Plan Review Notes
Plan Review Notes For Permit 18100540
Permit Number 18100540
Review Stop P-GREASE
Sequence Number 2
Notes
Date Text
2020-03-28 05:16:231) SHOW THE CAPACITY OF THE GREASE INTERCEPTORS ON THE
 CIVIL AND PLUMBING SHEETS. WPB AMEND TO FBC SEC.
 107.2.1.
 2) THE PLUMBING SPECIFICATIONS SECTION 22 1323 - PART 2
 - SECTION 2.01 (GREASE INTERCEPTOR) :
 TAG # GT-1 - SECTION C -ACCESSORIES: CALLS OUT A 4-INCH
 INFLUENT AND EFFLUENT TWO-WAY CLEANOUT, BUT ALSO CALLS
 OUT A 6-INCH SAMPLING PORT. THIS WOULD CREATE AN
 OBSTRUCTION TO FLOW AND VIOLATES FBC-PLUMBING
 SEC.706.2. THIS SECTION ALSO CALLS OUT A SCHIER
 INTERCEPTOR WITH 6-INCH INLET AND OUTLET. CLARIFY.
 3) THE INSTALLATION GUIDE/MANUAL FOR THE GREASE
 INTERCEPTORS SHALL BE ONSITE FOR INSPECTION.
 FBC-PLUMBING SEC. 1003.3.4. FACTORY SIZING CALCULATIONS
 SHALL BE SUBMITTED FOR REVIEW. FBC-PLUMBING SEC.1003.2,
 1003.3.4.
 4) A SEPARATE PERMIT IS REQUIRED FOR THE GREASE
 INTERCEPTORS. PLACE A NOTE ON DRAWING C.06 AND THE
 PLUMBING DRAWINGS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  