AREA CLOSER TO THE PROPOSED RETAIL. |
| | 18. GRADING PLAN SHEET 4 HAS LABELS BLACKED OUT. |
| | 19. A SEPARATE LANDSCAPE PERMIT WILL BE REQUIRED FOR |
| | THIS PERMIT. |
| | 20. PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE |
| | WITH PLANAR BREAK AT ALL APPLICABLE FACADES. |
| | 21. PLEASE SEE COMMENTS PROVIDED ON 11/29/2018 AS SOME |
| | OF THOSE HAVE NTO BEEN ADDRESSED. |