| Date |
Text |
| 2021-02-18 12:49:05 | 1) SHT. P.509 - DETAIL #2 SHOWS A 1 INCH GAS LINE DOWN |
| | TO AN AHU. WHERE IS THIS AHU LOCATED? THE GAS LINE |
| | SHOWS A SHUTOFF VALVE ON THE GAS LINE. THE SHUTOFF |
| | VALVE SHALL BE LOCATED IN THE SAME ROOM AS THE |
| | APPLIANCE AND WITHIN 6 FEET OF THE APPLIANCE PER |
| | FBC-FUEL GAS SEC.409.5.1. CLARIFY. |
| | 2) SHT. P.700 - KEYNOTE #7 - PROVIDE A REFERENCE RISER |
| | TAG FOR THIS LINE OR PROVIDE A SHEET NUMBER AS TO WHERE |
| | THE CONTINUATION OF THIS LINE CAN BE FOUND AND PROVIDE |
| | A COMPLETE GAS RISER FOR THIS AREA SHOWING ALL PIPE |
| | SIZES, BTU LOADS OF APPLIANCES/EQUIPMENT, GAS PRESURE |
| | OF SYSTEM, VALVES, LONGEST RUN FROM POINT OF DELIVRY, |
| | ETC. WPB AMEND. TO FBC SEC. 107.2.1,107.3.5.1.5. |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GAS |
| | APPLIANCES/EQUIPMENT IN THE RESTAURANT. WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 4) SHT. P.700 - KEYNOTE #11 - SUBMIT A COMPLETE GAS |
| | RISER FOR THIS AREA EVEN THOUGH IT IS FOR FUTURE OR THE |
| | LOAD IS ESTIMATED. WPB AMEND. TO FBC SEC. 107.2.1, |
| | 107.3.5.1.5. |
| | 5) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE |
| | INSTALLED WITHIN 1 FOOT OF EITHER SIDE OF THE |
| | REGULATORS PER FBC-FUEL GAS SEC.410.2 (7). |
| | 6) THE INSTALLATION OF THE MP REGULATORS SHALL ALSO |
| | COMPLY WITH FBC-FUEL GAS SEC.410.2 ITEMS #1-#6. |
| | 7) SHT. P.700 - NATURAL GAS SYSTEMS TABLE - SYSTEM #1 |
| | SHOWS THE MAXIMUM BTU LOAD AS 4854 CFH BUT THE GAS |
| | RISER ON THE SAME PAGE SHOWS THE BTU LOAD AS 3229 CFH. |
| | CLARIFY. |
| | 8) SHT. P.700 - KEYNOTE #3 - IDENTIFY THIS FUTURE |
| | LINE/SYSTEM ON THE GAS RISER.WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 9) SHT. P.700 - NATURAL GAS SYSTEMS TABLE - GAS SYSTEM |
| | #5 - THE TABLE NOTES THE BTU LOAD AS 3,650 CFH BUT THE |
| | RISER SHOWS 3,500 CFH. CLARIFY.. |
| | 10) SHT. P.700 - KEYNOTE #11 - PROVIDE A REFERENCE |
| | RISER TAG FOR THIS LINE OR PROVIDE A SHEET NUMBER AS TO |
| | WHERE THE CONTINUATION OF THIS LINE CAN BE FOUND AND |
| | PROVIDE A COMPLETE GAS RISER FOR THIS AREA SHOWING ALL |
| | PIPE SIZES, BTU LOADS OF APPLIANCES/EQUIPMENT, GAS |
| | PRESURE OF SYSTEM, VALVES, LONGEST RUN FROM POINT OF |
| | DELIVERY, ETC. WPB AMEND. TO FBC SEC. 107.2.1, |
| | 107.3.5.1.5. |
| | 11) SHT. P.700 - KEYNOTE #14 SHOWS THE GAS LINE WITH |
| | 579 CFH AND SHT. P.700A, DETAIL #2 SHOWS 500 CFH. |
| | CLARIFY. |
| | 12) SHT. P.700 - THERE ARE RISER TAGS AT HE GAS RISER |
| | ON LEVELS 6,7, & 8 WITH NO DRAWING LOCATIONS/SHEET |
| | NUMBERS ON THE RISER TAGS. CLARIFY. |
| | 13) SHT. P.700A - DETAIL #6 SHOWS THE THE LONGEST RUN |
| | AS 550 FEET.THIS LINE IS UNDERSIZED AS DESIGNED. A |
| | MAXIMUM OF 556,000 BTU'S CAN BE ACCOMMODATED ON A 2 1/2 |
| | INCH LINE AT A DISTANCE OF 550 FEET IN ACCORDANCE WITH |
| | FBC-FUEL GAS TABLE 402.4(1). CLARIFY. |
| | 14) SHT. P.700A - DETAIL #5 - SIZE THE SHORT SECTION OF |
| | THE GAS MAIN LINE BETWEEN THE 4 INCH LINE AND THE 2 1/2 |
| | INCH LINE. SIZING SHALL COMPLY WITH FBC-FUEL GAS TABLE |
| | 402.4 (1). 2ND REQUEST. CLARIFY. |
| | 15) SHT. P.700A - DETAILS # 1- #6 - THERE IS A NOTE ON |
| | ALL THE DETAILS THAT REFER TO DETAIL #10 ON SHT.P.802 |
| | BUT THERE IS NO SUCH DETAIL ON THIS SHEET. 2ND |
| | REQUEST.CLARIFY. THE RESPONSE NARRATIVE STATES THE |
| | DETAIL IS ON SHT. P.804, DETAIL #10, BUT THAT DETAIL IS |
| | FOR A THERMOSTATIC MIXING VALVE AND IS NOT APPLICABLE. |
| | 16) SHT. P.700A - DETAILS #1 & #3 - NOTE #4 STATES TO |
| | REFER TO SHT. P.802, DETAIL #6 FOR THE WATER HEATER |
| | DETAIL. DETAIL #6 ON SHT.P.802 IS FOR A CONDENSATE |
| | DRAIN. 2ND REQUEST. CLARIFY. |
| | 17) SHT. P.700A - PLACE THE SPECIFIC SHEET NUMBER OF |
| | THE ORIGIN/CONTINUATION OF THE GAS SUPPLY LIINES TO THE |
| | APPLIANCES/EQUIPMENT ON EACH GAS RISER DETAIL. 2ND |
| | REQUEST. |
| | 18) SHT. P.804 - SUBMIT THE SPECIFICATIONS/INSTALLATION |
| | MANUAL FOR THE GAS DETECTION SYSTEM AND REFERENCE THE |
| | STANDARD ON WHICH THIS SYSTEM IS DESIGNED. 2ND |
| | REQUEST.WPB AMEEND. TO FBC SEC.107.2.1. |
| | 19) SHT. P.700 - THERE ARE FOUR RISER TAGS ON THIS PAGE |
| | IDENTIFIED AS G/H1, G/H2, G/H3 AND G/R1 WITH NO DRAWING |
| | LOCATION ON THESE RISER TAGS. CLARIFY. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |