2021-02-19 11:02:151) SHT. C.03 SHOWS A 15 INCH PVC RWL NEAR THE SOUTHWEST
 CORNER OF THE PROPERTY NEAR THE BUS STOP. THE LINE IS
 NOT SHOWN ON SHT. P100 ( NEAR COLUMN LINE #1). CLARIFY.
 2) SHT.L5-711 - THE POOL DECK SHOWER DOES NOT APPEAR TO
 BE COMPLIANT WITH ANSI A117.1-1986 SEC.4.25.4.FOR FAIR
 HOUSING ACT COMPLIANCE. THE CONTROL RING APPEARS LIKE
 IT MAY REQUIRE GRASPING OR TWISTING OF THE WRIST TO
 OPERATE WHICH WILL VIOLATE THIS SECTION. THE SUBMITTED
 SPECIFICATION SHEET DOES NOT SHOW THAT THIS A HANDICAP
 ACCESSIBLE COMPLIANT UNIT. PROVIDE DOCUMENTATION TO
 SHOW COMPLIANCE.THE RESPONSE NARRATIVE REFERS TO DETAIL
 #8 ON THIS SHEET BUT THE DETAIL SHOWS A PLAN VIEW OF
 THE SHOWER WHICH DOES NOT ADDRESS THIS COMMENT. 2ND
 REQUEST.
 3) SHT. L5-711 - SHOW THE HEIGHT OF THE SHOWER CONTROL
 RING FROM FINISH GRADE TO THE CENTER OF THE CONTROL
 RING IN US CUSTOMARY UNITS.THE SPECIFICATION CURRENTLY
 SHOWS THE MEASUREMENT IN WHAT APPEARS TO BE
 MILLIMETERS. THE HEIGHT OF THE CONTROL RING SHALL
 COMPLY WITH ANSI A117.1-1986 SECS.4.2.5 & 4.2.6.
 4) SHT.A0.203 - ALTERNATIVE ROLL-IN SHOWER W/SEAT - THE
 CONTROLS SHALL BE LOCATED A MAXIMUM OF 15 INCHES FROM
 THE CENTERLIINE OF THE SEAT TO THE CENTERLINE OF THE
 CCONTROLS PER FBC-ACCESS. SEC.608.5.3 AND FIGURE
 608.5.3. THE DRAWING SHOWS THE 15 INCHES TO THE EDGE OF
 THE CONTROL AREA, NOT TO THE CENTER.
 5) SHT. A1.256 - SHT. A1.256 - OFFICE TOWER FLOOR PLAN
 - ROOF LEVEL - SUBMIT INFORMATION FOR THE CHEMICAL
 TREATMENT SYSTEM. SUBMIT MSDS SHEETS FOR THE CHEMICALS
 BEING USED. SUBMIT INFORMATION ON THE AMOUNTS OF EACH
 CHEMICAL BEING USED, WHERE THEY ARE BEING STORED, THE
 TYPES OF CONTAINERS THE CHEMICALS ARE STORED IN, ETC.
 COMPLIANCE WITH SEC. 414 & 415 OF THE 2014 FBC MAY BE
 REQUIRED. THE SUBMITTED RESPONSE NARRATIVE STATES THIS
 SYSTEM IS LIISTED UNDER THE DEFERRED SUBMITTALS ON SHT.
 M.002 BUT IT IS NOT.
 6) SHT.A1.502A - DETAIL #2 DOES NOT SHOW A SEAT IN THE
 SHOWER AND DETAIL #3 SHOWS A SEAT. CLARIFY.
 7) SHT. A1.503 - DETAIL #2 - SHOW THE LOCATION OF THE
 SHOWER CONTROLS. THE LOCATION OF THE CONTROLS SHALL
 COMPLY WITH FBC-ACCESS. SEC.608.5.2.
 8) SHT. A1.532 - MASTER BATH - THE FLOOR PLAN SHOWS THE
 DOOR SWINGING INTO THE SHOWER AND THE TOILET
 COMPARTMENT. THE INSWING DOOR IS IMPEDING ACCESS TO THE
 SHOWER CONTROLS AND THE USE OF THE TOILET AND DOES NOT
 COMPLY WITH FAIR HOUSING. REVERSE THE SWING OF THE
 DOOR.
 9) SHT. A1.532 - SHOW THE REQUIRED CLEAR FLOOR SPACE AT
 ALL THE FIXTURES IN THE FHA ADAPTABLE BATHROOM. WPB
 AMEND. TO FBC SEC. 107.2.1.
 10) SHT.A1.600 - DETAIL #1 - WOMEN'S RESTROOM - THE
 PLAN STATES A CLEAR FLOOR SPACE OF 60 INCHES WIDE FOR
 THE ACCESSIBLE STALL BUT THE PLAN ALSO SHOWS THE INSIDE
 CLEAR WIDTH AS 4 FEET 11 1/2 INCHES. IF THIS IS A ROUGH
 DIMENSION THEN THIS STALL WILL NOT BE WIDE ENOUGH AFTER
 FINISH. COMPLY WITH FBC-ACCESS. SEC.604.3.1.2ND
 REQUEST. CLARIFY.
 11) SHT. A1.600 - SHT.A1.600 - DETAIL #1 - MEN'S
 RESTROOM - ONE OF THE URINALS IS SHOWN AS 1 FOOT 2
 INCHES FROM A WALL TO THE CENTERLINE OF THE URINAL. A
 MINIMUM OF 15 INCHES FROM A WALL TO THE CENTER OF THE
 URINAL IS REQUIRED. FBC-PLUMBING SEC.405.3.1. 2ND
 REQUEST.
 12) SHT. A1.600 - GROUND LEVEL BATHROOM #0132- IS THIS
 A UNISEX TOILET ROOM OR GENDER SPECIFIC? CLARIFY.2ND
 REQUEST.
 13) SHT.A1.601 - DETAIL # 1 - GROUND LEVEL BATHROOM
 #0121 - THE DOOR TO ONE OF THE TOILET ROOMS IS SWINGING
 INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY.
 FBC-ACCESS. SEC. 603.2.3. SEE EXCEPTIONS. SHOW THE
 REQUIRED 30 INCH MINIMUM BY 48 INCH MINIMUM CLEAR FLOOR
 SPACE BEYOND THE ARC OF THE DOOR SWING ON THE PLANS. IT
 IS NOT SHOWN. 2ND REQUEST.
 14) SHT. A1.601 - DETAIL #1 - TOILET ROOM #0121 - THE
 DOOR IS IN FRONT OF THE WATER CLOSET. THE WATER CLOSET
 CANNOT OVERLAP THE REQUIRED MANEUVERING CLEARANCE FOR
 THE DOOR INSIDE THE ROOM. SHOW THE REQUIRED MANEUVERING
 CLEARANCE FOR THE DOOR IN ACCORDANCE WITH FBC-ACCESS.
 404.2.4.
 15) SHT. A1..602 - DETAIL #1 - WOMEN'S RESTROOM #0731-
 SHOW THE INSIDE CLEAR LENGTH OF THE AMBULATORY
 ACCESSIBLE TOILET STALL AND THE STANDARD TOILET STALLS.
 THE DIMENSIONS SHOWN ON THE PLAN ARE NOT CLEAR INSIDE
 DIMENSIONS. FBC-ACCESS. SEC.604.8.2.1,
 604.8.2FBC-PLUMBING SEC.405.3.1.2ND REQUEST.
 16) SHT. A1.603 - DETAILS #1 & #5 - IDENTIFY ON THE
 PLANS THAT THESE BATHROOMS ARE LOCATED IN THE HOTEL.
 2ND REQUEST.
 17) SHT. A1.607 - DETAIL #8 - THERE ARE NOTES ON THE
 PLAN POINTING TO NOTHING AND TO WRONG ITEMS, LOCATION
 OF GRAB BAR REINFORCEMENT IS WRONG,AND THE DOOR SWINGS
 INTO THE SHOWER. A PERSON IN A WHEELCHAIR WOULD NOT BE
 ABLE TO ACCESS THE CONTROLS. REVERSE THE DOOR SWING ON
 THE SHOWER.
 18) SHT. A1.607 - DETAIL #6 - IDENTIFY THE FHA BATHROOM
 TYPE ON THE PLANS.
 19) SHT. A1.608 - DETAIL #5 CALLS OUT A MASTER BATH BUT
 THE FLOOR PLAN SHOWS A KITCHEN. CLARIFY.
 20) SHT. A1.608 - DETAIL #4 - IDENTIFY THE FHA BATHROOM
 TYPE ON THE DETAIL AND PLEASE FIX THE OVERLAY OF THE
 UNIT NUMBER OVER THE COLUMN NUMBER.
 21) SHT. A1.608 - DETAIL #10 - THE LOCATION OF THE GRAB
 BAR REINFORCEMENTS ARE SHOWN IN THE MIDDLE OF THE
 FLOOR. CLARIFY.
 22) SHT. A1.609 - DETAIL #5 - THERE IS AN OVERLAY ON
 THIS DETAIL THAT NEEDS TO BE REMOVED AND ALSO FLOATING
 NOTES. CLEAN UP THIS DETAIL. WPB AMEND. TO FBC SEC.
 107.2.1.
 23) SHT.A1.609 - DETAIL #2 - CLEAN UP THIS DETAIL.
 CLEAR FLOOR SPACE IS SHOWN IN THE CLOSET. IF THIS IS
 SUPPOSED TO BE AN FHA COMPLIANT BATHROOM IT IS NOT. A
 WATER CLOSET CANNOT BE LOCATED NEXT TO THE SHOWER
 BECAUSE THE REQUIRED FLOOOR SPACE FOR THE SHOWER CANNOT
 BE PROVIDED. A NOTE ON THIS DETAIL STATES "BATHROOM 1
 FHA TYPE B." CLARIFY.
 24) SHT. A1.609 - DETAILL # 3 - INDICATE ON THE DETAIL
 IF THIS IS THE FHA COMPLIANT BATHROOM. IF SO, SHOW ALL
 THE REQUUIRED CLEAR FLOOR SPACES, LOCATION OF GRAB BAR
 REINFORCEMENT, AND THE DOORS ON THE SHOWER AND THE
 TOILET CCOMPARTMENT CANNOT SWING IN PER FHA DESIGN
 MANUAL/GUIDELINES.
 25) SHT. A1.609 - DETAIL #4 CALLS OUT BATHROOM 3 BUT
 THERE IS NO BATHROOM PLAN SHOWN. CLARIFY.
 26) SHT. A1.609 - DETAIL #8 - CORRECT THE LOCATION OF
 THE GRAB BAR REINFORCEMENT FOR THE TOILET ON THE PLAN.
 27) SHT. A1.609 - DETAIIL #9 - IF THIS IS SUPPOSED TO
 BE AN FHA COMPLIANT BATHROOM IT IS NOT. A WATER CLOSET
 CANNOT BE LOCATED NEXT TO THE SHOWER BECAUSE THE
 REQUIRED FLOOOR SPACE FOR THE SHOWER CANNOT BE
 PROVIDED. CLARIFY.
 28) SHT. A1.610 - DETAIL # 2 - CLEAN UP THIS PLAN. THE
 LAVATORY IS SHOWN LOCATED PARTIALLY IN THE WALL.
 29) SHT. A1.610 - DETAIL #1 - THE FLOOR PLAN SHOWS THE
 DOOR SWINGING INTO THE SHOWER AND THE TOILET
 COMPARTMENT. THE INSWING DOOR IS IMPEDING ACCESS TO THE
 SHOWER CONTROLS AND THE USE OF THE TOILET AND DOES NOT
 COMPLY WITH FAIR HOUSING. REVERSE THE SWING OF THE
 DOOR.
 30) SHT. A1.610 - DETAIL #3 - THE NOTES AND DETAILS FOR
 THE GRAB BAR REINFORCEMENT DON'T MAKE SENSE. CORRECT
 THE DEFICIENCIES. IF THIS IS SUPPOSED TO BE AN FHA
 OMPLIANT BATHROOM SHOW ALL CLEAR FLOOR FLOOOR SPACES
 AND THE FHA BATHROOM TYPE ON THE PLAN. THE LAVATORY
 APPEARS LIKE ENCROACH INTO THE REQUIRED CLEAR FLOOR
 SPACE FFOR THE SHOWER.CLARIFY.
 31) SHT. A1.610 - DETAIL # 6 - IF THIS IS THE FHA
 COMPLIANT BATHROOM, PLACE THE TYPE OF FHA BATHROOM ON
 THE PLAN AND CORRECT THE OVERLAY OF THE UNIT NUMBER ON
 THE FLOOR PLAN.PLEASE CORRECT THE OVERLAY ON DETAIL #5
 ALSO.
 32) SHT. A1.610 - DETAIL #7 - CORRECT THIS DETAIL.
 LOCATION OF REINFORCEMENT AND CLEAR FLOOR SPACES ARE
 OUT OF WHACK. CONTROLS ARE CALLED OUT ON THE
 LAVATORY.BATHROOM FLOOR PLAN IS CUTOFF AND INCOMPLETE.
 CLARIIFY.
 33) SHT. P1.00 - THERE IS A LINE IDENTIFIED AS "8 INCH
 CWS UP" AND THE ARROW APPEARS TO POINT TO A 10 INCH
 SANITARY LINE. REFER TO COLUMN LINE G-11 NEAR STAIR #1.
 CLARIFY.
 34) SHT. P100 - EXPAND THE PIPING LAYOUT FOR THE
 SANITARY AND VENT LINES AND TAG THE RISERS AT THE
 TOILET ROOMS BY ELEVATORS P03, P04, & P05 ON COLUUMN
 LINE H.
 35) SHT. P100 - ONE OF THE 6 INCH KW LINES BY THE
 GREASE IINTERCEPTORS IS ALSO LABELED AS AN 8 INCH CW
 UP. CLARIFY.
 36) SHT. P100 - THERE ARE A LOT OF DRAIN LINES ON THIS
 PLAN, ESPECIALLY AT THE STAIRS, THAT BEAR NO RISER
 TAGS.CLARIFY.
 38) SHT. P.101 & SHT. P.101B SHOWS AN 8 INCH SANITARY
 LINE WITHIN THE STAIRWAY # 4 AND ALSO A 4 INCH GW LINE
 IN STAIRWAY #10. THE LINE IS NOT PERMITTED WITHIN THE
 STAIRWAY PER FBC-BUILDING SEC.1023.5.
 39) SHTS. P.101A, P.101B, P.101C, & P.101C - THERE ARE
 DRAIN, GAS, RAINWATER, CONDENSATE AND WATER LINES THAT
 HAVE NO RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING
 LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS
 IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE
 REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO
 FBC SEC. 107.2.1, 107.3.5.1.3.
 40) IDENTIFY THE STAIR NUMBERS ON THE PLUMBING SHEETS.
 THIS WILL HELP IN DETERMINING THE LOCATION OF PIPE
 SYSTEMS ON THE RE-REVIEW.WPB AMND. TO FBC SEC.
 107.2.1.2ND REQUEST.
 41) SHTS. P.102A, P.102B, P.102C, P.102D - THERE ARE
 DRAIN, RAINWATER, CONDENSATE AND WATER LINES THAT HAVE
 NO RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING
 LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS
 IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE
 REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO
 FBC SEC. 107.2.1, 107.3.5.1.3.
 42) SHTS.P.103A, P.103B, P.103C, P.103D - THERE ARE
 DRAIN, RAINWATER, CONDENSATE AND WATER LINES THAT HAVE
 NO RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING
 LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS
 IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE
 REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO
 FBC SEC. 107.2.1, 107.3.5.1.3.
 43 - SHTS. P.104A THROUGH SHT. P104D - THERE ARE DRAIN,
 RAINWATER, CONDENSATE AND WATER LINES THAT HAVE NO
 RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING
 LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS
 IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE
 REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO
 FBC SEC. 107.2.1, 107.3.5.1.3.
 44) SHTS. P1.05A THROUGH P.105D - THERE ARE DRAIN,
 RAINWATER, CONDENSATE AND WATER LINES THAT HAVE NO
 RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING
 LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS
 IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE
 REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO
 FBC SEC. 107.2.1, 107.3.5.1.3.
 45) SHTS. P.106A THROUGH SHT. 106D - THERE ARE DRAIN,
 RAINWATER, CONDENSATE AND WATER LINES THAT HAVE NO
 RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING
 LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS
 IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE
 REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO
 FBC SEC. 107.2.1, 107.3.5.1.3.
 46) SHTS. P.107A THROUGH P.107D - THERE ARE DRAIN,
 RAINWATER, CONDENSATE AND WATER LINES THAT HAVE NO
 RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING
 LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS
 IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE
 REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO
 FBC SEC. 107.2.1, 107.3.5.1.3.
 47) SHTS. P.108A THROUGH P.108D - THERE ARE DRAIN,
 RAINWATER, CONDENSATE AND WATER LINES THAT HAVE NO
 RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING
 LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS
 IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE
 REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO
 FBC SEC. 107.2.1, 107.3.5.1.3.
 48) SHT. P.105D SHOWS 2-4INCH RW LINES WITHIN THE
 STAIRWAY #7. THESE LINES ARE NOT PERMITTED WITHIN THE
 STAIRWAY PER FBC-BUILDING SEC.1023.5.
 49) SHT. P.106D SHOWS FOUR- 4 INCH ROOF DRAINS AND A 4
 INCH RW LINE WITHIN STAIRWAY #7.THE LINES ARE NOT
 PERMITTED WITHIN THE STAIRWAY PER FBC-BUILDING
 SEC.1023.5.
 50) SHTS. P.107A, P.107C & P.107D - THE DRAWINGS SHOW
 RAINWATER DRAIN PIPING AND ROOF DRAINS LOCATED IN
 STAIRWAYS #5, #12, & #7. THESE LINES AND DRAINS ARE NOT
 PERMITTED WITHIN THE STAIRWAY PER FBC-BUILDING
 SEC.1023.5.
 51) SHTS. P.108A, P.108B, P.108C - THE DRAWINGS SHOW
 RAINWATER DRAIN PIPING, DRAINS AND CONDENSATE PIPING IN
 STAIRWAYS #5, 8 & #9. THE LINES AND DRAINS ARE NOT
 PERMITTED WITHIN THE STAIRWAY PER FBC-BUILDING
 SEC.1023.5.
 52) THE OVERALL PIPNG PLANS FOR THE PODIUM LEVELS ARE
 MISSING SECTIONS OF PIPING AND BASICALLY HAVE NO
 INFORMATION ON THEM AND ARE USELESS FOR REVIEW.I
 UNDERSTAND THAT THESE ARE OVERALLL PLANS BUT THE
 DRAWINGS ARE MISSING BASIC ESSENTIAL INFORMATION FOR
 PLAN REVIEW. WPB AMEND. TO FFBC SEC. 107.2.1,
 107.3.5.1.3.
 53) SHTS. P.251 THROUGH 256 - THE RISER TAGS FOR THE LW
 RISERS ARE MISSING THE DRAWING LOCATIONS ON THE RISER
 TAGS. CLARIFY.
 54) SHTS. P. 258 THROUGH P.261 - THE RISER TAGS FOR THE
 LW RISERS ARE MISSING THE DRAWING LOCATIONS ON THE
 RISER TAGS.CLARIFY.
 55) SHT. P.510 - DETAIL #6 - TWO LAVATORIES ARE MISSING
 FROM THE SANITARY RISER. CLARIFY.
 56) SHT. P.510 - DETAIL #3 - A LAVATORY IN THE MEN'S
 AND WOMEN'S HANDICAP STALL IS MISSING FROM SANITARY
 RISER. CLARIFY.
 57) SHT. P.510 - DETAILS #2 & #3 THE DRINKING FOUNTAINS
 ARE MISSING FROM THE SANITARY AND WATER RISERS.
 58) SHT. P.5.11 - DETAIL #4 - ROOMS #0243 & 0245 - THE
 URINAL DOES NOT APPEAR TO BE VENTED. CLARIFY.
 59) SHT. P.511 -DETAIL #4 - THE LAVATORY IN THE
 HANDICAP STALL IN THE WOMEN'S CHANGING FACILITY IS NOT
 SHOWN ON THE SANITARY RISER.
 60) SHT. P.511 - DETAIL #4 - IT APPEARS THERE IS A
 STANDARD WATER CLOSET IN THE WOMEN'S CHANGING FACILITY
 THAT IS NOT SHOWN ON THE SANITARY RISER DIAGRAM.
 61) SHT. P.511 - DETAIL #4 - THE LAVATORY IN THE MEN'S
 HANDICAP STALL IS NOT SHOWN ON THE SANITARY RISER.
 62) SHT. P.511 - DETAIL #4 - THERE IS A LAVATORY ON THE
 RISER DIAGRAM FOR THE MEN'S CHANGING FACILITY THAT IS
 NOT SHOWN ON THE FLOOR PLAN. 61) SHT. P.503 -
 63) SHT. P.513 - DETAIL #1 - REVVISE THIS DETAIL TO
 CLEARLY SHOW THE 3 LAVATORIES IN EACH RESTROOM. THERE
 IS AN OVERLAY THAT CURRENTLY LOOKS LIKE 5 LAVATORIES.
 2ND REQUEST.
 64) SHT. P.514 - DETAI #5 - THE LW RISER TAGS DO NOT
 HAVE DRAWING LOCATIONS ON THE RISER TAGS. CLARIFY.
 65) SHT. P.514 - DETAIL#6 - THE LAVATORY IN THE WOMEN'S
 HANDICAP ACCESSIIBLE STALL IS NOT SHOWN ON THE SANITARY
 RISER. CLARIFY.
 66) SHT. P.701 - THE RISER TAGS AT THE BOTTOM AND TOP
 OF THE HOTEL/OFFICE DOMESTIC WATER RISERS ARE MISSING
 THE DRAWING LOCATIONS. CLARIFY.
 67) SUBMIT A PIPING DETAIL FOR MASTER THERMOSTATIC
 MIXING VALVES TMV-1, TMV-2 & TMV-3. THE PIPING FOR
 RECIRCULATION SYSTEMS HAVING MASTER THERMOSTATIC VALVES
 SHALL CCOMPLY WITH FBC-PLUMBING SEC. 607.2.2. 2ND
 REQUEST.
 68) SHT. P.702 - THERE ARE BRANCHES OFF THE WATER
 RISERS THAT SOME HAVE NO SIZES OR THE AREA THEY SUPPLY.
 REFER TO LEVELS 2-8. SUPPLY THE REQUIRED INFO. WPB
 AMEND. TO FBC SEC. 107.3.5.1.3. 2ND REQUEST.
 69) SHT. P.703 - ALMOST ALL OF THE RISER TAGS ARE
 MISSING DRAWING LOCATION INFORMATION. CLARIFY.
 70) SHT. P.703A & P.703B - THERE ARE DRAWING LOCATION
 NUMBERS MISSING FROM NUMEROUS RISER TAGS ON THESE
 SHEETS.SUPPLY THE APPLICABLE DRAWING LOCATION NUMBERS
 ON THESE TAGS.
 71) SHT. P.703A - THE STACK DESIGNATION TYPE AND RISER
 NUMBERING ON THE RISER TAGS DOES NOT CORRELATE WITH THE
 REFERENCED RISER TAGS ON SHTS. P502 & SHT. P.503.
 CLARIFY.
 72) SHT. P.703B - RISER TAGS ARE MISSING THE DRAWING
 LOCATION NUMBERS ON THE RISER TAGS. ENSURE ALL RISER
 TAGS ARE COMPLETE.
 73) SHT. P.704 - NUMEROUS RISER TAGS ARE MISSING
 DRAWING LOCATION INFORMATION/NUMBERS.
 74) SHT. P.704A - RISER TAGS ARE MISSING THE DRAWING
 LOCATION NUMBERS ON THE RISER TAGS. ENSURE ALL RISER
 TAGS ARE COMPLETE.
 75) SHT. P.704B - RISER TAGS ARE MISSING THE DRAWING
 LOCATION NUMBERS ON THE RISER TAGS. ENSURE ALL RISER
 TAGS ARE COMPLETE.
 76) SHT. P.705A - THE PRINTING ON THE RISER TAGS IS SO
 LIGHT THAT IT IS ILLEGIBLE. PROVIDE LEGIBLE INFO. WPB
 AMEND. TO FBC SEC. 107.2.1.
 77) SHT. SHT. P.706 - DETAILS #7, 8, 10, 11, &12 - ONLY
 4 FIXTURE UNITS ARE ALLOWED ON A 2 INCH WET VENT PER
 FBC-PLUMBING TABLE 912.3. THE HORIZONTAL DRAIN FROM THE
 WATER CLOSET SHALL BE 3 INCHES UP TO THE FIRST
 HORIZONTAL FIXTURE DRAIN (BATHTUB/SHOWER).
 78) SHT. P.706 - DETAIL #9 - THE HORIZONTAL DRAIN FROM
 THE WATER CLOSET UP TO THE FIRST HORIZONTAL BRANCH
 SHALL BE 3 INCHES IN DIAMETER PER FBC-PLUMBING TABLE
 912.3.
 79) SHT. P.706 - DETAIL #10 & #20 - THE BATHTUBS ARE
 NOT VENTED. THEY CANNOT CONNECT DIRECTLY TO THE SHOWER
 OR WATER CLOSET FIXTURE DRAIN. FBC-PLUMBING
 SECS.1002.1, 901.2.
 80) SHT. P.706 - DETAIL #19 - THE DRAIN FROM THE
 WASHING MACHINE BOX TO THE STACK SHALL BE A MINIMUM OF
 3 INCHES IN DIAMETER PERR FBC-PLUMBING SEC.406.2.
 81) SHT. P.707 - DETAILS #1,2,3,4,,& 5 - RISER TAG
 NUMBERS, STACK DESIGNATION AND DRAWING LOCATION
 INFORMATION IS MISSING FROM THE RISER TAGS. ENSURE ALL
 RISER TAGS ARE COMPLETE.
 82) SHT. P.709 - THE DRAIN FROM THE WASHING MACHINE BOX
 TO THE STACK SHALL BE A MINIMUM OF 3 INCHES IN DIAMETER
 PERR FBC-PLUMBING SEC.406.2.
 83) SHT. P.709 - THE DRAWING LOCATION INFORMATION IS
 MISSING FROM ALL OF THE WASTE AN SANITARY STACK RISER
 DIAGRAMS. ENSURE ALL RISER TAGS ARE COMPLETE.
 84) SHT. P.709 - IDENTIFY THE CONTINUATION POINTS OF
 BOTH 6 INCH VERTICAL SANITARY DRAINS THAT TURN DOWN.
 85) SHT. P.710 - DETAIL #5 - THE WATER RISER DIAGRAM
 DOES NOT CORRELATE WITH THE REFERENCED ENLARGED FLOOR
 PLAN DETAIL #5 ON SHT. P.505. THESES ARE TWO DIFFERENT
 UNITS. CLARIFY.
 86) SHT.P.710 - DETAIL #4 - THE WATER CONNECTION FROM
 THE WATER RISER TO THE UNIT IS MISSING. CLARIFY.
 87) SHT. P.711 - DETAIL #2 - THERE IS A BATHTUB MISSING
 ON THE WATER RISER IN ONE OF THE BATHROOMS AND THE
 SHOWER IS LABELED AS A BATHTUB IN THE SAME BATHROOM,
 AND ONLY ONE LAVATORY IS SHOWN ON THE RISER IN THIS
 SAME BATH. CLARIFY.
 88) SHT. P.711 - DETAIL #2 - THERE IS A BATHTUB SHOWN
 ON THE WATER RISER IN THE MASTER BATH BUT IT IS NOT
 SHOWN ON THE FLOOR PLAN AND THE WATER CLOSET AND
 LAVATORY ARE REVRSED ON THE WATER RISER IN THE MASTER
 BATH.. CLARIFFY.
 89) SHT. P.711 - DETAIL #6 -THE LAYOUT OF THE FIXTURES
 ON THE WATER RISER DIAGRAM DOES NOT CORRELATE WITH THE
 LAYOUT OF THE PLUMBING FIXTURES ON REFERENCED SHT.
 P.507, DETAIL #2. ALSO, THE RISER TAG INFORMATION IS SO
 LIGHT IT IS ILLEGIBLE. CLARIFY.
 90) SHT. P.712 - DETAIL #F - THE SANITARY RISER IS
 INCOMPLETE. FIXTURES ARE MISSING. EXPAND THE RIDER SO A
 PROPER REVIEW CAN BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1, 107.3.5.1.3.
 91) SHT. P.712 - THE WATER SUPPLY BRANCHES FROM THE
 RISERS TO THE MEN'S AND WOMEN'S OFFICE TOILET RROOMS
 REQUIRE SHUTOFF VALVES TO RESTROOMS. FBC-PLUMBING SEC.
 606.1.
 92) SHT. P.712 - DETAILS #3, #4, & #6 - THE RISER TAGS
 ARE MISSING THE RISER INFORMATION. ENSURE ALL RISER
 TAGS ARE COMPLETE.
 93) SHT. P.712 - DETAIL #6 - THE DRINKING FOUNTAINS
 SHOWN ON DETAIL #3 ARE NOT SHOWN ON THE WATER RISER ON
 DETAIL #6 OR THE WATER RISER FOR THE OFFICE TOWER -
 WOMEN'S TOILET ROOM. CLARIFY.
 94) SHT. P.720 - IDENTIFY ALL RISERS WITH RISER TAGS
 COMPLETE WITH ALL RISER TAG INFO AND FIXTURE UNIT
 LOADS. THERE ARE STILL RISERS THAT HAVE NO TAGS. WPB
 AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.
 95) SHT. P.730 - IDENTIFY ALL RISERS WITH RISER TAGS
 COMPLETE WITH ALL RISER TAG INFO AND THE GPM'S DRAINING
 INTO EACH RISER. WPB AMEND. TO FBC SEC. 107.2.1,
 107.3.5.1.3.
 96) SHT. P.731 - THE DRAWING IS INCOMPLETE.SECTIONS OF
 PIPE ARE MISSING, PIPE SIZES ARE MISSING, NO RISER
 TAGS, SECTIONS OF THE PIPING SYSTEM ARE CONGESTED AND
 DIFICULT TO REVIEW.WPB AMEND. TO FBC SEC. 107.2.1,
 107.3.5.1.3.
 97) SHT. P.732 - THE RISER SHOWS THE SQUARE FOOTAGE
 AREA BEING DRAINED BUT NO GPM'S. COMPLY WITH
 FBC-PLUMBING SEC. 11106.2. CLARIFY.
 98) SHT. P.733- THERE ARE SEVERAL RISER TAGS MISSING
 THE DRAWING LOCATION INFORMATION.ENSURE ALL RISER TAGS
 ARE COMPLETE.
 99) SHT. P.734 - THERE ARE SEVERAL RISER TAGS MISSING
 THE DRAWING LOCATION INFORMATION.ENSURE ALL RISER TAGS
 ARE COMPLETE.
 100) SHT. P.803 - DETAIL #9 - SUBMIT DETAILS AS TO HOW
 THE WOOD BLOCK IS BEING ATTACHED TO THE ROOF. WPB
 AMEND. TO FBC SEC. 107.2.1.2ND REQUEST.
 101) HT. P.803 - DETAIL #3 SHOWS JOINTS UNDER THE SLAB
 - PLUMBING SPECIFICATIONS SEC.221110 - PART 2 - 2.02
 STATES THAT "ENTRANCE PIPING TO THE BUILDING TO
 TERMINATE ABOVE GRADE." THE DETAIL ON P.803 SHOWS
 FLANGED FITTINGS UNDER THE SLAB. CLARIFY. IF THIS
 PIPING ARRANGEMENT IS TO REMAIN, SUBMIT DETAILS ON
 FITTING RESTRAINTS AND THRUST BLOCK INFORMATION. WPB
 AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.2ND REQUEST.
 102) RIGID SUPPORT SWAY BRACING SHALL BE PROVIDED AT
 CHANGES IN DIRECTION GREATER THAN 45 DEGREES FOR PIPE
 SIZES 4 INCHES AND LARGER PER FBC-PLUMBING SEC.308.6.
 SUBMIT DETAILS FOR THE BRACING. 2ND REQUEST.
 103) SHT. P.804 - DETAIL #7 - THE REDUCED PRESSURE
 BACKFLOW PREVENTER AT HE TRASH CHUTE REQUIRES A DRAIN
 PIPED TO AN APPROVEDD POINT OF DISPOSAL.M
 104) THE PLUMBING SPECIFICATIONS SECTION 22 1323 - PART
 2 - SECTION 2.01 (GREASE INTERCEPTOR) :TAG # GT-1 -
 SECTION C -ACCESSORIES: CALLS OUT A 4-INCH INFLUENT AND
 EFFLUENT TWO-WAY CLEANOUT, BUT ALSO CALLS OUT A 6-INCH
 SAMPLING PORT. THIS WOULD CREATE AN OBSTRUCTION TO FLOW
 AND VIOLATES FBC-PLUMBING SEC.706.2. THIS SECTION ALSO
 CALLS OUT A SCHIER INTERCEPTOR WITH 6-INCH INLET AND
 OUTLET. CLARIFY. 2ND REQUEST. THE SUBMITTED RESPONSE
 NARRATIVE STATES THE 4 INCH REFERENCE IS INCCORRECT BUT
 THE SPECIFICATION IS STILL WRONG.CORRECT THE
 SPECIFICATION.
 NOTE: WHEN THE REVISED PLANS ARE UPLOADED, ENSURE THEY
 ARE DONE IN SEQUENTIAL ORDER AND THAT ALL PLANS ARE IN
 SEQUENTIAL ORDER. I HAVE WASTED AN INORDINATE AMOUNT OF
 TIME DURING THIS LAST REVIEW SEARCHING THROUGH NUMEROUS
 DRAWINGS TO FIND THE CORRECT PLAN THAT WAS SUPPOSED TO
 HAVE ADDRESSED THE REVIEW COMMENT.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW