Plan Review Notes
Plan Review Notes For Permit 18100540
Permit Number 18100540
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2020-03-12 10:09:50THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) SHEET A 1.108 - PLEASE REVIEW THE REQUIREMENT FOR AN
 ELEVATOR LOBBY AT THE FREIGHT ELEVATOR.
  
 PLEASE REVIEW AND CORRECT, IF APPLICABLE, WITH
 REVISIONS.
  
  
  
 2) STAIR PRESSURIZATION RATIONAL ANALYSIS REPORT -
  
 ON PAGE 13 OF THE STAIR PRESSURIZATION RATIONAL
 ANALYSIS REPORT DOCUMENT SECTION 11. CONCLUSION THERE
 IS AN INDICATION OF A DETAILED SEQUENCE OF OPERATION,
 WHICH DOES NOT APPEAR TO BE SUBMITTED.
  
 PLEASE AND PROVIDE AND CONTINUE TO WORK WITH THE OFFICE
 OF THE FIRE MARSHAL AND THE BUILDING DEPARTMENT'S
 MECHANICAL PLAN REVIEWERS AND INSPECTORS FOR APPROVAL.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  