| Plan Review Notes For Permit 18100540 |
| Permit Number |
18100540 |
|
| Review Stop |
P-IRRIGATE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-03-28 04:45:45 | 1) SHT. LIR5-000 SHOWS A PRESSURE VACUUM BREAKER TYPE | | | BACKFLOW PREVENTION DEVICE FOR THE IRRIGATION SYSTEM. | | | THIS TYPE OF DEVICE IS NOT APPROVED TO BE INSTALLED ON | | | A COMMERCIAL IRRIGATION SYSTEM PER THE CITY OF WEST | | | PALM BEACH CROSS CONNECTION CONTROL MANUAL. A REDUCED | | | PRESSURE ZONE VALVE IS THE MINIMUM REQUIRED PROTECTION | | | ON THIS SYSTEM. A SEPARATE PERMIT IS REQUIRED FOR THE | | | INSTALLATION OF THIS DEVICE. THE DEVICE MUST BE LEAD | | | FREE AND BE LISTED ON THE UNIVERSITY OF SOUTHERN | | | CALIFORNIA'S FOUNDATION FOR CROSS CONNECTION CONTROL | | | LIST OF APPROVED DEVICES. THE DEVICE MUST BE TESTED AND | | | CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES | | | DEPARTMENT WHEN IT IS INSTALLED PER THE CITY OF WEST | | | PALM BEACH CROSS CONNECTION CONTROL MANUAL. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|