Plan Review Notes
Plan Review Notes For Permit 18100540
Permit Number 18100540
Review Stop P-IRRIGATE
Sequence Number 2
Notes
Date Text
2020-03-28 04:45:451) SHT. LIR5-000 SHOWS A PRESSURE VACUUM BREAKER TYPE
 BACKFLOW PREVENTION DEVICE FOR THE IRRIGATION SYSTEM.
 THIS TYPE OF DEVICE IS NOT APPROVED TO BE INSTALLED ON
 A COMMERCIAL IRRIGATION SYSTEM PER THE CITY OF WEST
 PALM BEACH CROSS CONNECTION CONTROL MANUAL. A REDUCED
 PRESSURE ZONE VALVE IS THE MINIMUM REQUIRED PROTECTION
 ON THIS SYSTEM. A SEPARATE PERMIT IS REQUIRED FOR THE
 INSTALLATION OF THIS DEVICE. THE DEVICE MUST BE LEAD
 FREE AND BE LISTED ON THE UNIVERSITY OF SOUTHERN
 CALIFORNIA'S FOUNDATION FOR CROSS CONNECTION CONTROL
 LIST OF APPROVED DEVICES. THE DEVICE MUST BE TESTED AND
 CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES
 DEPARTMENT WHEN IT IS INSTALLED PER THE CITY OF WEST
 PALM BEACH CROSS CONNECTION CONTROL MANUAL.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  