| Plan Review Notes For Permit 18100540 |
| Permit Number |
18100540 |
|
| Review Stop |
P-GREASE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-03-28 05:16:23 | 1) SHOW THE CAPACITY OF THE GREASE INTERCEPTORS ON THE | | | CIVIL AND PLUMBING SHEETS. WPB AMEND TO FBC SEC. | | | 107.2.1. | | | 2) THE PLUMBING SPECIFICATIONS SECTION 22 1323 - PART 2 | | | - SECTION 2.01 (GREASE INTERCEPTOR) : | | | TAG # GT-1 - SECTION C -ACCESSORIES: CALLS OUT A 4-INCH | | | INFLUENT AND EFFLUENT TWO-WAY CLEANOUT, BUT ALSO CALLS | | | OUT A 6-INCH SAMPLING PORT. THIS WOULD CREATE AN | | | OBSTRUCTION TO FLOW AND VIOLATES FBC-PLUMBING | | | SEC.706.2. THIS SECTION ALSO CALLS OUT A SCHIER | | | INTERCEPTOR WITH 6-INCH INLET AND OUTLET. CLARIFY. | | | 3) THE INSTALLATION GUIDE/MANUAL FOR THE GREASE | | | INTERCEPTORS SHALL BE ONSITE FOR INSPECTION. | | | FBC-PLUMBING SEC. 1003.3.4. FACTORY SIZING CALCULATIONS | | | SHALL BE SUBMITTED FOR REVIEW. FBC-PLUMBING SEC.1003.2, | | | 1003.3.4. | | | 4) A SEPARATE PERMIT IS REQUIRED FOR THE GREASE | | | INTERCEPTORS. PLACE A NOTE ON DRAWING C.06 AND THE | | | PLUMBING DRAWINGS. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|