Plan Review Notes For Permit 18100540
Permit Number 18100540
Review Stop M
Sequence Number 3
Notes
Date Text
2021-01-07 09:01:373RD REVIEW FBC-2017 MECHANICAL
 PERMIT-18100540
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M.201A AND SHEET M.201B: PLEASE SHOW A DETAIL
 OF THE MECHANICAL SYSTEM FOR THE EXIT PASSAGEWAY
 SHOWING HOW IT MEETS FBC M 601.3. THE EXIT PASSAGEWAY
 CANNOT BE SERVED BY A SYSTEM THAT SERVES ANY OTHER
 AREA.
  
 2) SHEET M.201A AND M.201B: PLEASE EXPLAIN THE INTAKE
 DUCT IN ELECTRIC ROOM (E4) FBC 107.2.1
  
 3) PREVIOUS COMMENT #12- THE RESPONSE STATES TO LOOK ON
 SHEET MP.002 FOR THE REMOTE FUEL FILL STATION AND FILL
 PIPE. THERE IS NO MP.002 SHEET SUBMITTED IN THIS
 PACKAGE.
  
 4) SHEET M.715 AND SHEET M.707: THE DRYER EXHAUST
 DIAGRAM SHOWS OFF SETS IN SEVERAL RISERS, PLEASE SHOW
 HOW THIS WOULD MEET FBC M 504.8 (4)
  
 5) SHEET M.715: PLEASE SHOW THAT THE EXHAUST FAN FOR
 THE DRYER EXHAUST SUB DUCT MEETS FBC M 504.8 (5)
  
 6) SHEET M.715: PLEASE SHOW THAT THE EXHAUST FAN FOR
 THE DRYER SUBDUCT MEETS FBC M 504.8 (8)
  
 7) SHEETS M.254- SHEET M.262: PLEASE REMOVE THE DRYER
 BOOSTER FANS AS THERE IS NO REFERENCE OF THESE IN THE
 2014 FBC M.
  
 8) THE DRYER EXHAUST DUCT MUST BE INSTALLED BY THE
 MANUFACTURES INSTALLATION INSTRUCTIONS. THE TYPICAL
 DRYER INSTALLATION MANUAL WILL ALLOW ONLY (4) 90 DEGREE
 FITTINGS IN A SINGLE RUN. I DO SEE SEVERAL DRYER DUCT
 WITH MORE THAN THE 4 90 DEGREE FITTINGS IN A SINGLE
 RUN, PLEASE CORRECT THIS. FBC M 504.6.4.2
  
 9) PLEASE PROVIDE A LETTER FROM THE DRYER MANUFACTURER
 STATING THAT THE X VENT DRYER EXHAUST TERMINATION IS
 ALLOWED WITH EACH SPECIFIC DRYER. THE X VENT IS UNIQUE
 IN THE FACT THAT IT USES BOTH THE BACK-DRAFT DAMPER AND
 THE LOUVER. THE INSTALLATION MANUAL DOES NOT ADDRESS
 THIS KIND OF INSTALLATION. WITH THE X VENT SYSTEM THE
 BOX OF THE X VENT IS MOUNTED INTO THE EXTERIOR OF THE
 WALL AND THE LOUVER IS FLUSH TO THE EXTERIOR WALL. THE
 EXHAUST OF THE DRYER MUST TRAVEL THROUGH THE EXHAUST
 DUCT, OPEN THE BACK-DRAFT DAMPER AND TRAVEL THROUGH THE
 X VENT COVER (LOUVER) BEFORE IT IS EXHAUSTED TO THE
 OUTDOORS. BECAUSE THIS PRODUCT USES BOTH THE BACK-DRAFT
 DAMPER AND THE OUTER COVER OF THE BOX (LOUVER) INSTEAD
 OF EITHER THE BACK-DRAFT DAMPER OR THE LOUVER AS
 TYPICALLY SEEN IN THE MANUFACTURES INSTALLATION MANUAL
 THE OUTER LOUVER IS A RESTRICTION THAT MUST BE
 ADDRESSED. IN LIEU OF THE MANUFACTURES LETTER STATING
 THE MAXIMUM DRYER EXHAUST DUCT TO BE USED WITH THE X
 VENT SYSTEM THE ENGINEER OF RECORD MUST DETERMINE THE
 AMOUNT OF RESTRICTION THIS CREATES AND THE EFFECT TO
 THE DRYER EXHAUST DUCT LENGTH. THE ENGINEER OF RECORD
 MUST SUBMIT THE CALCULATIONS AND PROVIDE MAX. EXHAUST
 DRYER DUCT LENGTHS FOR EACH DRYER USED IN THIS PROJECT.
 FBC M 504.8.4.2
  
 10) PLEASE PROVIDE THE SPECIFIC DRYER SPECIFICATIONS
 ALONG WITH THE DRYER DUCT LENGTHS. FBC M 504.6.4
  
 11) SHEET M.205B; WHAT IS THE WATER HEATER INTAKE AND
 EXHAUST PIPING MATERIAL? PLEASE PROVIDE THE
 SPECIFICATIONS FOR THE MENTIONED FIRE WRAP MATERIAL
 CALLED OUT ON THE DRAWING FOR THE SPECIFIC PIPING
 MATERIAL OF THE INTAKE AND EXHAUST PIPING. FBC 107.2.1
  
 12) SHEET M.701; I DO NOT SEE THE MENTIONED SD?S AT THE
 RETURN DUCT OF THE ERU-3 AND AHU-11 ON EACH LEVEL OF
 OFFICE TOWER. PLEASE CLOUD THE SD?S TO CLEARLY SHOW THE
 CHANGES. FBC 107.2.1
  
 13) SHEETS M.606-M.607; PLEASE IDENTIFY EACH VENT ZONE
 IN THE OUTDOOR AIR CALCULATIONS TO MATCH THE TABLES
 EITHER IN THE 2014 FBC M TABLE 403.3 OR ASHRAE 62.1
 TABLE 6.2.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  