| Plan Review Notes For Permit 18100540 |
| Permit Number |
18100540 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-03-12 10:09:50 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | | | | 1) SHEET A 1.108 - PLEASE REVIEW THE REQUIREMENT FOR AN | | | ELEVATOR LOBBY AT THE FREIGHT ELEVATOR. | | | | | | PLEASE REVIEW AND CORRECT, IF APPLICABLE, WITH | | | REVISIONS. | | | | | | | | | | | | 2) STAIR PRESSURIZATION RATIONAL ANALYSIS REPORT - | | | | | | ON PAGE 13 OF THE STAIR PRESSURIZATION RATIONAL | | | ANALYSIS REPORT DOCUMENT SECTION 11. CONCLUSION THERE | | | IS AN INDICATION OF A DETAILED SEQUENCE OF OPERATION, | | | WHICH DOES NOT APPEAR TO BE SUBMITTED. | | | | | | PLEASE AND PROVIDE AND CONTINUE TO WORK WITH THE OFFICE | | | OF THE FIRE MARSHAL AND THE BUILDING DEPARTMENT'S | | | MECHANICAL PLAN REVIEWERS AND INSPECTORS FOR APPROVAL. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|