| Plan Review Notes For Permit 18100540 |
| Permit Number |
18100540 |
|
| Review Stop |
SIGNATURE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-02-21 07:49:47 | PLUMBING SHEETS ARE NOT ELECTRONICALLY SIGNED AND | | | SEALED PER FL. ADMIN. CODE RULE 61G15--23.004, | | | 61G15-23.005. T.LARGE | | 2020-02-10 18:05:44 | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | **REVISED 12/15/20, DOCUSIGN OK PER FBPE EMAIL FROM | | | W.ANDERSON** | | | | | | 1. CIVIL, ARCH & STRUCTURAL PAGES SPOT CHECKED; OK. | | | | | | 2. COMMENT REMOVED PER FBPE EMAIL | | | | | | 3. COMMENT REMOVED PER FBPE EMAIL | | | | | | 4. FS471, IT IS NOT CLEAR WHO PREPARED THE STAIR | | | PRESSURIZATION RATIONAL ANALYSIS (SUPPORTING | | | DOCUMENTS). THERE IS NO TITLE BLOCK AND THE DOCUMENT IS | | | NOT SIGNED AND SEALED. THIS DOCUMENT SHOULD BE REVIEWED | | | BY DESIGNER OF RECORD. | | | | | | |
|