Plan Review Notes
Plan Review Notes For Permit 18100540
Permit Number 18100540
Review Stop B
Sequence Number 3
Notes
Date Text
2021-01-29 10:39:57BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 18100540
 550 N. QUADRILLE BLVD.
 BUILDING PERMIT 30 STORY BLDG W/ TWO TOWERS
 CONSTRUCTION TYPE: 1A, SPRINKLERED
 MIXED OCCUPANCY: B, R-1, R-2, A-2, A4, S-2, M, E
  
 1 ST REVIEW: APRIL 18, 2019 - DYLAN BATTLES
 2 ND REVIEW: MARCH 2, 2020 - DYLAN BATTLES
 3 RD REVIEW: JANUARY 13, 2021 - ROBERT MCDOUGAL
  
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 FLORIDA BUILDING CODE,5TH EDITION (2014)
 FBC[AMENDED] = 2014 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) NOT RESOLVED. THERE ARE STILL SOME ERRORS AND THE
 PAGE DID NOT LOAD PROPERLY. THE BOTTOM OF THE SHEET IS
 CUT OFF AND THERE IS A PARTIAL SHEET AT THE TOP.
 107.5.3 FBC[AMENDED]PLEASE UPDATE SHEET A0.102 SITE
 DATA. THE DIAGRAM IN THE UPPER RIGHT CORNER DOESN'T
 REFLECT THE CHANGES IN ROOMS SHOWN IN THE PLANS.
 COMPARE SHEET A1.500 FOR SUITE AND UNIT COUNTS.
  
 A) NOT RESOLVED. THERE ARE SEVERAL PAGES OF THE SAME
 SHEETS. RATHER THAN BEING THE SAME SHEET VERSION-ED,
 THERE IS A PAGE WITH THE OLD PLAN SHEET AND A PAGE WITH
 THE REVISED PLAN SHEET. AS A GENERAL COMMENT, PLEASE
 LOOK IN PROJECTDOX AND NOTE IF SOME SHEETS MAY NOT HAVE
 BEEN REPLACED FOR SECOND REVIEW. EITHER UPLOAD REVISED
 SHEETS, LEAVE IT DIDN'T CHANGE OR REQUEST IT TO BE
 DELETED.
  
 B) NOT RESOLVED COMPLETELY. A PORTION OF THE WALL IS
 MISSING BETWEEN UNIT B-1 AND THE UNIT ABOVE IT THAT IS
 NOT LABELED. THE WOMENS BATHROOM AT THE PREFUNCTION
 AREA IS MISSING DETAILS. SEE MARKUPS ON SHEET A1.260.
 LEVEL 8 - SHEET A1.260. IS THE COLUMN LAYER TURNED OFF?
 ALSO, MISSING UNIT NUMBER ABOVE UNIT B1 08-22
 THIS SHEET WAS NOT REVISED FROM FIRST REVIEW SO I THINK
 IT REFLECTS OLD LAYOUT. PLEASE UPLOAD NEW LEVEL 8
 RESIDENTIAL SHEET.
  
 C) NOT RESOLVED. SEE SHEETS PAGES 03.071(A1.265) AND
 03.072(A1.266) FOR REDUNDANT AND CONFLICTING
 INFORMATION. LEVEL 13-14 - 08 UNITS EACH FLOOR . SHEET
 A1.265 SAYS LEVEL 13-14, BUT THEN THE NEXT SHEET IS
 LEVEL 14. PLEASE ADJUST TITLE BLOCK TO STATE LEVEL 13
 ONLY.
  
 D) NOT RESOLVED. PAGE 03.072(A1.266) IS STILL IN THE
 PLANS. LEVEL 14 - 08 UNITS. SHEET A1.266 IS THE COLUMN
 LAYER TURNED OFF? ALSO, MISSING UNIT NUMBERS.
  
 E) RESOLVED. LEVEL 3 - MISSING SUITE NUMBER NEXT TO
 SUITE 7.1 ON SHEET A1.103. LOOKS LIKE IT SHOULD BE
 SUITE 8.
  
 F) RESOLVED. LEVEL 9 - MISSING SUITE NUMBER NEXT
 BETWEEN SUITE 1.3B AND 1.3D ON SHEET A1.109
  
 G) RESOLVED. LEVEL 16 - SUITE 2B ADA LOOKS LIKE WALL
 WAS LEFT BETWEEN ENTRY AND SLEEPING AREA.
  
 H) RESOLVED. LEVEL 17, I CAN'T FIND OFFICE LEVEL FLOOR
 PLAN. I DO SEE RCP AND LIFE SAFETY. PLEASE CHECK IF IT
 WAS LOADED INTO PROJECT DOX.
  
 2) NOT RESOLVED. PAGE 03.052 (A1.240) WAS NOT UPDATED
 AND IS STILL IN THE PLANS. 107.5.3 FBC[AMENDED]SHEET
 03.052 - A1.240 - HOTEL TOWER FLOOR PLAN - LEVEL 8 HAS
 NOT BEEN UPDATED. PLEASE UPLOAD A NEW VERSION, OR
 REQUEST IT BE DELETED FROM THE FOLDER. LEVEL EIGHT IS
 SHOWN ON PODIUM LEVEL 8 DRAWING 03.014 - A1.108 -
 PODIUM FLOOR PLAN AND IN QUADRANT PAGES AS WELL.
  
 3) NOT RESOLVED. THERE ARE STILL SOME ISSUES WITH THE
 ADA REQUIREMENTS. THE GUEST ROOM MATRIX ON PAGE 03.082
 (A1.500) HAS THE REQUIRED ADA ROOMS WITH MOBILITY
 FEATURES AS (5) ROOMS WITHOUT ROLL-IN SHOWERS, (2)
 ROOMS WITH ROLL-IN SHOWERS. THE 2010 ADA TABLE 224.2
 REQUIRES (6) ROOMS WITHOUT ROLL-IN SHOWERS, (2) ROOMS
 WITH ROLL-IN SHOWERS FOR A TOTAL OF (8) ROOMS. THE ADA
 REQUIREMENTS FOR GUEST ROOMS WITH COMMUNICATION
 FEATURES IN TABLE 224.4 IS 14 ROOMS WHEN 200 GUEST
 ROOMS ARE PROVIDED. AT LEAST ONE GUEST ROOM REQUIRED TO
 PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL
 ALSO PROVIDE COMMUNICATION FEATURES COMPLYING WITH
 806.3. NOT MORE THAN 10 PERCENT OF GUEST ROOMS REQUIRED
 TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL
 BE USED TO SATISFY THE MINIMUM NUMBER OF GUEST ROOMS
 REQUIRED TO PROVIDE COMMUNICATION FEATURES COMPLYING
 WITH 806.3. REVISE THE ROOM MATRIX TO CLEARLY SHOW
 COMPLIANCE OF SPECIFIC ROOMS. ALSO REVISE THE PLANS TO
 COMPLY.
 107.5.3 FBC[AMENDED]PLEASE ADD COMMUNICATION SYMBOL TO
 SUITE 4.2B ON SHEET A1.243 ROOM SUMMARY SHEET STATES
 LEVEL 12-15 AS COMMUNICATION. PLEASE ADD SYMBOL TO
 THOSE ROOMS AS WELL. ADD BOTH SYMBOLS TO SUITE 2.B ON
 SHEET A1.246
 PLEASE LOOK AT MOBILITY FEATURES DATA LAST LINE WHERE
 IT SAYS LEVEL 8-16 SUITE 4.2B. I DO SEE THAT THERE IS
 ADA ON LEVEL 16. ADD SYMBOLS AND CORRECT WHERE IT
 STATES 8-16 OR SHOW THAT LEVEL 8-15 SUITE 4.2B ARE ADA
 SUITES.
  
 4) NOT RESOLVED. PROVIDE A ROOM MATRIX THAT SHOWS WHICH
 SPECIFIC HOTEL ROOMS WILL MEET THE ACCESSIBILITY
 REQUIREMENTS FOR MOBILITY AND COMMUNICATION FEATURES.
 SEE FBC ACCESSIBILITY SECTIONS 224 AND 806. NOT MORE
 THAN 10 PERCENT OF GUEST ROOMS REQUIRED TO PROVIDE
 MOBILITY FEATURES COMPLYING WITH 806.2 SHALL BE USED TO
 SATISFY THE MINIMUM NUMBER OF GUEST ROOMS REQUIRED TO
 PROVIDE COMMUNICATION FEATURES COMPLYING WITH 806.3.
 SPECIFY THE LOCATION AND ACCESSIBILITY TYPE OT HOTEL
 ROOMS WITH THE APPROPRIATE SYMBOLS ON THE PLANS. 224.5
 FBC[A]DISPERSION. GUEST ROOMS REQUIRED TO PROVIDE
 MOBILITY FEATURES COMPLYING WITH 806.2 AND GUEST ROOMS
 REQUIRED TO PROVIDE COMMUNICATION FEATURES COMPLYING
 WITH 806.3 SHALL BE DISPERSED AMONG THE VARIOUS CLASSES
 OF GUEST ROOMS, AND SHALL PROVIDE CHOICES OF TYPES OF
 GUEST ROOMS, NUMBER OF BEDS, AND OTHER AMENITIES
 COMPARABLE TO THE CHOICES PROVIDED TO OTHER
 GUESTS.WHERE THE MINIMUM NUMBER OF GUEST ROOMS REQUIRED
 TO COMPLY WITH 806 IS NOT SUFFICIENT TO ALLOW FOR
 COMPLETE DISPERSION, GUEST ROOMS SHALL BE DISPERSED IN
 THE FOLLOWING PRIORITY: GUEST ROOM TYPE, NUMBER OF
 BEDS, AND AMENITIES. AT LEAST ONE GUEST ROOM REQUIRED
 TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL
 ALSO PROVIDE COMMUNICATION FEATURES COMPLYING WITH
 806.3. NOT MORE THAN 10 PERCENT OF GUEST ROOMS REQUIRED
 TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL
 BE USED TO SATISFY THE MINIMUM NUMBER OF GUEST ROOMS
 REQUIRED TO PROVIDE COMMUNICATION FEATURES COMPLYING
 WITH 806.3.
 -ONLY 10 PERCENT OF REQUIRED ROOMS CAN SHARE
 COMMUNICATION AND MOBILITY. PLEASE SHOW COMMUNICATION
 ROOMS ONLY SHARE IN ONE SUITE.
 -PLEASE VERIFY THAT ROOMS ARE EVENLY DISTRIBUTED FOR
 ROOM TYPES AND PRICE RANGE.
  
 5) NOT RESOLVED. PROVIDE A ROOM MATRIX TO SHOW WHICH
 SPECIFIC HOTEL ROOMS WILL MEET THIS REQUIREMENT. 806.4
 FBC[A]HOTEL,MOTEL AND CONDOMINIUM SPECIAL ACCESSIBILITY
 FEATURES. THIS SECTION DOES NOT RELIEVE THE OWNER OF
 THE RESPONSIBILITY OF PROVIDING ACCESSIBLE ROOMS IN
 CONFORMANCE WITH SECTION 224 AND 806 OF THIS CODE. IN
 ALL BUILDINGS, STRUCTURES AND FACILITIES LICENSED AS A
 HOTEL, MOTEL OR RESORT CONDOMINIUM PURSUANT TO CHAPTER
 509, F.S., A NUMBER OF ROOMS EQUALING AT LEAST 5
 PERCENT OF THE GUEST ROOMS MINUS THE TOTAL NUMBER OF
 REQUIRED (ACCESSIBLE) ROOMS REQUIRED BY TABLE 224.2
 SHALL PROVIDE THE FOLLOWING ADDITIONAL SPECIAL
 ACCESSIBILITY FEATURES:
 (I) GRAB RAILS IN BATHROOMS AND TOILET ROOMS WHICH
 COMPLY WITH SECTION 604.5.
 (II) ALL BEDS IN DESIGNED ACCESSIBLE GUEST ROOMS SHALL
 BE OPEN-FRAME TYPE THAT ALLOWS THE PASSAGE OF LIFT
 DEVICES.
 (III)WATER CLOSETS THAT COMPLY WITH SECTION 604.4.
 -SHOW WHICH ROOMS COMPLY WITH 806.4
  
 6) NOT RESOLVED. THERE ARE HOTEL ROOMS THAT APPEAR TO
 BE EQUIPPED WITH COOKING APPLIANCES. YOUR RESPONSE
 STATES THAT NOTE 26 ON SHEET A0.201 ADDRESSES THIS
 COMMENT. IT STATES THAT SERVICE APARTMENTS DESIGNED FOR
 STAYS OF MORE THAN 30 DAYS ARE REQUIRED TO COMPLY WITH
 FAIRHOUSING RATHER THAN ADA ACCESSIBILITY REQUIREMENTS.
 THIS IS NOT ACCURATE. BECAUSE THESE ARE HOTEL ROOMS
 THEY ARE NOT APARTMENTS AND ARE REQUIRED TO COMPLY WITH
 THE FLORIDA ACCESSIBILITY CODE AS WELL AS FAIRHOUSING
 GUIDELINES IF THEY ARE USED FOR STAYS OF MORE THAN 30
 DAYS. YOU WILL NEED TO IDENTIFY THESE ROOMS AND SHOW
 THAT THEY MEET THE MOST RESTRICTIVE REQUIREMENTS OF THE
 TWO. 224.1 ADVISORY FBC[A]ARE THERE NON-TRANSIENT ROOMS
 (MORE THAN 30 DAY STAY)?
 IF SO, THOSE ROOMS MAY FALL UNDER THE FAIRHOUSING
 GUIDELINES IN ADDITION TO ACCESSIBILITY FBC 2017 6 TH
 EDITION.
  
 FAIRHOUSING REVIEW:
 7) RESOLVED. 1986 ANSI [A117.1] IF A DESIGNER OR
 BUILDER CHOOSES TO FOLLOW AN ACCESSIBILITY STANDARD
 OTHER THAN THE 1986 ANSI A117.1 STANDARD, OR A MORE
 RECENT VERSION OF THE ANSI A117.1, SUCH AS THE 1992
 CABO/ANSI, THAT CARE BE TAKEN TO ENSURE THE STANDARD
 USED IS AT LEAST EQUIVALENT TO OR STRICTER THAN THE
 1986 ANSI A117.1 STANDARD.
 -WHAT STANDARD IS BEING APPLIED FOR COMPLIANCE WITH
 FAIR HOUSING? YOU CAN USE GUIDELINES THAT FALL WITHIN
 THE SAFE HARBOR FOR COMPLIANCE?
  
 A) PARTIALLY RESOLVED. PAGE 03.097(A1.519) THE MASTER
 BATH TOILET IN RESIDENTIAL UNIT S8 DOES NOT APPEAR TO
 COMPLY WITH A TYPE B BATHROOM. ON PAGE 03.102(A1.524)
 RESIDENTIAL UNIT B1 HAS ONE BATH ROOM MARKED AS TYPE A
 AND THE OTHER AS TYPE B. THE UNIT CAN ONLY BE ONE TYPE.
 ON PAGE 03.104(A1.526) SHOW THE REQUIRED CLEAR FLOOR
 SPACE AT THE TOILET IN UNIT B3.1. IT WOULD BE HELPFUL
 TO ADD A MATRIX OF ROOMS ON SHEET A1.500 WHICH BATHROOM
 SPEC IS BEING USED AND APPLY THE FOLLOWING FOR SPEC A
 AND B
  
 SPECIFICATION A:
 IF SPECIFICATION A IS USED IT APPLIES TO ALL BATHROOMS,
 AND ALL FIXTURES IN THOSE BATHROOMS MUST BE USABLE.
 SPECIFICATION B:
 IF SPECIFICATION B IS USED, IT APPLIES TO ONE BATHROOM,
 AND ONLY ONE OF EACH TYPE OF FIXTURE MUST BE USABLE;
 ADDITIONAL BATHROOMS IN THE UNIT ARE EXEMPT ONLY FROM
 MANEUVERING AND CLEAR FLOOR SPACE REQUIREMENTS AT
 FIXTURES.
  
 B) RESOLVED. PLEASE ADD TO FAIRHOUSING NOTES ON SHEET
 A1.528. THIS SAYS ALL BATHROOMS TO BE SPEC A. PLEASE
 ADJUST NOTE SINCE BOTH SPEC ARE BEING USED.
  
 C) RESOLVED. ADD NOTE FOR USABLE HARDWARE.
 REQUIREMENT 3 - USABLE DOORS. THE DOORS IN COMMON
 SPACES AND THE SIDE ENTERING INTO DWELLING UNITS NEED
 TO HAVE USABLE HARDWARE THAT CAN BE USED WITHOUT TIGHT
 GRASPING OR TWISTING.
 -TYPICALLY THE HARDWARE WOULD BE A LEVER TYPE. THIS
 TYPE OF HARDWARE WOULD NOT BE REQUIRED ONCE INSIDE THE
 UNIT. YOU MAY WANT TO CLARIFY HARDWARE ON THE DOOR
 SCHEDULE.
  
 D) NOT RESOLVED. DOOR SCHEDULES ON PAGES 03.242(A6.104)
 AND 03.243(A6.105) NEED TO BE CLEANED UP AND MADE
 LEGIBLE. DOOR SCHEDULE ON SHEET A6.104 IS DISTORTED AND
 INFORMATION IS NOT LEGIBLE. PLEASE ADJUST AND POPULATE
 AS NEEDED.
  
 E) RESOLVED. SHOW ACCESSIBLE ROUTES FOR EACH UNIT TYPE.
  
 F) RESOLVED. ADD DETAIL OF HOW ACCESS IS GAINED AT
 RESIDENTIAL BALCONY. IS THERE ELEVATION CHANGE TO MEET
 FAIRHOUSING MAX OF 4 INCHES TOP OF THRESHOLD?
  
 LIFE SAFETY:
  
 8) PARTIALLY RESOLVED. SPECIFY THE REQUIRED FIRE
 RATINGS FOR THE EXIT STAIR DOORS AND THE FIRE SERVICE
 ACCESS LOBBY DOORS IN THE DOOR SCHEDULES. 3006.2
 FBC[B]SHEET A1.107 SHOWS NO ELEVATOR LOBBY ON LEVEL 7
 AT ELEVATORS 8, 9 AND 10. IF REQUIRED PLEASE SHOW THE
 DOORS.
 1024.4 FBC[B]TERMINATION. EXIT PASSAGEWAYS ON THE LEVEL
 OF EXIT DISCHARGE SHALL TERMINATE AT AN EXIT DISCHARGE.
 EXIT PASSAGEWAYS
 ON OTHER LEVELS SHALL TERMINATE AT AN EXIT.
 EXIT DISCHARGE. THAT PORTION OF A MEANS OF EGRESS
 SYSTEM BETWEEN THE TERMINATION OF AN EXIT AND A PUBLIC
 WAY.
  
 9) RESOLVED. 3005.5 FBC[B] SHUNT TRIP. WHERE ELEVATOR
 HOISTWAYS, ELEVATOR MACHINE ROOMS, CONTROL ROOMS AND
 CONTROL SPACES CONTAINING ELEVATOR CONTROL EQUIPMENT
 ARE PROTECTED WITH AUTOMATIC SPRINKLERS, A MEANS
 INSTALLED IN ACCORDANCE WITH SECTION 21.4 OF NFPA 72
 SHALL BE PROVIDED TO DISCONNECT AUTOMATICALLY THE MAIN
 LINE POWER SUPPLY TO THE AFFECTED ELEVATOR PRIOR TO THE
 APPLICATION OF WATER. THIS MEANS SHALL NOT BE
 SELF-RESETTING. THE ACTIVATION OF AUTOMATIC SPRINKLERS
 OUTSIDE THE HOISTWAY, MACHINE ROOM, MACHINERY SPACE,
 CONTROL ROOM OR CONTROL SPACE SHALL NOT DISCONNECT THE
 MAIN LINE POWER SUPPLY.
  
 10) RESOLVED. 3006.2 FBC[B] HOISTWAY OPENING PROTECTION
 REQUIRED. ELEVATOR HOISTWAY DOOR OPENINGS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 3006.3 WHERE AN
 ELEVATOR HOISTWAY CONNECTS MORE THAN THREE STORIES, IS
 REQUIRED TO BE ENCLOSED WITHIN A SHAFT ENCLOSURE IN
 ACCORDANCE WITH SECTION 712.1.1 AND ANY OF THE
 FOLLOWING CONDITIONS APPLY:
 5. THE BUILDING IS A HIGH RISE AND THE ELEVATOR
 HOISTWAY IS MORE THAN 75 FEET (22 860 MM) IN HEIGHT.
 THE HEIGHT OF THE HOISTWAY SHALL BE MEASURED FROM THE
 LOWEST FLOOR TO THE HIGHEST FLOOR OF THE FLOORS SERVED
 BY THE HOISTWAY.
 -IS THE PRE FUNCTION AREA OPEN AIR? IT IS HARD TO TELL
 BUT IT APPREARS TO BE COVERED BY RESIDENTIAL ABOVE.
 -FREIGHT ELEVATOR DOES NOT HAVE ELEVATOR LOBBY ON THE 8
 TH FLOOR. PLEASE REVIEW 3006.2 FOR OPENING PROTECTION
 ON SHAFT MORE THAN 75 FEET.
  
 11) NOT RESOLVED. YOUR RESPONSE STATES THAT A LIFE
 SAFETY PLAN FOR THE PARK WAS ADDED ON SHEET ALS1.109.
 THERE IS NO SUCH SHEET IN THE PLANS OR THE PLAN INDEX.
 PLEASE CLARIFY. 107.5.3 FBC[AMENDED]ADD SCALE TO LIFE
 SAFETY PLANS. I THINK IT IS 1/16 SCALE.
 ALSO, IS THERE A LIFE SAFETY SHEET FOR THE PARK ABOVE
 THE TENNIS PAVILION? PLEASE PROVIDE OR LET ME KNOW
 WHICH SHEET I CAN FIND IT.
  
 12) NOT RESOLVED. THERE ARE EXIT DOORS AT GRADE LEVEL
 THAT DO NOT HAVE EGRESS LOAD TAGS. 1004 FBC[B]PLEASE
 PROVIDE TOTAL OCCUPANT LOAD FOR EACH EGRESS DOOR AT
 GRADE WHERE THE DOOR PROVIDES EGRESS FROM MULTIPLE
 AREAS. FOR EXAMPLE EGRESS DOORS IN HOTEL LOBBY PICKUP
 THE STAIRS AND OTHER AREAS FROM FIRST LEVEL USES. I AM
 LOOKING FOR DATA TAG LIKE WAS USED AT STAIRWAY DOORS.
  
 13) RESOLVED. 1025.1 FBC[B]GENERAL. APPROVED LUMINOUS
 EGRESS PATH MARKINGS DELINEATING THE EXIT PATH SHALL BE
 PROVIDED IN HIGH-RISE BUILDINGS OF GROUP A, B, E, I, M,
 AND R-1 OCCUPANCIES IN ACCORDANCE WITH SECTIONS 1025.1
 THROUGH 1025.5.
 -ST4 AND ST3 FROM R-1 LEVELS TO MEET 1025.1 FOR
 LUMINOUS MARKINGS.
  
 14) RESOLVED. 1013.2 FBC[B] FLOOR-LEVEL EXIT SIGNS IN
 GROUP R-1. WHERE EXIT SIGNS ARE REQUIRED IN GROUP R-1
 OCCUPANCIES BY SECTION 1013.1, ADDITIONAL LOW-LEVEL
 EXIT SIGNS SHALL BE PROVIDED IN ALL AREAS SERVING GUEST
 ROOMS IN GROUP R-1 OCCUPANCIES AND SHALL COMPLY WITH
 SECTION 1013.5.
 -ADD LOW LEVEL EXIT SIGNS AS REQUIRED, OR STATE WHICH
 PAGE THIS INFORMATION CAN BE FOUND.
  
 15) NOT RESOLVED. THE EXIT ACCESS TRAVEL DISTANCE FOR
 SPRINKLERED TYPE M OCCUPANCIES IS 250' IN 2014 FBC
 TABLE 1016.2 AND THE TABLE ON SHEET ALS1.101 HAS 400'.
 THE EGRESS TRAVEL DISTANCE FOR SPRINKLERED RESIDENTIAL
 OCCUPANCIES IS 250' IN FBC TABLE 1016.2 AND THE TABLE
 ON THE LIFE SAFETY PLANS SHEETS WITH RESIDENTIAL UNITS
 HAS 325'. YOU ARE REQUIRED TO MEET THE MOST RESTRICTIVE
 REQUIREMENT BETWEEN THE F.F.P.C. AND THE FBC BUILDING.
 SOME DESIGNERS LIST THE REQUIREMENTS OF BOTH CODES IN
 THEIR TABLES WITH A NOTE TO USE THE MOST RESTRICTIVE
 REQUIREMENT. PLEASE REVIEW ALL LIFE SAFETY PLANS FOR
 REQUESTED DATA. THE RESIDENTS LOUNGE AREA (0161) HAS AN
 OCCUPANT LOAD OF MORE THAN 49 AND REQUIRES TWO EXITS
 PER TABLE 1015.1. BE SURE TO SHOW EXIT ROUTES FOR ALL
 AREAS. 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA.
 THIS IS FOR ALL LIFE SAFETY SHEETS
 A. ADD MAX COMMON PATH AND MAX TRAVEL DISTANCE FOR R-1
 AND R-2 TO ALS1.100 COMPLIANCE SUMMARY FOR FLORIDA
 BUILDING CODE IN ADDITION TO THE PROVIDED NFPA. THE
 MORE RESTRICTIVE CODE WILL APPLY.
 B. SHOW MAXIMUM PATH OF TRAVEL ON ALL L.S. PLANS.
 CURRENTLY, L.S. SHEETS SHOW PATH OF TRAVEL DISTANCE OR
 TOTAL DISTANCE. PLANS SHOULD SHOW BOTH COMMON PATH OF
 TRAVEL AND EXIT ACCESS TRAVEL DISTANCE. THIS SHOULD BE
 DONE FOR WORST CASE IN EACH GENERAL AREA.
  
 16) NOT COMPLETELY RESOLVED. THERE ARE SEVERAL RAMPS
 SHOWN ON THE PLANS. PLEASE IDENTIFY EACH WITH AN ID TAG
 AND PROVIDE DETAILS FOR EACH OF THEM TO SHOW THAT THEY
 MEET THE ACCESSIBILITY REQUIREMENTS FOR RAMPS. FBC
 ACCESSIBILITY 405. 1003.5 FBC[B] ELEVATION CHANGE. DOES
 EXIT FROM RESIDENT LOBBY TO STAIR 2 HAVE STEPS? PLEASE
 REVIEW
 -HOW DO STEPS WORK AT EGRESS FROM RESIDENT LOUNGE TO
 STAIR ST2? PLEASE REVIEW 1003.5 FOR CHANGE IN ELEVATION
 IN PATH OF EGRESS.
  
 17) RESOLVED. 1012.9 FBC[B] INTERMEDIATE HANDRAILS.
 STAIRWAYS SHALL HAVE INTERMEDIATE HANDRAILS LOCATED IN
 SUCH A MANNER THAT ALL PORTIONS OF THE STAIRWAY MINIMUM
 WIDTH OR REQUIRED CAPACITY ARE WITHIN 30 INCHES (762
 MM) OF A HANDRAIL. ON MONUMENTAL STAIRS, HANDRAILS
 SHALL BE LOCATED ALONG THE MOST DIRECT PATH OF EGRESS
 TRAVEL.
 -CHECK COMPLIANCE WITH 1012.9 AT BALLROOM STEPS.
  
 18) RESOLVED. 713.13.4 CHUTE DISCHARGE ROOM. WASTE OR
 LINEN CHUTES SHALL DISCHARGE INTO AN ENCLOSED ROOM
 SEPARATED BY FIRE BARRIERS WITH A FIRE RESISTANCE
 RATING NOT LESS THAN THE REQUIRED FIRE RATING OF THE
 SHAFT ENCLOSURE AND CONSTRUCTED IN ACCORDANCE WITH
 SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN
 ACCORDANCE WITH SECTION 711, OR BOTH. OPENINGS INTO THE
 DISCHARGE ROOM FROM THE REMAINDER OF THE BUILDING SHALL
 BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE
 PROTECTION RATING EQUAL TO THE PROTECTION REQUIRED FOR
 THE SHAFT ENCLOSURE. DOORS SHALL BE SELF- OR
 AUTOMATICCLOSING UPON THE DETECTION OF SMOKE IN
 ACCORDANCE WITH SECTION 716.5.9.3. WASTE CHUTES SHALL
 NOT TERMINATE IN AN INCINERATOR ROOM. WASTE AND LINEN
 ROOMS THAT ARE NOT PROVIDED WITH CHUTES NEED ONLY
 COMPLY WITH TABLE 509.
 -DOUBLE DOORS TO TRASH ROOM AT BASE LEVEL SHOW 90
 MINUTE RATING, BUT 713.13.4 REQUIRES SAME LEVEL OF
 PROTECTION FOR OPENINGS IN DISCHARGE ROOM EQUAL TO THE
 SHAFT ENCLOSURE (2 HOURS).
  
 19) RESOLVED. 420.3 FBC[B]HORIZONTAL SEPARATION AND
 FBC[B] 602 FLOOR ASSEMBLIES SEPARATING DWELLING UNITS
 IN THE SAME BUILDINGS, FLOOR ASSEMBLIES SEPARATING
 SLEEPING UNITS IN THE SAME BUILDING AND FLOOR
 ASSEMBLIES SEPARATING DWELLING OR SLEEPING UNITS FROM
 OTHER OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME
 BUILDING SHALL BE CONSTRUCTED AS HORIZONTAL ASSEMBLIES
 IN ACCORDANCE WITH SECTION 711.
 -602 FBC[B]SHEET A7.310 HAS CEILING ASSEMBLIES. PLEASE
 SHOW THE RATED ASSEMBLY FOR CEILINGS SEPARATING
 DWELLING AND SLEEPING UNITS AS STATED IN LIFE SAFETY
 COMPLIANCE SUMMARY ALS1.100.
  
 20) NOT RESOLVED. THE TAG ON THE WASTE CHUTE ACCESS
 DOORS FROM THE CORRIDORS STILL HAVE NR INSTEAD OF 45
 MIN. ON THE LIFE SAFETY PLANS.713.13.3 FBC[B]CHUTE
 ACCESS ROOMS. ACCESS OPENINGS FOR WASTE OR LINEN CHUTES
 SHALL BE LOCATED IN ROOMS OR COMPARTMENTS ENCLOSED BY
 NOT LESS THAN 1-HOUR FIRE BARRIERS CONSTRUCTED IN
 ACCORDANCE WITH SECTION 707 OR HORIZONTAL ASSEMBLIES
 CONSTRUCTED IN ACCORDANCE WITH SECTION 711, OR BOTH.
 OPENINGS INTO THE ACCESS ROOMS SHALL BE PROTECTED BY
 OPENING PROTECTIVES HAVING A FIRE PROTECTION RATING OF
 NOT LESS THAN 3/4 HOUR. DOORS SHALL BE SELF- OR
 AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE IN
 ACCORDANCE WITH SECTION 716.5.9.3.
 -LIFE SAFETY SHEETS SHOW CHUTE ACCESS DOORS AS NOT
 RATED (NR). THESE ACCESS DOORS ARE REQUIRED TO HAVE A
 3/4 HOUR RATING PER 713.13.3.
 - ADD DOOR TAG TO THE DOORS LEADING TO THE TRASH CHUTE
 OR TELL ME WHAT SHEETS THER ARE ON. I WAS LOOKING ON
 QUADRANT SHEETS WHERE THE OTHER TAGS FOR COMMON SPACE
 DOORS WERE LOCATED.
  
 DEFERRED SUBMITTALS
 21) NOT COMPLETELY RESOLVED. PLEASE LABEL GENERAL NOTE
 16 ON SHEET A0.001 AS "DEFERRED SUBMITTALS" AND NOTE
 THAT THE ITEMS BEING DEFERRED ARE REQUIRED TO BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORDED AND SUBMITTED AND APPROVED BY THE CITY OF WEST
 PALM BEACH BUILDING DEPARTMENT PRIOR TO BEING
 INSTALLED. ANY ITEMS NOT LISTED WILL HAVE TO BE
 APPROVED BEFORE THE PERMIT CAN BE ISSUED. 107.3.4.1
 FBC[AMENDED] PLEASE PROVIDE A LIST OF DEFERRED
 SUBMITTALS ON PLANS SO THAT I WILL NOT ASK FOR ITEMS
 THAT WILL BE SUPPLIED AT A LATER DATE, OR INDICATE
 WHICH PAGE A LIST CAN BE FOUND.
 THESE ARE THE ONES I BELIEVE WE WILL NEED, BUT THIS IS
 NOT A COMPLETE LIST.
 A) COMPONENT & CLADDING PRODUCT APPROVALS (COMPLY WITH
 PRESSURES SHOWN ON SHEET S0.0.5)
 B) CURTAIN WALL SUBMITTAL (COMPLY WITH PRESSURES SHOWN
 ON SHEET S0.0.5)
 C) FENESTRATION SHOP DRAWINGS TO INCLUDE ALL WINDOWS,
 DOORS, TRANSOMS, SLIDERS, LOUVERS AND MULL BARS.
 D) FLOORING UNDERLAYMENT WITH THREE REPORTS:
 1. 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND
 SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF
 NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED,
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E90.
 2. 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR
 BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR
 NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN
 ACCORDANCE WITH ASTM E492.
 3. 603.1 FBC[B] ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
 E) RAILINGS AND GUARDRAILS. INCLUDES BALCONIES, STAIRS
 AND COMMON SPACES.
 F) PARKING GARAGE VEHICLE BARRIER PER 406.4.2 FBC[B]
 G) FIRE SPRAY
 H) 806.1 FBC[B] GENERAL REQUIREMENTS. CURTAINS,
 DRAPERIES, HANGINGS AND OTHER DECORATIVE MATERIALS
 SUSPENDED FROM WALLS OR CEILINGS SHALL MEET THE FLAME
 PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 IN
 ACCORDANCE WITH SECTION 806.2 OR BE NONCOMBUSTIBLE.
 I) LIGHTWIEGHT CONCRETE.
 J) WINDOW WASHING EQUIPMENT ATTACHMENTS/LOCATIONS AT
 ROOF.
 K) E.F.I.S. IF APPLICABLE
 L) LIGHTING CONTROLS PER ENERGY CODE C405.2 LIGHTING
 CONTROLS (MANDATORY) C405.5 EXTERIOR LIGHTING
 (MANDATORY)
 M) FINAL GYM EQUIPMENT LAYOUT WITH ACCESSIBILTY
 REQUIREMENTS PROVIDED.
 PRODUCT APPROVALS FOR ROOFING ARE PROVIDED, BUT NO
 SELECTIONS ARE MADE AND IT IS NOT CLEAR WHICH AREA OF
 ROOF RECEIVE.
 ROOFING CAN BE ADDED TO DEFERRED SUBMITTAL LIST.
  
 22) NOT RESOLVED. THE PRODUCT APPROVALS THAT WERE
 SUBMITTED ARE REQUIRED TO BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. IF YOU ARE NOT SURE
 WHICH PRODUCTS WILL BE USED, YOU CAN SPECIFY ON THE
 PLANS THAT THEY WILL BE SUBMITTED LATER. ALSO, PROVIDE
 PRODUCT APPROVAL FOR ROOF INSULATION AND ATTACHMENT.
 OTHER PRODUCT APPROVALS WERE SUBMITTED FOR DOORS, BUT
 THEY WERE NOT STAMPED AS REVIEWED. AS PART OF
 FENESTRATION PACKAGE PROVIDE ALL PRODUCT APPROVALS WITH
 INDICATION THAT THEY WERE REVIEWED BY THE DESIGNER OF
 RECORD.
  
 23) RESOLVED. ENERGY CODE REVIEW:
 A) THIS BUILDING WAS BROUGHT IN UNDER 2014 CODE CYCLE.
 PLEASE REVISE TO THAT CODE DATE, OR PROVIDE LETTER OF
 COMPLIANCE THAT CURRENT CODES ARE EQUIVALENT.
 B) C407.2.1 ROOF/CEILING THERMAL ENVELOPE. SECTIONS FOR
 ROOFING AND DOORS SHOW NO DATA. PLEASE INCLUDE THOSE
 VALUES IN THE ENERGY CALCULATIONS.
 C) IN SECTION FOR WALLS THE ASSEMBLY STATES 6 INCH
 INSULATION. WHERE IS THAT ASSEMBLY BEING USED ON THE
 BUILDING?
  
 ACCESSIBILITY REVIEW:
  
 24) PROVIDE DETAILS TO SHOW THAT THE BUILT IN LOCKER
 ROOM BENCHES ARE ADA COMPLIANT. 803.1 FBC[A] GENERAL.
 DRESSING, FITTING, AND LOCKER ROOMS SHALL COMPLY WITH
 803.
 803.2 FBC[A] TURNING SPACE. TURNING SPACE COMPLYING
 WITH 304 SHALL BE PROVIDED WITHIN THE ROOM.
 803.3 FBC[A] DOOR SWING. DOORS SHALL NOT SWING INTO THE
 ROOM UNLESS A CLEAR FLOOR OR GROUND SPACE COMPLYING
 WITH 305.3 IS PROVIDED BEYOND THE ARC OF THE DOOR
 SWING.
 803.4 FBC[A] BENCHES. A BENCH COMPLYING WITH 903 SHALL
 BE PROVIDED WITHIN THE ROOM.
 903.4 FBC[A] BACK SUPPORT. THE BENCH SHALL PROVIDE FOR
 BACK SUPPORT OR SHALL BE AFFIXED TO A WALL. BACK
 SUPPORT SHALL BE 42 INCHES LONG MINIMUM AND SHALL
 EXTEND FROM A POINT 2 INCHES MAXIMUM ABOVE THE SEAT
 SURFACE TO A POINT 18 INCHES MINIMUM ABOVE THE SEAT
 SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES MAXIMUM FROM
 THE REAR EDGE OF THE SEAT MEASURED HORIZONTALLY.
  
 25) NOT COMPLETELY RESOLVED. THE ADA INFORMATION, CLEAR
 FLOOR SPACE WAS NOT PROVIDED FOR THE EXERCISE EQUIPMENT
 IN THE MENS GYM. 236.1 FBC[A]GENERAL. AT LEAST ONE OF
 EACH TYPE OF EXERCISE MACHINE AND EQUIPMENT SHALL
 COMPLY WITH 1004.
 1004.1 FBC[A]CLEAR FLOOR SPACE. EXERCISE MACHINES AND
 EQUIPMENT SHALL HAVE A CLEAR FLOOR SPACE COMPLYING WITH
 305 POSITIONED FOR TRANSFER OR FOR USE BY AN INDIVIDUAL
 SEATED IN A WHEELCHAIR. CLEAR FLOOR OR GROUND SPACES
 REQUIRED AT EXERCISE MACHINES AND EQUIPMENT SHALL BE
 PERMITTED TO OVERLAP.
  
 ADVISORY 1004.1 FBC[A]CLEAR FLOOR SPACE. ONE CLEAR
 FLOOR OR GROUND SPACE IS PERMITTED TO BE SHARED BETWEEN
 TWO PIECES OF EXERCISE EQUIPMENT.TO OPTIMIZE SPACE USE,
 DESIGNERS SHOULD CAREFULLY CONSIDER LAYOUT OPTIONS SUCH
 AS CONNECTING ENDS OF THE ROW AND CENTER AISLE SPACES.
 THE POSITION OF THE CLEAR FLOOR SPACE MAY VARY GREATLY
 DEPENDING ON THE USE OF THE EQUIPMENT OR MACHINE. FOR
 EXAMPLE, TO PROVIDE ACCESS TO A SHOULDER PRESS MACHINE,
 CLEAR FLOOR SPACE NEXT TO THE SEAT WOULD BE APPROPRIATE
 TO ALLOW FOR TRANSFER. CLEAR FLOOR SPACE FOR A BENCH
 PRESS MACHINE DESIGNED FOR USE BY AN INDIVIDUAL SEATED
 IN A WHEELCHAIR, HOWEVER, WILL MOST LIKELY BE CENTERED
 ON THE OPERATING MECHANISMS.
  
 26) NOT RESOLVED. THE NOTES ON THE POOLS STATE TO REFER
 TO SHEETS SP.001, SP.002 AND SP.003. I WAS NOT ABLE TO
 FIND THESE SHEETS. SHOW HOW THE POOLS WILL COMPLY WITH
 FBC ACCESSIBILITY SECTION 242.2 SWIMMING POOLS. AT
 LEAST TWO ACCESSIBLE MEANS OF ENTRY SHALL BE PROVIDED
 FOR SWIMMING POOLS. (SEE EXCEPTIONS) ACCESSIBLE MEANS
 OF ENTRY SHALL BE SWIMMING POOL LIFTS COMPLYING WITH
 1009.2; SLOPED ENTRIES COMPLYING WITH 1009.3; TRANSFER
 WALLS COMPLYING WITH 1009.4; TRANSFER SYSTEMS COMPLYING
 WITH 1009.5; AND POOL STAIRS COMPLYING WITH 1009.6. AT
 LEAST ONE ACCESSIBLE MEANS OF ENTRY PROVIDED SHALL
 COMPLY WITH 1009.2 OR 1009.3. ADVISORY 242.2 SWIMMING
 POOLS. WHERE MORE THAN ONE MEANS OF ACCESS IS PROVIDED
 INTO THE WATER, IT IS RECOMMENDED THAT THE MEANS BE
 DIFFERENT. PROVIDING DIFFERENT MEANS OF ACCESS WILL
 BETTER SERVE THE VARYING NEEDS OF PEOPLE WITH
 DISABILITIES IN GETTING INTO AND OUT OF A SWIMMING
 POOL. IT IS ALSO RECOMMENDED THAT WHERE TWO OR MORE
 MEANS OF ACCESS ARE PROVIDED, THEY NOT BE PROVIDED IN
 THE SAME LOCATION IN THE POOL. DIFFERENT LOCATIONS WILL
 PROVIDE INCREASED OPTIONS FOR ENTRY AND EXIT,
 ESPECIALLY IN LARGER POOLS. ADVISORY 242.2 SWIMMING
 POOLS EXCEPTION 1. POOL WALLS AT DIVING AREAS AND AREAS
 ALONG POOL WALLS WHERE THERE IS NO POOL ENTRY BECAUSE
 OF LANDSCAPING OR ADJACENT STRUCTURES ARE TO BE COUNTED
 WHEN DETERMINING THE NUMBER OF ACCESSIBLE MEANS OF
 ENTRY REQUIRED.
 COMMUNITY POOLS THAT ARE ASSOCIATED WITH A PRIVATE
 RESIDENTIAL COMMUNITY THAT DO NOT RECEIVE GOVERNMENTAL
 FINANCIAL ASSISTANCE OR SPONSORSHIP AND ARE LIMITED TO
 THE EXCLUSIVE OF RESIDENTS AND THEIR GUESTS ARE NOT
 COVERED BY THE ADA ACCESSIBILITY REQUIREMENTS,
 INCLUDING PROVISIONS FOR POOL LIFTS OR SLOPED ENTRIES.
 IF A SWIMMING POOL LOCATED IN A RESIDENTIAL COMMUNITY
 IS MADE AVAILABLE TO THE PUBLIC FOR RENTAL OR USE IT IS
 REQUIRED TO COMPLY WITH TITLE II OF THE ADA. SPECIFY ON
 THE PLANS THE FORMER OR SHOW COMPLIANCE WITH THE LATTER
 STATEMENTS. SEE DECLARATORY STATEMENT, DS 2013-011.
  
 1009.1 GENERAL. WHERE PROVIDED, POOL LIFTS, SLOPED
 ENTRIES, TRANSFER WALLS, TRANSFER SYSTEMS, AND POOL
 STAIRS SHALL COMPLY WITH 1009.
 -IF POOL LIFTS ARE PROVIDED PLEASE ADD DETAILS TO THE
 ADA DETAIL SHEET.
 ALSO, ADD ANY ADDITIONAL DETAILS IF APPLICABLE TO ADA
 DETAILS FOR THE POOLS.
  
 27) NOT RESOLVED. PROVIDE DETAILS OF ALL RAMPS TO SHOW
 COMPLIANCE WITH ACCESSIBILITY REQUIREMENTS. THE MAXIMUM
 RAMP SLOPE IS 1:12 (8%). FBC ACCESSIBILITY SECTION 405.
 405.8 FBC[A]HANDRAILS.RAMP RUNS WITH A RISE GREATER
 THAN 6 INCHES (150 MM) SHALL HAVE HANDRAILS COMPLYING
 WITH 505.
 -SHEET ALS1.107 SHOWS RAMP FROM PRE-FUNCTION UP TO
 ELEVATORS AND STAIR ST8. WILL THERE BE RAILS PROVIDE
 THE RAMP AS REQUIRED? ALSO, IS THE WALKWAY FROM RAMP TO
 STAIR 8 GOING TO HAVE RAIL OR IS IT OPEN FROM ABOVE TO
 PRE-FUNCTION?
  
 CHAPTER 4 - HIGHRISE:
  
 28) RESOLVED. 403.5.3.1 FBC[B]STAIRWAY COMMUNICATION
 SYSTEM. A TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS
 SYSTEM CONNECTED TO AN APPROVED CONSTANTLY ATTENDED
 STATION SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH
 FLOOR IN EACH STAIRWAY WHERE THE DOORS TO THE STAIRWAY
 ARE LOCKED.
 -WILL THE DOORS BE LOCKED FROM THE STAIRWAY SIDE? IF SO
 PLEASE ADD COMMUNICATION SYSTEM AS REQUIRED IN
 403.5.3.1
  
 29) NOT RESOLVED. THERE ARE SEVERAL EXIT STAIRWAYS THAT
 ARE NOT CONTINUOUS FROM THE UPPER FLOORS TO THE LEVEL
 OF EXIT DISCHARGE AT THE GROUND FLOOR. THE PLANS SHOW
 THAT THE STAIRWAYS TRANSFER THROUGH A FIRE RATED
 "TRANSFER" CORRIDOR (EXIT PASSAGEWAY) TO ANOTHER
 STAIRWAY IN ORDER TO TRAVEL TO THE EXIT DISCHARGE.
 THERE ARE OPENINGS INTO THE CORRIDOR (EXIT PASSAGEWAY)
 TO AN AHU ROOM AND TWO MAINTENANCE/ACCESS ROOMS. PLEASE
 KEEP IN MIND THAT ONCE AN OCCUPANT ENTERS AN EXIT
 STAIRWAY THE EXPECTATION IS THAT THE OCCUPANT WILL HAVE
 THE SAME PROTECTION AS PROVIDED BY THE EXIT STAIRWAY
 UNTIL THEY REACH THE EXIT DISCHARGE. THE SAME
 REQUIREMENTS FOR THE STAIRWAY WILL APPLY TO THE
 TRANSFER CORRIDOR. NO OPENINGS, PENETRATIONS OR SYSTEMS
 OTHER THAN THOSE REQUIRED AS A PART OF THE EMERGENCY
 EGRESS SYSTEM AND THOSE THAT SERVICE THE STAIRWAY ARE
 ALLOWED. THERE IS ALSO A CONCERN THAT A DOUBLE DOOR
 THAT OPENS DIRECTLY TO THE PARKING GARAGE. PLEASE
 PROVIDE A NARRATIVE THAT EXPLAINS THE RATIONALE AND
 INTENTIONS FOR THE EXIT STAIRS THAT HAVE THIS DESIGN.
 FBC 1009 THE1022.8 FBC[B] DISCHARGE IDENTIFICATION. AN
 INTERIOR EXIT STAIRWAY AND RAMP SHALL NOT CONTINUE
 BELOW ITS LEVEL OF EXIT DISCHARGE UNLESS AN APPROVED
 BARRIER IS PROVIDED AT THE LEVEL OF EXIT DISCHARGE TO
 PREVENT PERSONS FROM UNINTENTIONALLY CONTINUING INTO
 LEVELS BELOW. DIRECTIONAL EXIT SIGNS SHALL BE PROVIDED
 AS SPECIFIED IN SECTION 1011.
 -IF STAIRWAY 4 AT 2 ND LEVEL TRANSFERS TO STAIRWAY 11
 THAN 1022.8 APPLIES.
  
 30) NOT RESOLVED. ADD NOTES TO PAGE 10.001 SHEET FR.001
 THAT SPECIFY THAT A MINIMUM OF TWO RISERS WILL BE
 PROVIDED AND THAT EACH RISER SHALL SUPPLY SPRINKLERS ON
 ALTERNATE FLOORS. 403.3.1 FBC[B]NUMBER OF SPRINKLER
 RISERS AND SYSTEM DESIGN. EACH SPRINKLER SYSTEM ZONE IN
 BUILDINGS THAT ARE MORE THAN 420 FEET (128 000 MM) IN
 BUILDING HEIGHT SHALL BE SUPPLIED BY NO FEWER THAN TWO
 RISERS. EACH RISER SHALL SUPPLY SPRINKLERS ON ALTERNATE
 FLOORS. IF MORE THAN TWO RISERS ARE PROVIDED FOR A
 ZONE, SPRINKLERS ON ADJACENT FLOORS SHALL NOT BE
 SUPPLIED FROM THE SAME RISER.
 -PLEASE SEE HOW THIS APPLIES TO OFFICE TOWER ONLY AND
 UPDATE FS DRAWINGS AS APPLICABLE.
  
 NEW COMMENTS:
  
 31) THERE ARE SOME SHEETS THAT ARE DUPLICATED AND THEY
 ARE NOT LISTED AS PREVIOUS VERSIONS OF THE SHEET. I AM
 NOT SURE WHY THIS HAPPENED. PERHAPS THEY WERE NAMED
 DIFFERENTLY WHEN RESUBMITTING. PLEASE REMOVE THE
 DUPLICATED SHEETS THAT ARE NOT VERSION-ED. CONTACT THE
 PERMIT LIBRARIAN IF YOU REQUIRE ASSISTANCE. FBC
 AMENDMENTS 107
  
 32) SHOW COMPLIANCE WITH FBC 403.4.5 EMERGENCY
 RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN
 ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE. THIS
 TYPICALLY REQUIRES A BI-DIRECTIONAL ANTENNA (BDA
 SYSTEM) OR SOME OTHER APPROVED METHOD.
  
 33) NOTE #4 ON SHEET ALS1.100 IS APPARENTLY FOR ANOTHER
 PROJECT. IT SPECIFIES OCEAN DRIVE AND HEATHER DRIVE AS
 EMERGENCY STAGING AREAS. PLEASE CORRECT. FBC AMENDMENTS
 107.2.1
  
 34) ON PAGE 04.016 - ALS1.116, THE RESIDENTIAL ELEVATOR
 MACHINE ROOM LIFE SAFETY PLAN IS NOT CLEAR. IT APPEARS
 THAT THE PATH OF TRAVEL IS GOING THROUGH WALLS. PLEASE
 CLARIFY. FBC AMENDMENTS 107.2.1
  
 35) ON PAGE 04.024 -ALS1.109, SHOW THE TOTAL OCCUPANT
 LOAD OF THE TERRACE AND PICKLE BALL COURTS, THE LOADS
 AT EACH EXIT DOOR AND THE COMBINED LOADS AT THE HOTEL
 AND RESIDENT EXIT STAIRWAYS. FBC 1004
  
 36) ON SHEET A7.700 THERE APPEARS TO BE A WALL SHOWN IN
 THE CENTER OF THE SCREEN ROOM THAT IS RUNNING THROUGH
 SOME OF THE SEATING. PLEASE CLARIFY. FBC 107.2.1
  
 37) ON SHEET A0.001, GENERAL NOTES 6-10 ARE MISSING.
 PLEASE CLARIFY. FBC AMENDMENTS 107.2.1
  
 38) ALSO ON SHEET A0.001, GENERAL NOTE 15 SHOULD
 REFERENCE ASCE 7-10, RATHER THAN ASCE 7-88. FBC CHAPTER
 35.
  
 39) FBC ACCESSIBILITY 505.10.3 REQUIRES THE HANDRAIL
 EXTENSIONS AT THE BOTTOM OF STAIRS TO EXTEND AT THE
 SLOPE OF THE STAIRFLIGHT FOR THE LENGTH OF A STAIR
 TREAD BEFORE RETURNING TO THE WALL, FLOOR OR POST.
  
 40) THE STAIR DETAIL DRAWINGS THAT START ON PG
 03.208-A5.101 APPEAR TO HAVE SOME ISSUES. PLEASE REVIEW
 THE MINIMUM 44" STAIRWAY WIDTH REQUIRED BY FBC 1009.4.
 THE 3'-8" RADIUS AT THE STAIR LANDINGS IN SOME OF THE
 DETAILS ARE INCORRECT.
  
 41) ON PAGE 04.002 - ALS1.101, EXIT PASSAGEWAY 0158 IS
 SHOWN WITH A ONE HOUR FIRE RATED WALL AND A 45 MINUTE
 FIRE RATED DOOR. FBC 1023 REQUIRES EXIT PASSAGEWAY
 ENCLOSURES TO HAVE WALLS, FLOORS AND CEILINGS OF NOT
 LESS THAN THAT REQUIRED FOR ANY CONNECTING INTERIOR
 EXIT STAIRWAY OR RAMP. SINCE THE CONNECTING STAIRWAY
 HAS A TWO HOUR FIRE RATING, THIS PASSAGEWAY IS ALSO
 REQUIRED TO HAVE A TWO HOUR FIRE RATING AND A 90 MINUTE
 FIRE RATED DOOR.
  
 42) THE BUILDING OFFICIAL HAS DETERMINED THAT WHEN CAR
 CHARGING STATIONS ARE PROVIDED, AT LEAST ONE ACCESSIBLE
 EV CHARGING STATION IS TO BE PROVIDED FOR EVERY 25
 TOTAL EV CHARGING STATIONS. THE ACCESSIBLE EV CHARGING
 STATIONS CAN BE LOCATED WITH THE OTHERS.
  
 43) I DID NOT SEE THE DETAILS/ELEVATIONS OF BUILT-IN
 ITEMS IN THE COMMON USE AREAS, SUCH AS RECEPTION DESKS,
 SERVICE COUNTERS, BREAK ROOM KITCHENS, ETC. THAT ARE
 REQUIRED TO BE ACCESSIBLE PER FBC ACCESSIBILITY
 CHAPTERS 8 AND 9. PLEASE INDICATE SHEETS THEY ARE ON OR
 PROVIDE SHEETS WITH DETAILS AND ELEVATIONS FOR THESE
 ITEMS.
  
 44) NOTE: ADDITIONAL COMMENTS MAY RESULT FROM THE
 RESPONSES TO THESE PLAN REVIEW COMMENTS.
  
 -PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW EACH
 COMMENT IS BEING ADDRESSED.
 -FEEL FREE TO CONTACT ME AT 561-805-6714 (M-F 8-5) TO
 DISCUSS COMMENTS, OR E-MAIL ANYTIME [email protected]
  
 NOTE: SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES)
 ARE REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS AND SPAS
 GENERATORS
 ALL OTHER ITEMS OTHER THAN BMEP
  
  
  
  
  
  