| 2021-02-19 11:02:15 | 1) SHT. C.03 SHOWS A 15 INCH PVC RWL NEAR THE SOUTHWEST |
| | CORNER OF THE PROPERTY NEAR THE BUS STOP. THE LINE IS |
| | NOT SHOWN ON SHT. P100 ( NEAR COLUMN LINE #1). CLARIFY. |
| | 2) SHT.L5-711 - THE POOL DECK SHOWER DOES NOT APPEAR TO |
| | BE COMPLIANT WITH ANSI A117.1-1986 SEC.4.25.4.FOR FAIR |
| | HOUSING ACT COMPLIANCE. THE CONTROL RING APPEARS LIKE |
| | IT MAY REQUIRE GRASPING OR TWISTING OF THE WRIST TO |
| | OPERATE WHICH WILL VIOLATE THIS SECTION. THE SUBMITTED |
| | SPECIFICATION SHEET DOES NOT SHOW THAT THIS A HANDICAP |
| | ACCESSIBLE COMPLIANT UNIT. PROVIDE DOCUMENTATION TO |
| | SHOW COMPLIANCE.THE RESPONSE NARRATIVE REFERS TO DETAIL |
| | #8 ON THIS SHEET BUT THE DETAIL SHOWS A PLAN VIEW OF |
| | THE SHOWER WHICH DOES NOT ADDRESS THIS COMMENT. 2ND |
| | REQUEST. |
| | 3) SHT. L5-711 - SHOW THE HEIGHT OF THE SHOWER CONTROL |
| | RING FROM FINISH GRADE TO THE CENTER OF THE CONTROL |
| | RING IN US CUSTOMARY UNITS.THE SPECIFICATION CURRENTLY |
| | SHOWS THE MEASUREMENT IN WHAT APPEARS TO BE |
| | MILLIMETERS. THE HEIGHT OF THE CONTROL RING SHALL |
| | COMPLY WITH ANSI A117.1-1986 SECS.4.2.5 & 4.2.6. |
| | 4) SHT.A0.203 - ALTERNATIVE ROLL-IN SHOWER W/SEAT - THE |
| | CONTROLS SHALL BE LOCATED A MAXIMUM OF 15 INCHES FROM |
| | THE CENTERLIINE OF THE SEAT TO THE CENTERLINE OF THE |
| | CCONTROLS PER FBC-ACCESS. SEC.608.5.3 AND FIGURE |
| | 608.5.3. THE DRAWING SHOWS THE 15 INCHES TO THE EDGE OF |
| | THE CONTROL AREA, NOT TO THE CENTER. |
| | 5) SHT. A1.256 - SHT. A1.256 - OFFICE TOWER FLOOR PLAN |
| | - ROOF LEVEL - SUBMIT INFORMATION FOR THE CHEMICAL |
| | TREATMENT SYSTEM. SUBMIT MSDS SHEETS FOR THE CHEMICALS |
| | BEING USED. SUBMIT INFORMATION ON THE AMOUNTS OF EACH |
| | CHEMICAL BEING USED, WHERE THEY ARE BEING STORED, THE |
| | TYPES OF CONTAINERS THE CHEMICALS ARE STORED IN, ETC. |
| | COMPLIANCE WITH SEC. 414 & 415 OF THE 2014 FBC MAY BE |
| | REQUIRED. THE SUBMITTED RESPONSE NARRATIVE STATES THIS |
| | SYSTEM IS LIISTED UNDER THE DEFERRED SUBMITTALS ON SHT. |
| | M.002 BUT IT IS NOT. |
| | 6) SHT.A1.502A - DETAIL #2 DOES NOT SHOW A SEAT IN THE |
| | SHOWER AND DETAIL #3 SHOWS A SEAT. CLARIFY. |
| | 7) SHT. A1.503 - DETAIL #2 - SHOW THE LOCATION OF THE |
| | SHOWER CONTROLS. THE LOCATION OF THE CONTROLS SHALL |
| | COMPLY WITH FBC-ACCESS. SEC.608.5.2. |
| | 8) SHT. A1.532 - MASTER BATH - THE FLOOR PLAN SHOWS THE |
| | DOOR SWINGING INTO THE SHOWER AND THE TOILET |
| | COMPARTMENT. THE INSWING DOOR IS IMPEDING ACCESS TO THE |
| | SHOWER CONTROLS AND THE USE OF THE TOILET AND DOES NOT |
| | COMPLY WITH FAIR HOUSING. REVERSE THE SWING OF THE |
| | DOOR. |
| | 9) SHT. A1.532 - SHOW THE REQUIRED CLEAR FLOOR SPACE AT |
| | ALL THE FIXTURES IN THE FHA ADAPTABLE BATHROOM. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 10) SHT.A1.600 - DETAIL #1 - WOMEN'S RESTROOM - THE |
| | PLAN STATES A CLEAR FLOOR SPACE OF 60 INCHES WIDE FOR |
| | THE ACCESSIBLE STALL BUT THE PLAN ALSO SHOWS THE INSIDE |
| | CLEAR WIDTH AS 4 FEET 11 1/2 INCHES. IF THIS IS A ROUGH |
| | DIMENSION THEN THIS STALL WILL NOT BE WIDE ENOUGH AFTER |
| | FINISH. COMPLY WITH FBC-ACCESS. SEC.604.3.1.2ND |
| | REQUEST. CLARIFY. |
| | 11) SHT. A1.600 - SHT.A1.600 - DETAIL #1 - MEN'S |
| | RESTROOM - ONE OF THE URINALS IS SHOWN AS 1 FOOT 2 |
| | INCHES FROM A WALL TO THE CENTERLINE OF THE URINAL. A |
| | MINIMUM OF 15 INCHES FROM A WALL TO THE CENTER OF THE |
| | URINAL IS REQUIRED. FBC-PLUMBING SEC.405.3.1. 2ND |
| | REQUEST. |
| | 12) SHT. A1.600 - GROUND LEVEL BATHROOM #0132- IS THIS |
| | A UNISEX TOILET ROOM OR GENDER SPECIFIC? CLARIFY.2ND |
| | REQUEST. |
| | 13) SHT.A1.601 - DETAIL # 1 - GROUND LEVEL BATHROOM |
| | #0121 - THE DOOR TO ONE OF THE TOILET ROOMS IS SWINGING |
| | INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY. |
| | FBC-ACCESS. SEC. 603.2.3. SEE EXCEPTIONS. SHOW THE |
| | REQUIRED 30 INCH MINIMUM BY 48 INCH MINIMUM CLEAR FLOOR |
| | SPACE BEYOND THE ARC OF THE DOOR SWING ON THE PLANS. IT |
| | IS NOT SHOWN. 2ND REQUEST. |
| | 14) SHT. A1.601 - DETAIL #1 - TOILET ROOM #0121 - THE |
| | DOOR IS IN FRONT OF THE WATER CLOSET. THE WATER CLOSET |
| | CANNOT OVERLAP THE REQUIRED MANEUVERING CLEARANCE FOR |
| | THE DOOR INSIDE THE ROOM. SHOW THE REQUIRED MANEUVERING |
| | CLEARANCE FOR THE DOOR IN ACCORDANCE WITH FBC-ACCESS. |
| | 404.2.4. |
| | 15) SHT. A1..602 - DETAIL #1 - WOMEN'S RESTROOM #0731- |
| | SHOW THE INSIDE CLEAR LENGTH OF THE AMBULATORY |
| | ACCESSIBLE TOILET STALL AND THE STANDARD TOILET STALLS. |
| | THE DIMENSIONS SHOWN ON THE PLAN ARE NOT CLEAR INSIDE |
| | DIMENSIONS. FBC-ACCESS. SEC.604.8.2.1, |
| | 604.8.2FBC-PLUMBING SEC.405.3.1.2ND REQUEST. |
| | 16) SHT. A1.603 - DETAILS #1 & #5 - IDENTIFY ON THE |
| | PLANS THAT THESE BATHROOMS ARE LOCATED IN THE HOTEL. |
| | 2ND REQUEST. |
| | 17) SHT. A1.607 - DETAIL #8 - THERE ARE NOTES ON THE |
| | PLAN POINTING TO NOTHING AND TO WRONG ITEMS, LOCATION |
| | OF GRAB BAR REINFORCEMENT IS WRONG,AND THE DOOR SWINGS |
| | INTO THE SHOWER. A PERSON IN A WHEELCHAIR WOULD NOT BE |
| | ABLE TO ACCESS THE CONTROLS. REVERSE THE DOOR SWING ON |
| | THE SHOWER. |
| | 18) SHT. A1.607 - DETAIL #6 - IDENTIFY THE FHA BATHROOM |
| | TYPE ON THE PLANS. |
| | 19) SHT. A1.608 - DETAIL #5 CALLS OUT A MASTER BATH BUT |
| | THE FLOOR PLAN SHOWS A KITCHEN. CLARIFY. |
| | 20) SHT. A1.608 - DETAIL #4 - IDENTIFY THE FHA BATHROOM |
| | TYPE ON THE DETAIL AND PLEASE FIX THE OVERLAY OF THE |
| | UNIT NUMBER OVER THE COLUMN NUMBER. |
| | 21) SHT. A1.608 - DETAIL #10 - THE LOCATION OF THE GRAB |
| | BAR REINFORCEMENTS ARE SHOWN IN THE MIDDLE OF THE |
| | FLOOR. CLARIFY. |
| | 22) SHT. A1.609 - DETAIL #5 - THERE IS AN OVERLAY ON |
| | THIS DETAIL THAT NEEDS TO BE REMOVED AND ALSO FLOATING |
| | NOTES. CLEAN UP THIS DETAIL. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 23) SHT.A1.609 - DETAIL #2 - CLEAN UP THIS DETAIL. |
| | CLEAR FLOOR SPACE IS SHOWN IN THE CLOSET. IF THIS IS |
| | SUPPOSED TO BE AN FHA COMPLIANT BATHROOM IT IS NOT. A |
| | WATER CLOSET CANNOT BE LOCATED NEXT TO THE SHOWER |
| | BECAUSE THE REQUIRED FLOOOR SPACE FOR THE SHOWER CANNOT |
| | BE PROVIDED. A NOTE ON THIS DETAIL STATES "BATHROOM 1 |
| | FHA TYPE B." CLARIFY. |
| | 24) SHT. A1.609 - DETAILL # 3 - INDICATE ON THE DETAIL |
| | IF THIS IS THE FHA COMPLIANT BATHROOM. IF SO, SHOW ALL |
| | THE REQUUIRED CLEAR FLOOR SPACES, LOCATION OF GRAB BAR |
| | REINFORCEMENT, AND THE DOORS ON THE SHOWER AND THE |
| | TOILET CCOMPARTMENT CANNOT SWING IN PER FHA DESIGN |
| | MANUAL/GUIDELINES. |
| | 25) SHT. A1.609 - DETAIL #4 CALLS OUT BATHROOM 3 BUT |
| | THERE IS NO BATHROOM PLAN SHOWN. CLARIFY. |
| | 26) SHT. A1.609 - DETAIL #8 - CORRECT THE LOCATION OF |
| | THE GRAB BAR REINFORCEMENT FOR THE TOILET ON THE PLAN. |
| | 27) SHT. A1.609 - DETAIIL #9 - IF THIS IS SUPPOSED TO |
| | BE AN FHA COMPLIANT BATHROOM IT IS NOT. A WATER CLOSET |
| | CANNOT BE LOCATED NEXT TO THE SHOWER BECAUSE THE |
| | REQUIRED FLOOOR SPACE FOR THE SHOWER CANNOT BE |
| | PROVIDED. CLARIFY. |
| | 28) SHT. A1.610 - DETAIL # 2 - CLEAN UP THIS PLAN. THE |
| | LAVATORY IS SHOWN LOCATED PARTIALLY IN THE WALL. |
| | 29) SHT. A1.610 - DETAIL #1 - THE FLOOR PLAN SHOWS THE |
| | DOOR SWINGING INTO THE SHOWER AND THE TOILET |
| | COMPARTMENT. THE INSWING DOOR IS IMPEDING ACCESS TO THE |
| | SHOWER CONTROLS AND THE USE OF THE TOILET AND DOES NOT |
| | COMPLY WITH FAIR HOUSING. REVERSE THE SWING OF THE |
| | DOOR. |
| | 30) SHT. A1.610 - DETAIL #3 - THE NOTES AND DETAILS FOR |
| | THE GRAB BAR REINFORCEMENT DON'T MAKE SENSE. CORRECT |
| | THE DEFICIENCIES. IF THIS IS SUPPOSED TO BE AN FHA |
| | OMPLIANT BATHROOM SHOW ALL CLEAR FLOOR FLOOOR SPACES |
| | AND THE FHA BATHROOM TYPE ON THE PLAN. THE LAVATORY |
| | APPEARS LIKE ENCROACH INTO THE REQUIRED CLEAR FLOOR |
| | SPACE FFOR THE SHOWER.CLARIFY. |
| | 31) SHT. A1.610 - DETAIL # 6 - IF THIS IS THE FHA |
| | COMPLIANT BATHROOM, PLACE THE TYPE OF FHA BATHROOM ON |
| | THE PLAN AND CORRECT THE OVERLAY OF THE UNIT NUMBER ON |
| | THE FLOOR PLAN.PLEASE CORRECT THE OVERLAY ON DETAIL #5 |
| | ALSO. |
| | 32) SHT. A1.610 - DETAIL #7 - CORRECT THIS DETAIL. |
| | LOCATION OF REINFORCEMENT AND CLEAR FLOOR SPACES ARE |
| | OUT OF WHACK. CONTROLS ARE CALLED OUT ON THE |
| | LAVATORY.BATHROOM FLOOR PLAN IS CUTOFF AND INCOMPLETE. |
| | CLARIIFY. |
| | 33) SHT. P1.00 - THERE IS A LINE IDENTIFIED AS "8 INCH |
| | CWS UP" AND THE ARROW APPEARS TO POINT TO A 10 INCH |
| | SANITARY LINE. REFER TO COLUMN LINE G-11 NEAR STAIR #1. |
| | CLARIFY. |
| | 34) SHT. P100 - EXPAND THE PIPING LAYOUT FOR THE |
| | SANITARY AND VENT LINES AND TAG THE RISERS AT THE |
| | TOILET ROOMS BY ELEVATORS P03, P04, & P05 ON COLUUMN |
| | LINE H. |
| | 35) SHT. P100 - ONE OF THE 6 INCH KW LINES BY THE |
| | GREASE IINTERCEPTORS IS ALSO LABELED AS AN 8 INCH CW |
| | UP. CLARIFY. |
| | 36) SHT. P100 - THERE ARE A LOT OF DRAIN LINES ON THIS |
| | PLAN, ESPECIALLY AT THE STAIRS, THAT BEAR NO RISER |
| | TAGS.CLARIFY. |
| | 38) SHT. P.101 & SHT. P.101B SHOWS AN 8 INCH SANITARY |
| | LINE WITHIN THE STAIRWAY # 4 AND ALSO A 4 INCH GW LINE |
| | IN STAIRWAY #10. THE LINE IS NOT PERMITTED WITHIN THE |
| | STAIRWAY PER FBC-BUILDING SEC.1023.5. |
| | 39) SHTS. P.101A, P.101B, P.101C, & P.101C - THERE ARE |
| | DRAIN, GAS, RAINWATER, CONDENSATE AND WATER LINES THAT |
| | HAVE NO RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING |
| | LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS |
| | IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE |
| | REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO |
| | FBC SEC. 107.2.1, 107.3.5.1.3. |
| | 40) IDENTIFY THE STAIR NUMBERS ON THE PLUMBING SHEETS. |
| | THIS WILL HELP IN DETERMINING THE LOCATION OF PIPE |
| | SYSTEMS ON THE RE-REVIEW.WPB AMND. TO FBC SEC. |
| | 107.2.1.2ND REQUEST. |
| | 41) SHTS. P.102A, P.102B, P.102C, P.102D - THERE ARE |
| | DRAIN, RAINWATER, CONDENSATE AND WATER LINES THAT HAVE |
| | NO RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING |
| | LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS |
| | IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE |
| | REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO |
| | FBC SEC. 107.2.1, 107.3.5.1.3. |
| | 42) SHTS.P.103A, P.103B, P.103C, P.103D - THERE ARE |
| | DRAIN, RAINWATER, CONDENSATE AND WATER LINES THAT HAVE |
| | NO RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING |
| | LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS |
| | IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE |
| | REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO |
| | FBC SEC. 107.2.1, 107.3.5.1.3. |
| | 43 - SHTS. P.104A THROUGH SHT. P104D - THERE ARE DRAIN, |
| | RAINWATER, CONDENSATE AND WATER LINES THAT HAVE NO |
| | RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING |
| | LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS |
| | IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE |
| | REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO |
| | FBC SEC. 107.2.1, 107.3.5.1.3. |
| | 44) SHTS. P1.05A THROUGH P.105D - THERE ARE DRAIN, |
| | RAINWATER, CONDENSATE AND WATER LINES THAT HAVE NO |
| | RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING |
| | LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS |
| | IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE |
| | REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO |
| | FBC SEC. 107.2.1, 107.3.5.1.3. |
| | 45) SHTS. P.106A THROUGH SHT. 106D - THERE ARE DRAIN, |
| | RAINWATER, CONDENSATE AND WATER LINES THAT HAVE NO |
| | RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING |
| | LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS |
| | IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE |
| | REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO |
| | FBC SEC. 107.2.1, 107.3.5.1.3. |
| | 46) SHTS. P.107A THROUGH P.107D - THERE ARE DRAIN, |
| | RAINWATER, CONDENSATE AND WATER LINES THAT HAVE NO |
| | RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING |
| | LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS |
| | IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE |
| | REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO |
| | FBC SEC. 107.2.1, 107.3.5.1.3. |
| | 47) SHTS. P.108A THROUGH P.108D - THERE ARE DRAIN, |
| | RAINWATER, CONDENSATE AND WATER LINES THAT HAVE NO |
| | RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING |
| | LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS |
| | IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE |
| | REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO |
| | FBC SEC. 107.2.1, 107.3.5.1.3. |
| | 48) SHT. P.105D SHOWS 2-4INCH RW LINES WITHIN THE |
| | STAIRWAY #7. THESE LINES ARE NOT PERMITTED WITHIN THE |
| | STAIRWAY PER FBC-BUILDING SEC.1023.5. |
| | 49) SHT. P.106D SHOWS FOUR- 4 INCH ROOF DRAINS AND A 4 |
| | INCH RW LINE WITHIN STAIRWAY #7.THE LINES ARE NOT |
| | PERMITTED WITHIN THE STAIRWAY PER FBC-BUILDING |
| | SEC.1023.5. |
| | 50) SHTS. P.107A, P.107C & P.107D - THE DRAWINGS SHOW |
| | RAINWATER DRAIN PIPING AND ROOF DRAINS LOCATED IN |
| | STAIRWAYS #5, #12, & #7. THESE LINES AND DRAINS ARE NOT |
| | PERMITTED WITHIN THE STAIRWAY PER FBC-BUILDING |
| | SEC.1023.5. |
| | 51) SHTS. P.108A, P.108B, P.108C - THE DRAWINGS SHOW |
| | RAINWATER DRAIN PIPING, DRAINS AND CONDENSATE PIPING IN |
| | STAIRWAYS #5, 8 & #9. THE LINES AND DRAINS ARE NOT |
| | PERMITTED WITHIN THE STAIRWAY PER FBC-BUILDING |
| | SEC.1023.5. |
| | 52) THE OVERALL PIPNG PLANS FOR THE PODIUM LEVELS ARE |
| | MISSING SECTIONS OF PIPING AND BASICALLY HAVE NO |
| | INFORMATION ON THEM AND ARE USELESS FOR REVIEW.I |
| | UNDERSTAND THAT THESE ARE OVERALLL PLANS BUT THE |
| | DRAWINGS ARE MISSING BASIC ESSENTIAL INFORMATION FOR |
| | PLAN REVIEW. WPB AMEND. TO FFBC SEC. 107.2.1, |
| | 107.3.5.1.3. |
| | 53) SHTS. P.251 THROUGH 256 - THE RISER TAGS FOR THE LW |
| | RISERS ARE MISSING THE DRAWING LOCATIONS ON THE RISER |
| | TAGS. CLARIFY. |
| | 54) SHTS. P. 258 THROUGH P.261 - THE RISER TAGS FOR THE |
| | LW RISERS ARE MISSING THE DRAWING LOCATIONS ON THE |
| | RISER TAGS.CLARIFY. |
| | 55) SHT. P.510 - DETAIL #6 - TWO LAVATORIES ARE MISSING |
| | FROM THE SANITARY RISER. CLARIFY. |
| | 56) SHT. P.510 - DETAIL #3 - A LAVATORY IN THE MEN'S |
| | AND WOMEN'S HANDICAP STALL IS MISSING FROM SANITARY |
| | RISER. CLARIFY. |
| | 57) SHT. P.510 - DETAILS #2 & #3 THE DRINKING FOUNTAINS |
| | ARE MISSING FROM THE SANITARY AND WATER RISERS. |
| | 58) SHT. P.5.11 - DETAIL #4 - ROOMS #0243 & 0245 - THE |
| | URINAL DOES NOT APPEAR TO BE VENTED. CLARIFY. |
| | 59) SHT. P.511 -DETAIL #4 - THE LAVATORY IN THE |
| | HANDICAP STALL IN THE WOMEN'S CHANGING FACILITY IS NOT |
| | SHOWN ON THE SANITARY RISER. |
| | 60) SHT. P.511 - DETAIL #4 - IT APPEARS THERE IS A |
| | STANDARD WATER CLOSET IN THE WOMEN'S CHANGING FACILITY |
| | THAT IS NOT SHOWN ON THE SANITARY RISER DIAGRAM. |
| | 61) SHT. P.511 - DETAIL #4 - THE LAVATORY IN THE MEN'S |
| | HANDICAP STALL IS NOT SHOWN ON THE SANITARY RISER. |
| | 62) SHT. P.511 - DETAIL #4 - THERE IS A LAVATORY ON THE |
| | RISER DIAGRAM FOR THE MEN'S CHANGING FACILITY THAT IS |
| | NOT SHOWN ON THE FLOOR PLAN. 61) SHT. P.503 - |
| | 63) SHT. P.513 - DETAIL #1 - REVVISE THIS DETAIL TO |
| | CLEARLY SHOW THE 3 LAVATORIES IN EACH RESTROOM. THERE |
| | IS AN OVERLAY THAT CURRENTLY LOOKS LIKE 5 LAVATORIES. |
| | 2ND REQUEST. |
| | 64) SHT. P.514 - DETAI #5 - THE LW RISER TAGS DO NOT |
| | HAVE DRAWING LOCATIONS ON THE RISER TAGS. CLARIFY. |
| | 65) SHT. P.514 - DETAIL#6 - THE LAVATORY IN THE WOMEN'S |
| | HANDICAP ACCESSIIBLE STALL IS NOT SHOWN ON THE SANITARY |
| | RISER. CLARIFY. |
| | 66) SHT. P.701 - THE RISER TAGS AT THE BOTTOM AND TOP |
| | OF THE HOTEL/OFFICE DOMESTIC WATER RISERS ARE MISSING |
| | THE DRAWING LOCATIONS. CLARIFY. |
| | 67) SUBMIT A PIPING DETAIL FOR MASTER THERMOSTATIC |
| | MIXING VALVES TMV-1, TMV-2 & TMV-3. THE PIPING FOR |
| | RECIRCULATION SYSTEMS HAVING MASTER THERMOSTATIC VALVES |
| | SHALL CCOMPLY WITH FBC-PLUMBING SEC. 607.2.2. 2ND |
| | REQUEST. |
| | 68) SHT. P.702 - THERE ARE BRANCHES OFF THE WATER |
| | RISERS THAT SOME HAVE NO SIZES OR THE AREA THEY SUPPLY. |
| | REFER TO LEVELS 2-8. SUPPLY THE REQUIRED INFO. WPB |
| | AMEND. TO FBC SEC. 107.3.5.1.3. 2ND REQUEST. |
| | 69) SHT. P.703 - ALMOST ALL OF THE RISER TAGS ARE |
| | MISSING DRAWING LOCATION INFORMATION. CLARIFY. |
| | 70) SHT. P.703A & P.703B - THERE ARE DRAWING LOCATION |
| | NUMBERS MISSING FROM NUMEROUS RISER TAGS ON THESE |
| | SHEETS.SUPPLY THE APPLICABLE DRAWING LOCATION NUMBERS |
| | ON THESE TAGS. |
| | 71) SHT. P.703A - THE STACK DESIGNATION TYPE AND RISER |
| | NUMBERING ON THE RISER TAGS DOES NOT CORRELATE WITH THE |
| | REFERENCED RISER TAGS ON SHTS. P502 & SHT. P.503. |
| | CLARIFY. |
| | 72) SHT. P.703B - RISER TAGS ARE MISSING THE DRAWING |
| | LOCATION NUMBERS ON THE RISER TAGS. ENSURE ALL RISER |
| | TAGS ARE COMPLETE. |
| | 73) SHT. P.704 - NUMEROUS RISER TAGS ARE MISSING |
| | DRAWING LOCATION INFORMATION/NUMBERS. |
| | 74) SHT. P.704A - RISER TAGS ARE MISSING THE DRAWING |
| | LOCATION NUMBERS ON THE RISER TAGS. ENSURE ALL RISER |
| | TAGS ARE COMPLETE. |
| | 75) SHT. P.704B - RISER TAGS ARE MISSING THE DRAWING |
| | LOCATION NUMBERS ON THE RISER TAGS. ENSURE ALL RISER |
| | TAGS ARE COMPLETE. |
| | 76) SHT. P.705A - THE PRINTING ON THE RISER TAGS IS SO |
| | LIGHT THAT IT IS ILLEGIBLE. PROVIDE LEGIBLE INFO. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 77) SHT. SHT. P.706 - DETAILS #7, 8, 10, 11, &12 - ONLY |
| | 4 FIXTURE UNITS ARE ALLOWED ON A 2 INCH WET VENT PER |
| | FBC-PLUMBING TABLE 912.3. THE HORIZONTAL DRAIN FROM THE |
| | WATER CLOSET SHALL BE 3 INCHES UP TO THE FIRST |
| | HORIZONTAL FIXTURE DRAIN (BATHTUB/SHOWER). |
| | 78) SHT. P.706 - DETAIL #9 - THE HORIZONTAL DRAIN FROM |
| | THE WATER CLOSET UP TO THE FIRST HORIZONTAL BRANCH |
| | SHALL BE 3 INCHES IN DIAMETER PER FBC-PLUMBING TABLE |
| | 912.3. |
| | 79) SHT. P.706 - DETAIL #10 & #20 - THE BATHTUBS ARE |
| | NOT VENTED. THEY CANNOT CONNECT DIRECTLY TO THE SHOWER |
| | OR WATER CLOSET FIXTURE DRAIN. FBC-PLUMBING |
| | SECS.1002.1, 901.2. |
| | 80) SHT. P.706 - DETAIL #19 - THE DRAIN FROM THE |
| | WASHING MACHINE BOX TO THE STACK SHALL BE A MINIMUM OF |
| | 3 INCHES IN DIAMETER PERR FBC-PLUMBING SEC.406.2. |
| | 81) SHT. P.707 - DETAILS #1,2,3,4,,& 5 - RISER TAG |
| | NUMBERS, STACK DESIGNATION AND DRAWING LOCATION |
| | INFORMATION IS MISSING FROM THE RISER TAGS. ENSURE ALL |
| | RISER TAGS ARE COMPLETE. |
| | 82) SHT. P.709 - THE DRAIN FROM THE WASHING MACHINE BOX |
| | TO THE STACK SHALL BE A MINIMUM OF 3 INCHES IN DIAMETER |
| | PERR FBC-PLUMBING SEC.406.2. |
| | 83) SHT. P.709 - THE DRAWING LOCATION INFORMATION IS |
| | MISSING FROM ALL OF THE WASTE AN SANITARY STACK RISER |
| | DIAGRAMS. ENSURE ALL RISER TAGS ARE COMPLETE. |
| | 84) SHT. P.709 - IDENTIFY THE CONTINUATION POINTS OF |
| | BOTH 6 INCH VERTICAL SANITARY DRAINS THAT TURN DOWN. |
| | 85) SHT. P.710 - DETAIL #5 - THE WATER RISER DIAGRAM |
| | DOES NOT CORRELATE WITH THE REFERENCED ENLARGED FLOOR |
| | PLAN DETAIL #5 ON SHT. P.505. THESES ARE TWO DIFFERENT |
| | UNITS. CLARIFY. |
| | 86) SHT.P.710 - DETAIL #4 - THE WATER CONNECTION FROM |
| | THE WATER RISER TO THE UNIT IS MISSING. CLARIFY. |
| | 87) SHT. P.711 - DETAIL #2 - THERE IS A BATHTUB MISSING |
| | ON THE WATER RISER IN ONE OF THE BATHROOMS AND THE |
| | SHOWER IS LABELED AS A BATHTUB IN THE SAME BATHROOM, |
| | AND ONLY ONE LAVATORY IS SHOWN ON THE RISER IN THIS |
| | SAME BATH. CLARIFY. |
| | 88) SHT. P.711 - DETAIL #2 - THERE IS A BATHTUB SHOWN |
| | ON THE WATER RISER IN THE MASTER BATH BUT IT IS NOT |
| | SHOWN ON THE FLOOR PLAN AND THE WATER CLOSET AND |
| | LAVATORY ARE REVRSED ON THE WATER RISER IN THE MASTER |
| | BATH.. CLARIFFY. |
| | 89) SHT. P.711 - DETAIL #6 -THE LAYOUT OF THE FIXTURES |
| | ON THE WATER RISER DIAGRAM DOES NOT CORRELATE WITH THE |
| | LAYOUT OF THE PLUMBING FIXTURES ON REFERENCED SHT. |
| | P.507, DETAIL #2. ALSO, THE RISER TAG INFORMATION IS SO |
| | LIGHT IT IS ILLEGIBLE. CLARIFY. |
| | 90) SHT. P.712 - DETAIL #F - THE SANITARY RISER IS |
| | INCOMPLETE. FIXTURES ARE MISSING. EXPAND THE RIDER SO A |
| | PROPER REVIEW CAN BE DONE. WPB AMEND. TO FBC SEC. |
| | 107.2.1, 107.3.5.1.3. |
| | 91) SHT. P.712 - THE WATER SUPPLY BRANCHES FROM THE |
| | RISERS TO THE MEN'S AND WOMEN'S OFFICE TOILET RROOMS |
| | REQUIRE SHUTOFF VALVES TO RESTROOMS. FBC-PLUMBING SEC. |
| | 606.1. |
| | 92) SHT. P.712 - DETAILS #3, #4, & #6 - THE RISER TAGS |
| | ARE MISSING THE RISER INFORMATION. ENSURE ALL RISER |
| | TAGS ARE COMPLETE. |
| | 93) SHT. P.712 - DETAIL #6 - THE DRINKING FOUNTAINS |
| | SHOWN ON DETAIL #3 ARE NOT SHOWN ON THE WATER RISER ON |
| | DETAIL #6 OR THE WATER RISER FOR THE OFFICE TOWER - |
| | WOMEN'S TOILET ROOM. CLARIFY. |
| | 94) SHT. P.720 - IDENTIFY ALL RISERS WITH RISER TAGS |
| | COMPLETE WITH ALL RISER TAG INFO AND FIXTURE UNIT |
| | LOADS. THERE ARE STILL RISERS THAT HAVE NO TAGS. WPB |
| | AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3. |
| | 95) SHT. P.730 - IDENTIFY ALL RISERS WITH RISER TAGS |
| | COMPLETE WITH ALL RISER TAG INFO AND THE GPM'S DRAINING |
| | INTO EACH RISER. WPB AMEND. TO FBC SEC. 107.2.1, |
| | 107.3.5.1.3. |
| | 96) SHT. P.731 - THE DRAWING IS INCOMPLETE.SECTIONS OF |
| | PIPE ARE MISSING, PIPE SIZES ARE MISSING, NO RISER |
| | TAGS, SECTIONS OF THE PIPING SYSTEM ARE CONGESTED AND |
| | DIFICULT TO REVIEW.WPB AMEND. TO FBC SEC. 107.2.1, |
| | 107.3.5.1.3. |
| | 97) SHT. P.732 - THE RISER SHOWS THE SQUARE FOOTAGE |
| | AREA BEING DRAINED BUT NO GPM'S. COMPLY WITH |
| | FBC-PLUMBING SEC. 11106.2. CLARIFY. |
| | 98) SHT. P.733- THERE ARE SEVERAL RISER TAGS MISSING |
| | THE DRAWING LOCATION INFORMATION.ENSURE ALL RISER TAGS |
| | ARE COMPLETE. |
| | 99) SHT. P.734 - THERE ARE SEVERAL RISER TAGS MISSING |
| | THE DRAWING LOCATION INFORMATION.ENSURE ALL RISER TAGS |
| | ARE COMPLETE. |
| | 100) SHT. P.803 - DETAIL #9 - SUBMIT DETAILS AS TO HOW |
| | THE WOOD BLOCK IS BEING ATTACHED TO THE ROOF. WPB |
| | AMEND. TO FBC SEC. 107.2.1.2ND REQUEST. |
| | 101) HT. P.803 - DETAIL #3 SHOWS JOINTS UNDER THE SLAB |
| | - PLUMBING SPECIFICATIONS SEC.221110 - PART 2 - 2.02 |
| | STATES THAT "ENTRANCE PIPING TO THE BUILDING TO |
| | TERMINATE ABOVE GRADE." THE DETAIL ON P.803 SHOWS |
| | FLANGED FITTINGS UNDER THE SLAB. CLARIFY. IF THIS |
| | PIPING ARRANGEMENT IS TO REMAIN, SUBMIT DETAILS ON |
| | FITTING RESTRAINTS AND THRUST BLOCK INFORMATION. WPB |
| | AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.2ND REQUEST. |
| | 102) RIGID SUPPORT SWAY BRACING SHALL BE PROVIDED AT |
| | CHANGES IN DIRECTION GREATER THAN 45 DEGREES FOR PIPE |
| | SIZES 4 INCHES AND LARGER PER FBC-PLUMBING SEC.308.6. |
| | SUBMIT DETAILS FOR THE BRACING. 2ND REQUEST. |
| | 103) SHT. P.804 - DETAIL #7 - THE REDUCED PRESSURE |
| | BACKFLOW PREVENTER AT HE TRASH CHUTE REQUIRES A DRAIN |
| | PIPED TO AN APPROVEDD POINT OF DISPOSAL.M |
| | 104) THE PLUMBING SPECIFICATIONS SECTION 22 1323 - PART |
| | 2 - SECTION 2.01 (GREASE INTERCEPTOR) :TAG # GT-1 - |
| | SECTION C -ACCESSORIES: CALLS OUT A 4-INCH INFLUENT AND |
| | EFFLUENT TWO-WAY CLEANOUT, BUT ALSO CALLS OUT A 6-INCH |
| | SAMPLING PORT. THIS WOULD CREATE AN OBSTRUCTION TO FLOW |
| | AND VIOLATES FBC-PLUMBING SEC.706.2. THIS SECTION ALSO |
| | CALLS OUT A SCHIER INTERCEPTOR WITH 6-INCH INLET AND |
| | OUTLET. CLARIFY. 2ND REQUEST. THE SUBMITTED RESPONSE |
| | NARRATIVE STATES THE 4 INCH REFERENCE IS INCCORRECT BUT |
| | THE SPECIFICATION IS STILL WRONG.CORRECT THE |
| | SPECIFICATION. |
| | NOTE: WHEN THE REVISED PLANS ARE UPLOADED, ENSURE THEY |
| | ARE DONE IN SEQUENTIAL ORDER AND THAT ALL PLANS ARE IN |
| | SEQUENTIAL ORDER. I HAVE WASTED AN INORDINATE AMOUNT OF |
| | TIME DURING THIS LAST REVIEW SEARCHING THROUGH NUMEROUS |
| | DRAWINGS TO FIND THE CORRECT PLAN THAT WAS SUPPOSED TO |
| | HAVE ADDRESSED THE REVIEW COMMENT. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |