Plan Review Notes
Plan Review Notes For Permit 18100540
Permit Number 18100540
Review Stop E
Sequence Number 3
Notes
Date Text
2021-02-03 07:39:15ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E.502A
 1) NO SIZES OF CONDUCTORS FROM THE PANELS TO THE
 TRANSFORMERS AND THEN AGAIN ON THE SECONDARY SIDE.
  
 2) GROUNDING SHOWN AT TRANSFORMERS PLEASE INDICATE WHAT
 THEY ARE TO TIE INTO FOR GROUNDING.
  
 3) FEEDERS TO THE FOLLOWING SHOW NOT SIZES AS WELL
 N2A1, SWB3, SWBC, SWBH4, SWBH1, SWBH3, KITCHEN PANEL,
 POOL PANEL, HOTEL POOL PANEL, GYM PANEL, AND N4H8B.
  
 PAGE E.502B
 1) NO SIZES OF CONDUCTORS FROM THE PANELS TO THE
 TRANSFORMERS AND THEN AGAIN ON THE SECONDARY SIDE.
  
 2) NO FEEDER SIZES TO CH, CWH
  
 PAGE E503
 1) GENERATOR 1 HAS 800A FEEDER WITH OVERCURRENT
 PROTECTION GOING TO FIRE PUMP, BUT IT HAS A 1600A
 FEEDER WITH NO OVER CURRENT PROTECTION AT THE GENERATOR
 WHAT SECTION ALLOWS THIS AND IF IT DOES THE CONDUCTORS
 WILL HAVE TO BE 115% PER 445.13
  
 2) PANEL DQ4H5 SHOWS NO OVERCURRENT PROTECTION SIZES
 AND APPEARS TO HAVE 3 SPARES?
  
 3) PANEL DE4H5 SAME AS ABOVE
  
 4) PANEL DQ4HRB NO WIRE SIZES FROM PANEL TO TRANSFORMER
 AND THEN AGAIN ON THE SECONDARY SIDE OF THE
 TRANSFORMER.
  
 PAGE E504
 1) WIRE SIZES FROM PANELS TO TRANSFORMER AND THEN AGAIN
 ON THE SECONDARY SIDE.
  
 2) SWBNRR NO SIZES ON OVERCURRENT PROTECTION 5 SPARES?
  
 3) DN4PR1 NO OVERCURRENT SIZES ON BREAKERS.
  
  
 PAGE E505
 1) PANELS DQ4RRA, DE4RR, AND DQ4RRB HAVE NO OVERCURRENT
 PROTECTION SHOWN ON BREAKERS AND IF THERE ARE SPARES.
  
 2) WIRE SIZES FROM PANELS TO TRANSFORMERS AND ON THE
 SECONDARY SIDE ARE NOT SHOWN.
  
 PLANS ARE GENERALY GOOD PLANS BUT THE RISER HAS YOU
 LOOKING IN SEVERAL PLACES TO COME UP WITH THE SIZES OF
 CONDUCTORS AND OVERCURRENT PROTECTION ON PRIMARIES AND
 SECONDARIES OF THE TRANSFORMERS. IT WOULD BE A BENEFIT
 TO HAVE THE WIRE SIZES AND OVERCURRENT PROTECTION ON
 THE RISER MAYBE WITH A TABLE SHOWING THE WIRES AND
 OCPS.
  
 SMOKE ALARMS IN RESIDENTIAL UNITS NEEDS TO BE LOOKED AT
 IN REFERENCE TO LOCATIONS OF THE SMOKE ALARMS OR
 DETECTORS. NFPA 72 GIVES LOCATIONS FOR SMOKE ALARMS
 NEAR BATHROOM DOORS AND COOKING APPLIANCES THAT SEEMED
 TO HAVE BEEN OVERLOOKED. SEE NFPA 72 SECTIONS
 29.8.3.4(4), AND (6) FOR COOKING APPLIABCES AND
 BATHROOM LOCATIONS.