| 2021-01-29 10:39:57 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 18100540 |
| | 550 N. QUADRILLE BLVD. |
| | BUILDING PERMIT 30 STORY BLDG W/ TWO TOWERS |
| | CONSTRUCTION TYPE: 1A, SPRINKLERED |
| | MIXED OCCUPANCY: B, R-1, R-2, A-2, A4, S-2, M, E |
| | |
| | 1 ST REVIEW: APRIL 18, 2019 - DYLAN BATTLES |
| | 2 ND REVIEW: MARCH 2, 2020 - DYLAN BATTLES |
| | 3 RD REVIEW: JANUARY 13, 2021 - ROBERT MCDOUGAL |
| | |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | FLORIDA BUILDING CODE,5TH EDITION (2014) |
| | FBC[AMENDED] = 2014 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| | BELOW) |
| | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| | BUILDING-PERMIT-FORMS |
| | FBC[B] = FBC BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | |
| | 1) NOT RESOLVED. THERE ARE STILL SOME ERRORS AND THE |
| | PAGE DID NOT LOAD PROPERLY. THE BOTTOM OF THE SHEET IS |
| | CUT OFF AND THERE IS A PARTIAL SHEET AT THE TOP. |
| | 107.5.3 FBC[AMENDED]PLEASE UPDATE SHEET A0.102 SITE |
| | DATA. THE DIAGRAM IN THE UPPER RIGHT CORNER DOESN'T |
| | REFLECT THE CHANGES IN ROOMS SHOWN IN THE PLANS. |
| | COMPARE SHEET A1.500 FOR SUITE AND UNIT COUNTS. |
| | |
| | A) NOT RESOLVED. THERE ARE SEVERAL PAGES OF THE SAME |
| | SHEETS. RATHER THAN BEING THE SAME SHEET VERSION-ED, |
| | THERE IS A PAGE WITH THE OLD PLAN SHEET AND A PAGE WITH |
| | THE REVISED PLAN SHEET. AS A GENERAL COMMENT, PLEASE |
| | LOOK IN PROJECTDOX AND NOTE IF SOME SHEETS MAY NOT HAVE |
| | BEEN REPLACED FOR SECOND REVIEW. EITHER UPLOAD REVISED |
| | SHEETS, LEAVE IT DIDN'T CHANGE OR REQUEST IT TO BE |
| | DELETED. |
| | |
| | B) NOT RESOLVED COMPLETELY. A PORTION OF THE WALL IS |
| | MISSING BETWEEN UNIT B-1 AND THE UNIT ABOVE IT THAT IS |
| | NOT LABELED. THE WOMENS BATHROOM AT THE PREFUNCTION |
| | AREA IS MISSING DETAILS. SEE MARKUPS ON SHEET A1.260. |
| | LEVEL 8 - SHEET A1.260. IS THE COLUMN LAYER TURNED OFF? |
| | ALSO, MISSING UNIT NUMBER ABOVE UNIT B1 08-22 |
| | THIS SHEET WAS NOT REVISED FROM FIRST REVIEW SO I THINK |
| | IT REFLECTS OLD LAYOUT. PLEASE UPLOAD NEW LEVEL 8 |
| | RESIDENTIAL SHEET. |
| | |
| | C) NOT RESOLVED. SEE SHEETS PAGES 03.071(A1.265) AND |
| | 03.072(A1.266) FOR REDUNDANT AND CONFLICTING |
| | INFORMATION. LEVEL 13-14 - 08 UNITS EACH FLOOR . SHEET |
| | A1.265 SAYS LEVEL 13-14, BUT THEN THE NEXT SHEET IS |
| | LEVEL 14. PLEASE ADJUST TITLE BLOCK TO STATE LEVEL 13 |
| | ONLY. |
| | |
| | D) NOT RESOLVED. PAGE 03.072(A1.266) IS STILL IN THE |
| | PLANS. LEVEL 14 - 08 UNITS. SHEET A1.266 IS THE COLUMN |
| | LAYER TURNED OFF? ALSO, MISSING UNIT NUMBERS. |
| | |
| | E) RESOLVED. LEVEL 3 - MISSING SUITE NUMBER NEXT TO |
| | SUITE 7.1 ON SHEET A1.103. LOOKS LIKE IT SHOULD BE |
| | SUITE 8. |
| | |
| | F) RESOLVED. LEVEL 9 - MISSING SUITE NUMBER NEXT |
| | BETWEEN SUITE 1.3B AND 1.3D ON SHEET A1.109 |
| | |
| | G) RESOLVED. LEVEL 16 - SUITE 2B ADA LOOKS LIKE WALL |
| | WAS LEFT BETWEEN ENTRY AND SLEEPING AREA. |
| | |
| | H) RESOLVED. LEVEL 17, I CAN'T FIND OFFICE LEVEL FLOOR |
| | PLAN. I DO SEE RCP AND LIFE SAFETY. PLEASE CHECK IF IT |
| | WAS LOADED INTO PROJECT DOX. |
| | |
| | 2) NOT RESOLVED. PAGE 03.052 (A1.240) WAS NOT UPDATED |
| | AND IS STILL IN THE PLANS. 107.5.3 FBC[AMENDED]SHEET |
| | 03.052 - A1.240 - HOTEL TOWER FLOOR PLAN - LEVEL 8 HAS |
| | NOT BEEN UPDATED. PLEASE UPLOAD A NEW VERSION, OR |
| | REQUEST IT BE DELETED FROM THE FOLDER. LEVEL EIGHT IS |
| | SHOWN ON PODIUM LEVEL 8 DRAWING 03.014 - A1.108 - |
| | PODIUM FLOOR PLAN AND IN QUADRANT PAGES AS WELL. |
| | |
| | 3) NOT RESOLVED. THERE ARE STILL SOME ISSUES WITH THE |
| | ADA REQUIREMENTS. THE GUEST ROOM MATRIX ON PAGE 03.082 |
| | (A1.500) HAS THE REQUIRED ADA ROOMS WITH MOBILITY |
| | FEATURES AS (5) ROOMS WITHOUT ROLL-IN SHOWERS, (2) |
| | ROOMS WITH ROLL-IN SHOWERS. THE 2010 ADA TABLE 224.2 |
| | REQUIRES (6) ROOMS WITHOUT ROLL-IN SHOWERS, (2) ROOMS |
| | WITH ROLL-IN SHOWERS FOR A TOTAL OF (8) ROOMS. THE ADA |
| | REQUIREMENTS FOR GUEST ROOMS WITH COMMUNICATION |
| | FEATURES IN TABLE 224.4 IS 14 ROOMS WHEN 200 GUEST |
| | ROOMS ARE PROVIDED. AT LEAST ONE GUEST ROOM REQUIRED TO |
| | PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL |
| | ALSO PROVIDE COMMUNICATION FEATURES COMPLYING WITH |
| | 806.3. NOT MORE THAN 10 PERCENT OF GUEST ROOMS REQUIRED |
| | TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL |
| | BE USED TO SATISFY THE MINIMUM NUMBER OF GUEST ROOMS |
| | REQUIRED TO PROVIDE COMMUNICATION FEATURES COMPLYING |
| | WITH 806.3. REVISE THE ROOM MATRIX TO CLEARLY SHOW |
| | COMPLIANCE OF SPECIFIC ROOMS. ALSO REVISE THE PLANS TO |
| | COMPLY. |
| | 107.5.3 FBC[AMENDED]PLEASE ADD COMMUNICATION SYMBOL TO |
| | SUITE 4.2B ON SHEET A1.243 ROOM SUMMARY SHEET STATES |
| | LEVEL 12-15 AS COMMUNICATION. PLEASE ADD SYMBOL TO |
| | THOSE ROOMS AS WELL. ADD BOTH SYMBOLS TO SUITE 2.B ON |
| | SHEET A1.246 |
| | PLEASE LOOK AT MOBILITY FEATURES DATA LAST LINE WHERE |
| | IT SAYS LEVEL 8-16 SUITE 4.2B. I DO SEE THAT THERE IS |
| | ADA ON LEVEL 16. ADD SYMBOLS AND CORRECT WHERE IT |
| | STATES 8-16 OR SHOW THAT LEVEL 8-15 SUITE 4.2B ARE ADA |
| | SUITES. |
| | |
| | 4) NOT RESOLVED. PROVIDE A ROOM MATRIX THAT SHOWS WHICH |
| | SPECIFIC HOTEL ROOMS WILL MEET THE ACCESSIBILITY |
| | REQUIREMENTS FOR MOBILITY AND COMMUNICATION FEATURES. |
| | SEE FBC ACCESSIBILITY SECTIONS 224 AND 806. NOT MORE |
| | THAN 10 PERCENT OF GUEST ROOMS REQUIRED TO PROVIDE |
| | MOBILITY FEATURES COMPLYING WITH 806.2 SHALL BE USED TO |
| | SATISFY THE MINIMUM NUMBER OF GUEST ROOMS REQUIRED TO |
| | PROVIDE COMMUNICATION FEATURES COMPLYING WITH 806.3. |
| | SPECIFY THE LOCATION AND ACCESSIBILITY TYPE OT HOTEL |
| | ROOMS WITH THE APPROPRIATE SYMBOLS ON THE PLANS. 224.5 |
| | FBC[A]DISPERSION. GUEST ROOMS REQUIRED TO PROVIDE |
| | MOBILITY FEATURES COMPLYING WITH 806.2 AND GUEST ROOMS |
| | REQUIRED TO PROVIDE COMMUNICATION FEATURES COMPLYING |
| | WITH 806.3 SHALL BE DISPERSED AMONG THE VARIOUS CLASSES |
| | OF GUEST ROOMS, AND SHALL PROVIDE CHOICES OF TYPES OF |
| | GUEST ROOMS, NUMBER OF BEDS, AND OTHER AMENITIES |
| | COMPARABLE TO THE CHOICES PROVIDED TO OTHER |
| | GUESTS.WHERE THE MINIMUM NUMBER OF GUEST ROOMS REQUIRED |
| | TO COMPLY WITH 806 IS NOT SUFFICIENT TO ALLOW FOR |
| | COMPLETE DISPERSION, GUEST ROOMS SHALL BE DISPERSED IN |
| | THE FOLLOWING PRIORITY: GUEST ROOM TYPE, NUMBER OF |
| | BEDS, AND AMENITIES. AT LEAST ONE GUEST ROOM REQUIRED |
| | TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL |
| | ALSO PROVIDE COMMUNICATION FEATURES COMPLYING WITH |
| | 806.3. NOT MORE THAN 10 PERCENT OF GUEST ROOMS REQUIRED |
| | TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL |
| | BE USED TO SATISFY THE MINIMUM NUMBER OF GUEST ROOMS |
| | REQUIRED TO PROVIDE COMMUNICATION FEATURES COMPLYING |
| | WITH 806.3. |
| | -ONLY 10 PERCENT OF REQUIRED ROOMS CAN SHARE |
| | COMMUNICATION AND MOBILITY. PLEASE SHOW COMMUNICATION |
| | ROOMS ONLY SHARE IN ONE SUITE. |
| | -PLEASE VERIFY THAT ROOMS ARE EVENLY DISTRIBUTED FOR |
| | ROOM TYPES AND PRICE RANGE. |
| | |
| | 5) NOT RESOLVED. PROVIDE A ROOM MATRIX TO SHOW WHICH |
| | SPECIFIC HOTEL ROOMS WILL MEET THIS REQUIREMENT. 806.4 |
| | FBC[A]HOTEL,MOTEL AND CONDOMINIUM SPECIAL ACCESSIBILITY |
| | FEATURES. THIS SECTION DOES NOT RELIEVE THE OWNER OF |
| | THE RESPONSIBILITY OF PROVIDING ACCESSIBLE ROOMS IN |
| | CONFORMANCE WITH SECTION 224 AND 806 OF THIS CODE. IN |
| | ALL BUILDINGS, STRUCTURES AND FACILITIES LICENSED AS A |
| | HOTEL, MOTEL OR RESORT CONDOMINIUM PURSUANT TO CHAPTER |
| | 509, F.S., A NUMBER OF ROOMS EQUALING AT LEAST 5 |
| | PERCENT OF THE GUEST ROOMS MINUS THE TOTAL NUMBER OF |
| | REQUIRED (ACCESSIBLE) ROOMS REQUIRED BY TABLE 224.2 |
| | SHALL PROVIDE THE FOLLOWING ADDITIONAL SPECIAL |
| | ACCESSIBILITY FEATURES: |
| | (I) GRAB RAILS IN BATHROOMS AND TOILET ROOMS WHICH |
| | COMPLY WITH SECTION 604.5. |
| | (II) ALL BEDS IN DESIGNED ACCESSIBLE GUEST ROOMS SHALL |
| | BE OPEN-FRAME TYPE THAT ALLOWS THE PASSAGE OF LIFT |
| | DEVICES. |
| | (III)WATER CLOSETS THAT COMPLY WITH SECTION 604.4. |
| | -SHOW WHICH ROOMS COMPLY WITH 806.4 |
| | |
| | 6) NOT RESOLVED. THERE ARE HOTEL ROOMS THAT APPEAR TO |
| | BE EQUIPPED WITH COOKING APPLIANCES. YOUR RESPONSE |
| | STATES THAT NOTE 26 ON SHEET A0.201 ADDRESSES THIS |
| | COMMENT. IT STATES THAT SERVICE APARTMENTS DESIGNED FOR |
| | STAYS OF MORE THAN 30 DAYS ARE REQUIRED TO COMPLY WITH |
| | FAIRHOUSING RATHER THAN ADA ACCESSIBILITY REQUIREMENTS. |
| | THIS IS NOT ACCURATE. BECAUSE THESE ARE HOTEL ROOMS |
| | THEY ARE NOT APARTMENTS AND ARE REQUIRED TO COMPLY WITH |
| | THE FLORIDA ACCESSIBILITY CODE AS WELL AS FAIRHOUSING |
| | GUIDELINES IF THEY ARE USED FOR STAYS OF MORE THAN 30 |
| | DAYS. YOU WILL NEED TO IDENTIFY THESE ROOMS AND SHOW |
| | THAT THEY MEET THE MOST RESTRICTIVE REQUIREMENTS OF THE |
| | TWO. 224.1 ADVISORY FBC[A]ARE THERE NON-TRANSIENT ROOMS |
| | (MORE THAN 30 DAY STAY)? |
| | IF SO, THOSE ROOMS MAY FALL UNDER THE FAIRHOUSING |
| | GUIDELINES IN ADDITION TO ACCESSIBILITY FBC 2017 6 TH |
| | EDITION. |
| | |
| | FAIRHOUSING REVIEW: |
| | 7) RESOLVED. 1986 ANSI [A117.1] IF A DESIGNER OR |
| | BUILDER CHOOSES TO FOLLOW AN ACCESSIBILITY STANDARD |
| | OTHER THAN THE 1986 ANSI A117.1 STANDARD, OR A MORE |
| | RECENT VERSION OF THE ANSI A117.1, SUCH AS THE 1992 |
| | CABO/ANSI, THAT CARE BE TAKEN TO ENSURE THE STANDARD |
| | USED IS AT LEAST EQUIVALENT TO OR STRICTER THAN THE |
| | 1986 ANSI A117.1 STANDARD. |
| | -WHAT STANDARD IS BEING APPLIED FOR COMPLIANCE WITH |
| | FAIR HOUSING? YOU CAN USE GUIDELINES THAT FALL WITHIN |
| | THE SAFE HARBOR FOR COMPLIANCE? |
| | |
| | A) PARTIALLY RESOLVED. PAGE 03.097(A1.519) THE MASTER |
| | BATH TOILET IN RESIDENTIAL UNIT S8 DOES NOT APPEAR TO |
| | COMPLY WITH A TYPE B BATHROOM. ON PAGE 03.102(A1.524) |
| | RESIDENTIAL UNIT B1 HAS ONE BATH ROOM MARKED AS TYPE A |
| | AND THE OTHER AS TYPE B. THE UNIT CAN ONLY BE ONE TYPE. |
| | ON PAGE 03.104(A1.526) SHOW THE REQUIRED CLEAR FLOOR |
| | SPACE AT THE TOILET IN UNIT B3.1. IT WOULD BE HELPFUL |
| | TO ADD A MATRIX OF ROOMS ON SHEET A1.500 WHICH BATHROOM |
| | SPEC IS BEING USED AND APPLY THE FOLLOWING FOR SPEC A |
| | AND B |
| | |
| | SPECIFICATION A: |
| | IF SPECIFICATION A IS USED IT APPLIES TO ALL BATHROOMS, |
| | AND ALL FIXTURES IN THOSE BATHROOMS MUST BE USABLE. |
| | SPECIFICATION B: |
| | IF SPECIFICATION B IS USED, IT APPLIES TO ONE BATHROOM, |
| | AND ONLY ONE OF EACH TYPE OF FIXTURE MUST BE USABLE; |
| | ADDITIONAL BATHROOMS IN THE UNIT ARE EXEMPT ONLY FROM |
| | MANEUVERING AND CLEAR FLOOR SPACE REQUIREMENTS AT |
| | FIXTURES. |
| | |
| | B) RESOLVED. PLEASE ADD TO FAIRHOUSING NOTES ON SHEET |
| | A1.528. THIS SAYS ALL BATHROOMS TO BE SPEC A. PLEASE |
| | ADJUST NOTE SINCE BOTH SPEC ARE BEING USED. |
| | |
| | C) RESOLVED. ADD NOTE FOR USABLE HARDWARE. |
| | REQUIREMENT 3 - USABLE DOORS. THE DOORS IN COMMON |
| | SPACES AND THE SIDE ENTERING INTO DWELLING UNITS NEED |
| | TO HAVE USABLE HARDWARE THAT CAN BE USED WITHOUT TIGHT |
| | GRASPING OR TWISTING. |
| | -TYPICALLY THE HARDWARE WOULD BE A LEVER TYPE. THIS |
| | TYPE OF HARDWARE WOULD NOT BE REQUIRED ONCE INSIDE THE |
| | UNIT. YOU MAY WANT TO CLARIFY HARDWARE ON THE DOOR |
| | SCHEDULE. |
| | |
| | D) NOT RESOLVED. DOOR SCHEDULES ON PAGES 03.242(A6.104) |
| | AND 03.243(A6.105) NEED TO BE CLEANED UP AND MADE |
| | LEGIBLE. DOOR SCHEDULE ON SHEET A6.104 IS DISTORTED AND |
| | INFORMATION IS NOT LEGIBLE. PLEASE ADJUST AND POPULATE |
| | AS NEEDED. |
| | |
| | E) RESOLVED. SHOW ACCESSIBLE ROUTES FOR EACH UNIT TYPE. |
| | |
| | F) RESOLVED. ADD DETAIL OF HOW ACCESS IS GAINED AT |
| | RESIDENTIAL BALCONY. IS THERE ELEVATION CHANGE TO MEET |
| | FAIRHOUSING MAX OF 4 INCHES TOP OF THRESHOLD? |
| | |
| | LIFE SAFETY: |
| | |
| | 8) PARTIALLY RESOLVED. SPECIFY THE REQUIRED FIRE |
| | RATINGS FOR THE EXIT STAIR DOORS AND THE FIRE SERVICE |
| | ACCESS LOBBY DOORS IN THE DOOR SCHEDULES. 3006.2 |
| | FBC[B]SHEET A1.107 SHOWS NO ELEVATOR LOBBY ON LEVEL 7 |
| | AT ELEVATORS 8, 9 AND 10. IF REQUIRED PLEASE SHOW THE |
| | DOORS. |
| | 1024.4 FBC[B]TERMINATION. EXIT PASSAGEWAYS ON THE LEVEL |
| | OF EXIT DISCHARGE SHALL TERMINATE AT AN EXIT DISCHARGE. |
| | EXIT PASSAGEWAYS |
| | ON OTHER LEVELS SHALL TERMINATE AT AN EXIT. |
| | EXIT DISCHARGE. THAT PORTION OF A MEANS OF EGRESS |
| | SYSTEM BETWEEN THE TERMINATION OF AN EXIT AND A PUBLIC |
| | WAY. |
| | |
| | 9) RESOLVED. 3005.5 FBC[B] SHUNT TRIP. WHERE ELEVATOR |
| | HOISTWAYS, ELEVATOR MACHINE ROOMS, CONTROL ROOMS AND |
| | CONTROL SPACES CONTAINING ELEVATOR CONTROL EQUIPMENT |
| | ARE PROTECTED WITH AUTOMATIC SPRINKLERS, A MEANS |
| | INSTALLED IN ACCORDANCE WITH SECTION 21.4 OF NFPA 72 |
| | SHALL BE PROVIDED TO DISCONNECT AUTOMATICALLY THE MAIN |
| | LINE POWER SUPPLY TO THE AFFECTED ELEVATOR PRIOR TO THE |
| | APPLICATION OF WATER. THIS MEANS SHALL NOT BE |
| | SELF-RESETTING. THE ACTIVATION OF AUTOMATIC SPRINKLERS |
| | OUTSIDE THE HOISTWAY, MACHINE ROOM, MACHINERY SPACE, |
| | CONTROL ROOM OR CONTROL SPACE SHALL NOT DISCONNECT THE |
| | MAIN LINE POWER SUPPLY. |
| | |
| | 10) RESOLVED. 3006.2 FBC[B] HOISTWAY OPENING PROTECTION |
| | REQUIRED. ELEVATOR HOISTWAY DOOR OPENINGS SHALL BE |
| | PROTECTED IN ACCORDANCE WITH SECTION 3006.3 WHERE AN |
| | ELEVATOR HOISTWAY CONNECTS MORE THAN THREE STORIES, IS |
| | REQUIRED TO BE ENCLOSED WITHIN A SHAFT ENCLOSURE IN |
| | ACCORDANCE WITH SECTION 712.1.1 AND ANY OF THE |
| | FOLLOWING CONDITIONS APPLY: |
| | 5. THE BUILDING IS A HIGH RISE AND THE ELEVATOR |
| | HOISTWAY IS MORE THAN 75 FEET (22 860 MM) IN HEIGHT. |
| | THE HEIGHT OF THE HOISTWAY SHALL BE MEASURED FROM THE |
| | LOWEST FLOOR TO THE HIGHEST FLOOR OF THE FLOORS SERVED |
| | BY THE HOISTWAY. |
| | -IS THE PRE FUNCTION AREA OPEN AIR? IT IS HARD TO TELL |
| | BUT IT APPREARS TO BE COVERED BY RESIDENTIAL ABOVE. |
| | -FREIGHT ELEVATOR DOES NOT HAVE ELEVATOR LOBBY ON THE 8 |
| | TH FLOOR. PLEASE REVIEW 3006.2 FOR OPENING PROTECTION |
| | ON SHAFT MORE THAN 75 FEET. |
| | |
| | 11) NOT RESOLVED. YOUR RESPONSE STATES THAT A LIFE |
| | SAFETY PLAN FOR THE PARK WAS ADDED ON SHEET ALS1.109. |
| | THERE IS NO SUCH SHEET IN THE PLANS OR THE PLAN INDEX. |
| | PLEASE CLARIFY. 107.5.3 FBC[AMENDED]ADD SCALE TO LIFE |
| | SAFETY PLANS. I THINK IT IS 1/16 SCALE. |
| | ALSO, IS THERE A LIFE SAFETY SHEET FOR THE PARK ABOVE |
| | THE TENNIS PAVILION? PLEASE PROVIDE OR LET ME KNOW |
| | WHICH SHEET I CAN FIND IT. |
| | |
| | 12) NOT RESOLVED. THERE ARE EXIT DOORS AT GRADE LEVEL |
| | THAT DO NOT HAVE EGRESS LOAD TAGS. 1004 FBC[B]PLEASE |
| | PROVIDE TOTAL OCCUPANT LOAD FOR EACH EGRESS DOOR AT |
| | GRADE WHERE THE DOOR PROVIDES EGRESS FROM MULTIPLE |
| | AREAS. FOR EXAMPLE EGRESS DOORS IN HOTEL LOBBY PICKUP |
| | THE STAIRS AND OTHER AREAS FROM FIRST LEVEL USES. I AM |
| | LOOKING FOR DATA TAG LIKE WAS USED AT STAIRWAY DOORS. |
| | |
| | 13) RESOLVED. 1025.1 FBC[B]GENERAL. APPROVED LUMINOUS |
| | EGRESS PATH MARKINGS DELINEATING THE EXIT PATH SHALL BE |
| | PROVIDED IN HIGH-RISE BUILDINGS OF GROUP A, B, E, I, M, |
| | AND R-1 OCCUPANCIES IN ACCORDANCE WITH SECTIONS 1025.1 |
| | THROUGH 1025.5. |
| | -ST4 AND ST3 FROM R-1 LEVELS TO MEET 1025.1 FOR |
| | LUMINOUS MARKINGS. |
| | |
| | 14) RESOLVED. 1013.2 FBC[B] FLOOR-LEVEL EXIT SIGNS IN |
| | GROUP R-1. WHERE EXIT SIGNS ARE REQUIRED IN GROUP R-1 |
| | OCCUPANCIES BY SECTION 1013.1, ADDITIONAL LOW-LEVEL |
| | EXIT SIGNS SHALL BE PROVIDED IN ALL AREAS SERVING GUEST |
| | ROOMS IN GROUP R-1 OCCUPANCIES AND SHALL COMPLY WITH |
| | SECTION 1013.5. |
| | -ADD LOW LEVEL EXIT SIGNS AS REQUIRED, OR STATE WHICH |
| | PAGE THIS INFORMATION CAN BE FOUND. |
| | |
| | 15) NOT RESOLVED. THE EXIT ACCESS TRAVEL DISTANCE FOR |
| | SPRINKLERED TYPE M OCCUPANCIES IS 250' IN 2014 FBC |
| | TABLE 1016.2 AND THE TABLE ON SHEET ALS1.101 HAS 400'. |
| | THE EGRESS TRAVEL DISTANCE FOR SPRINKLERED RESIDENTIAL |
| | OCCUPANCIES IS 250' IN FBC TABLE 1016.2 AND THE TABLE |
| | ON THE LIFE SAFETY PLANS SHEETS WITH RESIDENTIAL UNITS |
| | HAS 325'. YOU ARE REQUIRED TO MEET THE MOST RESTRICTIVE |
| | REQUIREMENT BETWEEN THE F.F.P.C. AND THE FBC BUILDING. |
| | SOME DESIGNERS LIST THE REQUIREMENTS OF BOTH CODES IN |
| | THEIR TABLES WITH A NOTE TO USE THE MOST RESTRICTIVE |
| | REQUIREMENT. PLEASE REVIEW ALL LIFE SAFETY PLANS FOR |
| | REQUESTED DATA. THE RESIDENTS LOUNGE AREA (0161) HAS AN |
| | OCCUPANT LOAD OF MORE THAN 49 AND REQUIRES TWO EXITS |
| | PER TABLE 1015.1. BE SURE TO SHOW EXIT ROUTES FOR ALL |
| | AREAS. 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA. |
| | THIS IS FOR ALL LIFE SAFETY SHEETS |
| | A. ADD MAX COMMON PATH AND MAX TRAVEL DISTANCE FOR R-1 |
| | AND R-2 TO ALS1.100 COMPLIANCE SUMMARY FOR FLORIDA |
| | BUILDING CODE IN ADDITION TO THE PROVIDED NFPA. THE |
| | MORE RESTRICTIVE CODE WILL APPLY. |
| | B. SHOW MAXIMUM PATH OF TRAVEL ON ALL L.S. PLANS. |
| | CURRENTLY, L.S. SHEETS SHOW PATH OF TRAVEL DISTANCE OR |
| | TOTAL DISTANCE. PLANS SHOULD SHOW BOTH COMMON PATH OF |
| | TRAVEL AND EXIT ACCESS TRAVEL DISTANCE. THIS SHOULD BE |
| | DONE FOR WORST CASE IN EACH GENERAL AREA. |
| | |
| | 16) NOT COMPLETELY RESOLVED. THERE ARE SEVERAL RAMPS |
| | SHOWN ON THE PLANS. PLEASE IDENTIFY EACH WITH AN ID TAG |
| | AND PROVIDE DETAILS FOR EACH OF THEM TO SHOW THAT THEY |
| | MEET THE ACCESSIBILITY REQUIREMENTS FOR RAMPS. FBC |
| | ACCESSIBILITY 405. 1003.5 FBC[B] ELEVATION CHANGE. DOES |
| | EXIT FROM RESIDENT LOBBY TO STAIR 2 HAVE STEPS? PLEASE |
| | REVIEW |
| | -HOW DO STEPS WORK AT EGRESS FROM RESIDENT LOUNGE TO |
| | STAIR ST2? PLEASE REVIEW 1003.5 FOR CHANGE IN ELEVATION |
| | IN PATH OF EGRESS. |
| | |
| | 17) RESOLVED. 1012.9 FBC[B] INTERMEDIATE HANDRAILS. |
| | STAIRWAYS SHALL HAVE INTERMEDIATE HANDRAILS LOCATED IN |
| | SUCH A MANNER THAT ALL PORTIONS OF THE STAIRWAY MINIMUM |
| | WIDTH OR REQUIRED CAPACITY ARE WITHIN 30 INCHES (762 |
| | MM) OF A HANDRAIL. ON MONUMENTAL STAIRS, HANDRAILS |
| | SHALL BE LOCATED ALONG THE MOST DIRECT PATH OF EGRESS |
| | TRAVEL. |
| | -CHECK COMPLIANCE WITH 1012.9 AT BALLROOM STEPS. |
| | |
| | 18) RESOLVED. 713.13.4 CHUTE DISCHARGE ROOM. WASTE OR |
| | LINEN CHUTES SHALL DISCHARGE INTO AN ENCLOSED ROOM |
| | SEPARATED BY FIRE BARRIERS WITH A FIRE RESISTANCE |
| | RATING NOT LESS THAN THE REQUIRED FIRE RATING OF THE |
| | SHAFT ENCLOSURE AND CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN |
| | ACCORDANCE WITH SECTION 711, OR BOTH. OPENINGS INTO THE |
| | DISCHARGE ROOM FROM THE REMAINDER OF THE BUILDING SHALL |
| | BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE |
| | PROTECTION RATING EQUAL TO THE PROTECTION REQUIRED FOR |
| | THE SHAFT ENCLOSURE. DOORS SHALL BE SELF- OR |
| | AUTOMATICCLOSING UPON THE DETECTION OF SMOKE IN |
| | ACCORDANCE WITH SECTION 716.5.9.3. WASTE CHUTES SHALL |
| | NOT TERMINATE IN AN INCINERATOR ROOM. WASTE AND LINEN |
| | ROOMS THAT ARE NOT PROVIDED WITH CHUTES NEED ONLY |
| | COMPLY WITH TABLE 509. |
| | -DOUBLE DOORS TO TRASH ROOM AT BASE LEVEL SHOW 90 |
| | MINUTE RATING, BUT 713.13.4 REQUIRES SAME LEVEL OF |
| | PROTECTION FOR OPENINGS IN DISCHARGE ROOM EQUAL TO THE |
| | SHAFT ENCLOSURE (2 HOURS). |
| | |
| | 19) RESOLVED. 420.3 FBC[B]HORIZONTAL SEPARATION AND |
| | FBC[B] 602 FLOOR ASSEMBLIES SEPARATING DWELLING UNITS |
| | IN THE SAME BUILDINGS, FLOOR ASSEMBLIES SEPARATING |
| | SLEEPING UNITS IN THE SAME BUILDING AND FLOOR |
| | ASSEMBLIES SEPARATING DWELLING OR SLEEPING UNITS FROM |
| | OTHER OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME |
| | BUILDING SHALL BE CONSTRUCTED AS HORIZONTAL ASSEMBLIES |
| | IN ACCORDANCE WITH SECTION 711. |
| | -602 FBC[B]SHEET A7.310 HAS CEILING ASSEMBLIES. PLEASE |
| | SHOW THE RATED ASSEMBLY FOR CEILINGS SEPARATING |
| | DWELLING AND SLEEPING UNITS AS STATED IN LIFE SAFETY |
| | COMPLIANCE SUMMARY ALS1.100. |
| | |
| | 20) NOT RESOLVED. THE TAG ON THE WASTE CHUTE ACCESS |
| | DOORS FROM THE CORRIDORS STILL HAVE NR INSTEAD OF 45 |
| | MIN. ON THE LIFE SAFETY PLANS.713.13.3 FBC[B]CHUTE |
| | ACCESS ROOMS. ACCESS OPENINGS FOR WASTE OR LINEN CHUTES |
| | SHALL BE LOCATED IN ROOMS OR COMPARTMENTS ENCLOSED BY |
| | NOT LESS THAN 1-HOUR FIRE BARRIERS CONSTRUCTED IN |
| | ACCORDANCE WITH SECTION 707 OR HORIZONTAL ASSEMBLIES |
| | CONSTRUCTED IN ACCORDANCE WITH SECTION 711, OR BOTH. |
| | OPENINGS INTO THE ACCESS ROOMS SHALL BE PROTECTED BY |
| | OPENING PROTECTIVES HAVING A FIRE PROTECTION RATING OF |
| | NOT LESS THAN 3/4 HOUR. DOORS SHALL BE SELF- OR |
| | AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE IN |
| | ACCORDANCE WITH SECTION 716.5.9.3. |
| | -LIFE SAFETY SHEETS SHOW CHUTE ACCESS DOORS AS NOT |
| | RATED (NR). THESE ACCESS DOORS ARE REQUIRED TO HAVE A |
| | 3/4 HOUR RATING PER 713.13.3. |
| | - ADD DOOR TAG TO THE DOORS LEADING TO THE TRASH CHUTE |
| | OR TELL ME WHAT SHEETS THER ARE ON. I WAS LOOKING ON |
| | QUADRANT SHEETS WHERE THE OTHER TAGS FOR COMMON SPACE |
| | DOORS WERE LOCATED. |
| | |
| | DEFERRED SUBMITTALS |
| | 21) NOT COMPLETELY RESOLVED. PLEASE LABEL GENERAL NOTE |
| | 16 ON SHEET A0.001 AS "DEFERRED SUBMITTALS" AND NOTE |
| | THAT THE ITEMS BEING DEFERRED ARE REQUIRED TO BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORDED AND SUBMITTED AND APPROVED BY THE CITY OF WEST |
| | PALM BEACH BUILDING DEPARTMENT PRIOR TO BEING |
| | INSTALLED. ANY ITEMS NOT LISTED WILL HAVE TO BE |
| | APPROVED BEFORE THE PERMIT CAN BE ISSUED. 107.3.4.1 |
| | FBC[AMENDED] PLEASE PROVIDE A LIST OF DEFERRED |
| | SUBMITTALS ON PLANS SO THAT I WILL NOT ASK FOR ITEMS |
| | THAT WILL BE SUPPLIED AT A LATER DATE, OR INDICATE |
| | WHICH PAGE A LIST CAN BE FOUND. |
| | THESE ARE THE ONES I BELIEVE WE WILL NEED, BUT THIS IS |
| | NOT A COMPLETE LIST. |
| | A) COMPONENT & CLADDING PRODUCT APPROVALS (COMPLY WITH |
| | PRESSURES SHOWN ON SHEET S0.0.5) |
| | B) CURTAIN WALL SUBMITTAL (COMPLY WITH PRESSURES SHOWN |
| | ON SHEET S0.0.5) |
| | C) FENESTRATION SHOP DRAWINGS TO INCLUDE ALL WINDOWS, |
| | DOORS, TRANSOMS, SLIDERS, LOUVERS AND MULL BARS. |
| | D) FLOORING UNDERLAYMENT WITH THREE REPORTS: |
| | 1. 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND |
| | FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND |
| | SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF |
| | NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED, |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E90. |
| | 2. 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING |
| | ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR |
| | BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR |
| | NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E492. |
| | 3. 603.1 FBC[B] ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | E) RAILINGS AND GUARDRAILS. INCLUDES BALCONIES, STAIRS |
| | AND COMMON SPACES. |
| | F) PARKING GARAGE VEHICLE BARRIER PER 406.4.2 FBC[B] |
| | G) FIRE SPRAY |
| | H) 806.1 FBC[B] GENERAL REQUIREMENTS. CURTAINS, |
| | DRAPERIES, HANGINGS AND OTHER DECORATIVE MATERIALS |
| | SUSPENDED FROM WALLS OR CEILINGS SHALL MEET THE FLAME |
| | PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 IN |
| | ACCORDANCE WITH SECTION 806.2 OR BE NONCOMBUSTIBLE. |
| | I) LIGHTWIEGHT CONCRETE. |
| | J) WINDOW WASHING EQUIPMENT ATTACHMENTS/LOCATIONS AT |
| | ROOF. |
| | K) E.F.I.S. IF APPLICABLE |
| | L) LIGHTING CONTROLS PER ENERGY CODE C405.2 LIGHTING |
| | CONTROLS (MANDATORY) C405.5 EXTERIOR LIGHTING |
| | (MANDATORY) |
| | M) FINAL GYM EQUIPMENT LAYOUT WITH ACCESSIBILTY |
| | REQUIREMENTS PROVIDED. |
| | PRODUCT APPROVALS FOR ROOFING ARE PROVIDED, BUT NO |
| | SELECTIONS ARE MADE AND IT IS NOT CLEAR WHICH AREA OF |
| | ROOF RECEIVE. |
| | ROOFING CAN BE ADDED TO DEFERRED SUBMITTAL LIST. |
| | |
| | 22) NOT RESOLVED. THE PRODUCT APPROVALS THAT WERE |
| | SUBMITTED ARE REQUIRED TO BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD. IF YOU ARE NOT SURE |
| | WHICH PRODUCTS WILL BE USED, YOU CAN SPECIFY ON THE |
| | PLANS THAT THEY WILL BE SUBMITTED LATER. ALSO, PROVIDE |
| | PRODUCT APPROVAL FOR ROOF INSULATION AND ATTACHMENT. |
| | OTHER PRODUCT APPROVALS WERE SUBMITTED FOR DOORS, BUT |
| | THEY WERE NOT STAMPED AS REVIEWED. AS PART OF |
| | FENESTRATION PACKAGE PROVIDE ALL PRODUCT APPROVALS WITH |
| | INDICATION THAT THEY WERE REVIEWED BY THE DESIGNER OF |
| | RECORD. |
| | |
| | 23) RESOLVED. ENERGY CODE REVIEW: |
| | A) THIS BUILDING WAS BROUGHT IN UNDER 2014 CODE CYCLE. |
| | PLEASE REVISE TO THAT CODE DATE, OR PROVIDE LETTER OF |
| | COMPLIANCE THAT CURRENT CODES ARE EQUIVALENT. |
| | B) C407.2.1 ROOF/CEILING THERMAL ENVELOPE. SECTIONS FOR |
| | ROOFING AND DOORS SHOW NO DATA. PLEASE INCLUDE THOSE |
| | VALUES IN THE ENERGY CALCULATIONS. |
| | C) IN SECTION FOR WALLS THE ASSEMBLY STATES 6 INCH |
| | INSULATION. WHERE IS THAT ASSEMBLY BEING USED ON THE |
| | BUILDING? |
| | |
| | ACCESSIBILITY REVIEW: |
| | |
| | 24) PROVIDE DETAILS TO SHOW THAT THE BUILT IN LOCKER |
| | ROOM BENCHES ARE ADA COMPLIANT. 803.1 FBC[A] GENERAL. |
| | DRESSING, FITTING, AND LOCKER ROOMS SHALL COMPLY WITH |
| | 803. |
| | 803.2 FBC[A] TURNING SPACE. TURNING SPACE COMPLYING |
| | WITH 304 SHALL BE PROVIDED WITHIN THE ROOM. |
| | 803.3 FBC[A] DOOR SWING. DOORS SHALL NOT SWING INTO THE |
| | ROOM UNLESS A CLEAR FLOOR OR GROUND SPACE COMPLYING |
| | WITH 305.3 IS PROVIDED BEYOND THE ARC OF THE DOOR |
| | SWING. |
| | 803.4 FBC[A] BENCHES. A BENCH COMPLYING WITH 903 SHALL |
| | BE PROVIDED WITHIN THE ROOM. |
| | 903.4 FBC[A] BACK SUPPORT. THE BENCH SHALL PROVIDE FOR |
| | BACK SUPPORT OR SHALL BE AFFIXED TO A WALL. BACK |
| | SUPPORT SHALL BE 42 INCHES LONG MINIMUM AND SHALL |
| | EXTEND FROM A POINT 2 INCHES MAXIMUM ABOVE THE SEAT |
| | SURFACE TO A POINT 18 INCHES MINIMUM ABOVE THE SEAT |
| | SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES MAXIMUM FROM |
| | THE REAR EDGE OF THE SEAT MEASURED HORIZONTALLY. |
| | |
| | 25) NOT COMPLETELY RESOLVED. THE ADA INFORMATION, CLEAR |
| | FLOOR SPACE WAS NOT PROVIDED FOR THE EXERCISE EQUIPMENT |
| | IN THE MENS GYM. 236.1 FBC[A]GENERAL. AT LEAST ONE OF |
| | EACH TYPE OF EXERCISE MACHINE AND EQUIPMENT SHALL |
| | COMPLY WITH 1004. |
| | 1004.1 FBC[A]CLEAR FLOOR SPACE. EXERCISE MACHINES AND |
| | EQUIPMENT SHALL HAVE A CLEAR FLOOR SPACE COMPLYING WITH |
| | 305 POSITIONED FOR TRANSFER OR FOR USE BY AN INDIVIDUAL |
| | SEATED IN A WHEELCHAIR. CLEAR FLOOR OR GROUND SPACES |
| | REQUIRED AT EXERCISE MACHINES AND EQUIPMENT SHALL BE |
| | PERMITTED TO OVERLAP. |
| | |
| | ADVISORY 1004.1 FBC[A]CLEAR FLOOR SPACE. ONE CLEAR |
| | FLOOR OR GROUND SPACE IS PERMITTED TO BE SHARED BETWEEN |
| | TWO PIECES OF EXERCISE EQUIPMENT.TO OPTIMIZE SPACE USE, |
| | DESIGNERS SHOULD CAREFULLY CONSIDER LAYOUT OPTIONS SUCH |
| | AS CONNECTING ENDS OF THE ROW AND CENTER AISLE SPACES. |
| | THE POSITION OF THE CLEAR FLOOR SPACE MAY VARY GREATLY |
| | DEPENDING ON THE USE OF THE EQUIPMENT OR MACHINE. FOR |
| | EXAMPLE, TO PROVIDE ACCESS TO A SHOULDER PRESS MACHINE, |
| | CLEAR FLOOR SPACE NEXT TO THE SEAT WOULD BE APPROPRIATE |
| | TO ALLOW FOR TRANSFER. CLEAR FLOOR SPACE FOR A BENCH |
| | PRESS MACHINE DESIGNED FOR USE BY AN INDIVIDUAL SEATED |
| | IN A WHEELCHAIR, HOWEVER, WILL MOST LIKELY BE CENTERED |
| | ON THE OPERATING MECHANISMS. |
| | |
| | 26) NOT RESOLVED. THE NOTES ON THE POOLS STATE TO REFER |
| | TO SHEETS SP.001, SP.002 AND SP.003. I WAS NOT ABLE TO |
| | FIND THESE SHEETS. SHOW HOW THE POOLS WILL COMPLY WITH |
| | FBC ACCESSIBILITY SECTION 242.2 SWIMMING POOLS. AT |
| | LEAST TWO ACCESSIBLE MEANS OF ENTRY SHALL BE PROVIDED |
| | FOR SWIMMING POOLS. (SEE EXCEPTIONS) ACCESSIBLE MEANS |
| | OF ENTRY SHALL BE SWIMMING POOL LIFTS COMPLYING WITH |
| | 1009.2; SLOPED ENTRIES COMPLYING WITH 1009.3; TRANSFER |
| | WALLS COMPLYING WITH 1009.4; TRANSFER SYSTEMS COMPLYING |
| | WITH 1009.5; AND POOL STAIRS COMPLYING WITH 1009.6. AT |
| | LEAST ONE ACCESSIBLE MEANS OF ENTRY PROVIDED SHALL |
| | COMPLY WITH 1009.2 OR 1009.3. ADVISORY 242.2 SWIMMING |
| | POOLS. WHERE MORE THAN ONE MEANS OF ACCESS IS PROVIDED |
| | INTO THE WATER, IT IS RECOMMENDED THAT THE MEANS BE |
| | DIFFERENT. PROVIDING DIFFERENT MEANS OF ACCESS WILL |
| | BETTER SERVE THE VARYING NEEDS OF PEOPLE WITH |
| | DISABILITIES IN GETTING INTO AND OUT OF A SWIMMING |
| | POOL. IT IS ALSO RECOMMENDED THAT WHERE TWO OR MORE |
| | MEANS OF ACCESS ARE PROVIDED, THEY NOT BE PROVIDED IN |
| | THE SAME LOCATION IN THE POOL. DIFFERENT LOCATIONS WILL |
| | PROVIDE INCREASED OPTIONS FOR ENTRY AND EXIT, |
| | ESPECIALLY IN LARGER POOLS. ADVISORY 242.2 SWIMMING |
| | POOLS EXCEPTION 1. POOL WALLS AT DIVING AREAS AND AREAS |
| | ALONG POOL WALLS WHERE THERE IS NO POOL ENTRY BECAUSE |
| | OF LANDSCAPING OR ADJACENT STRUCTURES ARE TO BE COUNTED |
| | WHEN DETERMINING THE NUMBER OF ACCESSIBLE MEANS OF |
| | ENTRY REQUIRED. |
| | COMMUNITY POOLS THAT ARE ASSOCIATED WITH A PRIVATE |
| | RESIDENTIAL COMMUNITY THAT DO NOT RECEIVE GOVERNMENTAL |
| | FINANCIAL ASSISTANCE OR SPONSORSHIP AND ARE LIMITED TO |
| | THE EXCLUSIVE OF RESIDENTS AND THEIR GUESTS ARE NOT |
| | COVERED BY THE ADA ACCESSIBILITY REQUIREMENTS, |
| | INCLUDING PROVISIONS FOR POOL LIFTS OR SLOPED ENTRIES. |
| | IF A SWIMMING POOL LOCATED IN A RESIDENTIAL COMMUNITY |
| | IS MADE AVAILABLE TO THE PUBLIC FOR RENTAL OR USE IT IS |
| | REQUIRED TO COMPLY WITH TITLE II OF THE ADA. SPECIFY ON |
| | THE PLANS THE FORMER OR SHOW COMPLIANCE WITH THE LATTER |
| | STATEMENTS. SEE DECLARATORY STATEMENT, DS 2013-011. |
| | |
| | 1009.1 GENERAL. WHERE PROVIDED, POOL LIFTS, SLOPED |
| | ENTRIES, TRANSFER WALLS, TRANSFER SYSTEMS, AND POOL |
| | STAIRS SHALL COMPLY WITH 1009. |
| | -IF POOL LIFTS ARE PROVIDED PLEASE ADD DETAILS TO THE |
| | ADA DETAIL SHEET. |
| | ALSO, ADD ANY ADDITIONAL DETAILS IF APPLICABLE TO ADA |
| | DETAILS FOR THE POOLS. |
| | |
| | 27) NOT RESOLVED. PROVIDE DETAILS OF ALL RAMPS TO SHOW |
| | COMPLIANCE WITH ACCESSIBILITY REQUIREMENTS. THE MAXIMUM |
| | RAMP SLOPE IS 1:12 (8%). FBC ACCESSIBILITY SECTION 405. |
| | 405.8 FBC[A]HANDRAILS.RAMP RUNS WITH A RISE GREATER |
| | THAN 6 INCHES (150 MM) SHALL HAVE HANDRAILS COMPLYING |
| | WITH 505. |
| | -SHEET ALS1.107 SHOWS RAMP FROM PRE-FUNCTION UP TO |
| | ELEVATORS AND STAIR ST8. WILL THERE BE RAILS PROVIDE |
| | THE RAMP AS REQUIRED? ALSO, IS THE WALKWAY FROM RAMP TO |
| | STAIR 8 GOING TO HAVE RAIL OR IS IT OPEN FROM ABOVE TO |
| | PRE-FUNCTION? |
| | |
| | CHAPTER 4 - HIGHRISE: |
| | |
| | 28) RESOLVED. 403.5.3.1 FBC[B]STAIRWAY COMMUNICATION |
| | SYSTEM. A TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS |
| | SYSTEM CONNECTED TO AN APPROVED CONSTANTLY ATTENDED |
| | STATION SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH |
| | FLOOR IN EACH STAIRWAY WHERE THE DOORS TO THE STAIRWAY |
| | ARE LOCKED. |
| | -WILL THE DOORS BE LOCKED FROM THE STAIRWAY SIDE? IF SO |
| | PLEASE ADD COMMUNICATION SYSTEM AS REQUIRED IN |
| | 403.5.3.1 |
| | |
| | 29) NOT RESOLVED. THERE ARE SEVERAL EXIT STAIRWAYS THAT |
| | ARE NOT CONTINUOUS FROM THE UPPER FLOORS TO THE LEVEL |
| | OF EXIT DISCHARGE AT THE GROUND FLOOR. THE PLANS SHOW |
| | THAT THE STAIRWAYS TRANSFER THROUGH A FIRE RATED |
| | "TRANSFER" CORRIDOR (EXIT PASSAGEWAY) TO ANOTHER |
| | STAIRWAY IN ORDER TO TRAVEL TO THE EXIT DISCHARGE. |
| | THERE ARE OPENINGS INTO THE CORRIDOR (EXIT PASSAGEWAY) |
| | TO AN AHU ROOM AND TWO MAINTENANCE/ACCESS ROOMS. PLEASE |
| | KEEP IN MIND THAT ONCE AN OCCUPANT ENTERS AN EXIT |
| | STAIRWAY THE EXPECTATION IS THAT THE OCCUPANT WILL HAVE |
| | THE SAME PROTECTION AS PROVIDED BY THE EXIT STAIRWAY |
| | UNTIL THEY REACH THE EXIT DISCHARGE. THE SAME |
| | REQUIREMENTS FOR THE STAIRWAY WILL APPLY TO THE |
| | TRANSFER CORRIDOR. NO OPENINGS, PENETRATIONS OR SYSTEMS |
| | OTHER THAN THOSE REQUIRED AS A PART OF THE EMERGENCY |
| | EGRESS SYSTEM AND THOSE THAT SERVICE THE STAIRWAY ARE |
| | ALLOWED. THERE IS ALSO A CONCERN THAT A DOUBLE DOOR |
| | THAT OPENS DIRECTLY TO THE PARKING GARAGE. PLEASE |
| | PROVIDE A NARRATIVE THAT EXPLAINS THE RATIONALE AND |
| | INTENTIONS FOR THE EXIT STAIRS THAT HAVE THIS DESIGN. |
| | FBC 1009 THE1022.8 FBC[B] DISCHARGE IDENTIFICATION. AN |
| | INTERIOR EXIT STAIRWAY AND RAMP SHALL NOT CONTINUE |
| | BELOW ITS LEVEL OF EXIT DISCHARGE UNLESS AN APPROVED |
| | BARRIER IS PROVIDED AT THE LEVEL OF EXIT DISCHARGE TO |
| | PREVENT PERSONS FROM UNINTENTIONALLY CONTINUING INTO |
| | LEVELS BELOW. DIRECTIONAL EXIT SIGNS SHALL BE PROVIDED |
| | AS SPECIFIED IN SECTION 1011. |
| | -IF STAIRWAY 4 AT 2 ND LEVEL TRANSFERS TO STAIRWAY 11 |
| | THAN 1022.8 APPLIES. |
| | |
| | 30) NOT RESOLVED. ADD NOTES TO PAGE 10.001 SHEET FR.001 |
| | THAT SPECIFY THAT A MINIMUM OF TWO RISERS WILL BE |
| | PROVIDED AND THAT EACH RISER SHALL SUPPLY SPRINKLERS ON |
| | ALTERNATE FLOORS. 403.3.1 FBC[B]NUMBER OF SPRINKLER |
| | RISERS AND SYSTEM DESIGN. EACH SPRINKLER SYSTEM ZONE IN |
| | BUILDINGS THAT ARE MORE THAN 420 FEET (128 000 MM) IN |
| | BUILDING HEIGHT SHALL BE SUPPLIED BY NO FEWER THAN TWO |
| | RISERS. EACH RISER SHALL SUPPLY SPRINKLERS ON ALTERNATE |
| | FLOORS. IF MORE THAN TWO RISERS ARE PROVIDED FOR A |
| | ZONE, SPRINKLERS ON ADJACENT FLOORS SHALL NOT BE |
| | SUPPLIED FROM THE SAME RISER. |
| | -PLEASE SEE HOW THIS APPLIES TO OFFICE TOWER ONLY AND |
| | UPDATE FS DRAWINGS AS APPLICABLE. |
| | |
| | NEW COMMENTS: |
| | |
| | 31) THERE ARE SOME SHEETS THAT ARE DUPLICATED AND THEY |
| | ARE NOT LISTED AS PREVIOUS VERSIONS OF THE SHEET. I AM |
| | NOT SURE WHY THIS HAPPENED. PERHAPS THEY WERE NAMED |
| | DIFFERENTLY WHEN RESUBMITTING. PLEASE REMOVE THE |
| | DUPLICATED SHEETS THAT ARE NOT VERSION-ED. CONTACT THE |
| | PERMIT LIBRARIAN IF YOU REQUIRE ASSISTANCE. FBC |
| | AMENDMENTS 107 |
| | |
| | 32) SHOW COMPLIANCE WITH FBC 403.4.5 EMERGENCY |
| | RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN |
| | ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE. THIS |
| | TYPICALLY REQUIRES A BI-DIRECTIONAL ANTENNA (BDA |
| | SYSTEM) OR SOME OTHER APPROVED METHOD. |
| | |
| | 33) NOTE #4 ON SHEET ALS1.100 IS APPARENTLY FOR ANOTHER |
| | PROJECT. IT SPECIFIES OCEAN DRIVE AND HEATHER DRIVE AS |
| | EMERGENCY STAGING AREAS. PLEASE CORRECT. FBC AMENDMENTS |
| | 107.2.1 |
| | |
| | 34) ON PAGE 04.016 - ALS1.116, THE RESIDENTIAL ELEVATOR |
| | MACHINE ROOM LIFE SAFETY PLAN IS NOT CLEAR. IT APPEARS |
| | THAT THE PATH OF TRAVEL IS GOING THROUGH WALLS. PLEASE |
| | CLARIFY. FBC AMENDMENTS 107.2.1 |
| | |
| | 35) ON PAGE 04.024 -ALS1.109, SHOW THE TOTAL OCCUPANT |
| | LOAD OF THE TERRACE AND PICKLE BALL COURTS, THE LOADS |
| | AT EACH EXIT DOOR AND THE COMBINED LOADS AT THE HOTEL |
| | AND RESIDENT EXIT STAIRWAYS. FBC 1004 |
| | |
| | 36) ON SHEET A7.700 THERE APPEARS TO BE A WALL SHOWN IN |
| | THE CENTER OF THE SCREEN ROOM THAT IS RUNNING THROUGH |
| | SOME OF THE SEATING. PLEASE CLARIFY. FBC 107.2.1 |
| | |
| | 37) ON SHEET A0.001, GENERAL NOTES 6-10 ARE MISSING. |
| | PLEASE CLARIFY. FBC AMENDMENTS 107.2.1 |
| | |
| | 38) ALSO ON SHEET A0.001, GENERAL NOTE 15 SHOULD |
| | REFERENCE ASCE 7-10, RATHER THAN ASCE 7-88. FBC CHAPTER |
| | 35. |
| | |
| | 39) FBC ACCESSIBILITY 505.10.3 REQUIRES THE HANDRAIL |
| | EXTENSIONS AT THE BOTTOM OF STAIRS TO EXTEND AT THE |
| | SLOPE OF THE STAIRFLIGHT FOR THE LENGTH OF A STAIR |
| | TREAD BEFORE RETURNING TO THE WALL, FLOOR OR POST. |
| | |
| | 40) THE STAIR DETAIL DRAWINGS THAT START ON PG |
| | 03.208-A5.101 APPEAR TO HAVE SOME ISSUES. PLEASE REVIEW |
| | THE MINIMUM 44" STAIRWAY WIDTH REQUIRED BY FBC 1009.4. |
| | THE 3'-8" RADIUS AT THE STAIR LANDINGS IN SOME OF THE |
| | DETAILS ARE INCORRECT. |
| | |
| | 41) ON PAGE 04.002 - ALS1.101, EXIT PASSAGEWAY 0158 IS |
| | SHOWN WITH A ONE HOUR FIRE RATED WALL AND A 45 MINUTE |
| | FIRE RATED DOOR. FBC 1023 REQUIRES EXIT PASSAGEWAY |
| | ENCLOSURES TO HAVE WALLS, FLOORS AND CEILINGS OF NOT |
| | LESS THAN THAT REQUIRED FOR ANY CONNECTING INTERIOR |
| | EXIT STAIRWAY OR RAMP. SINCE THE CONNECTING STAIRWAY |
| | HAS A TWO HOUR FIRE RATING, THIS PASSAGEWAY IS ALSO |
| | REQUIRED TO HAVE A TWO HOUR FIRE RATING AND A 90 MINUTE |
| | FIRE RATED DOOR. |
| | |
| | 42) THE BUILDING OFFICIAL HAS DETERMINED THAT WHEN CAR |
| | CHARGING STATIONS ARE PROVIDED, AT LEAST ONE ACCESSIBLE |
| | EV CHARGING STATION IS TO BE PROVIDED FOR EVERY 25 |
| | TOTAL EV CHARGING STATIONS. THE ACCESSIBLE EV CHARGING |
| | STATIONS CAN BE LOCATED WITH THE OTHERS. |
| | |
| | 43) I DID NOT SEE THE DETAILS/ELEVATIONS OF BUILT-IN |
| | ITEMS IN THE COMMON USE AREAS, SUCH AS RECEPTION DESKS, |
| | SERVICE COUNTERS, BREAK ROOM KITCHENS, ETC. THAT ARE |
| | REQUIRED TO BE ACCESSIBLE PER FBC ACCESSIBILITY |
| | CHAPTERS 8 AND 9. PLEASE INDICATE SHEETS THEY ARE ON OR |
| | PROVIDE SHEETS WITH DETAILS AND ELEVATIONS FOR THESE |
| | ITEMS. |
| | |
| | 44) NOTE: ADDITIONAL COMMENTS MAY RESULT FROM THE |
| | RESPONSES TO THESE PLAN REVIEW COMMENTS. |
| | |
| | -PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW EACH |
| | COMMENT IS BEING ADDRESSED. |
| | -FEEL FREE TO CONTACT ME AT 561-805-6714 (M-F 8-5) TO |
| | DISCUSS COMMENTS, OR E-MAIL ANYTIME [email protected] |
| | |
| | NOTE: SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) |
| | ARE REQUIRED FOR: |
| | LIGHT POLES/SITE LIGHTING |
| | FIRE ALARM |
| | FIRE SPRINKLER |
| | LOW VOLTAGE |
| | ACCESS |
| | LANDSCAPING |
| | IRRIGATION |
| | PARKING LOT |
| | SWIMMING POOLS AND SPAS |
| | GENERATORS |
| | ALL OTHER ITEMS OTHER THAN BMEP |
| | |
| | |
| | |
| | |
| | |
| | |