| 2020-03-22 04:50:20 | STEP ADDED BY MISTAKE. |
| 2020-03-22 04:49:29 | THE FOLLOWING COMMENTS ARE FROM THE PLUMBING PLAN |
| | REVIEW THAT WAS DONE ON 4/9/2019 THAT HAVE NOT BEEN |
| | PROPERLY ADDRESSED: |
| | PLUMBING: |
| | COMMENT # 2 - PLACE A NOTE ON THE PLANS THAT THE |
| | RESIDENTIAL TOWER UNITS AND THE COMMON AREAS SHALL |
| | COMPLY WITH THE FAIR HOUSING ACT REQUIREMENTS AND ANSI |
| | A117.1 - 1986. THE NOTE THAT WAS PLACED ON THE PLAN |
| | REFERS TO THE FLORIDA BUILDING CODE ACCESSIBILITY 2014. |
| | 2ND REQUEST. |
| | COMMENT #32 -ON THE PLUMBING SHEETS, LABEL AND TAG ALL |
| | RISERS ON ALL FLOOR PLANS. THERE ARE NUMEROUS RISERS |
| | THAT HAVE NO LABELS OR TAGS AND THERE ARE OTHERS THAT |
| | HAVE INCOMPLETE INFORMATION ( RISERS ARE LABELED WITH |
| | NO TAG OR TAGGED WITH NO LABEL). WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | COMMENT #35 - THE PLANS SHOW AIR ADMITTANCE VALVES |
| | INSTALLED ON SOME OF THE KITCHEN SINKS.WHERE THE |
| | HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR BRANCH |
| | INTERVALS FROM THE TOP OF THE STACK, THE HORIZONTAL |
| | BRANCH SHALL BE PROVIDED WITH A RELIEF VENT THAT SHALL |
| | CONNECT TO A VENT STACK OR STACK VENT , OR EXTEND |
| | OUTDOORS TO THE OPEN AIR. I DID NOT SEE WHERE THIS WAS |
| | DONE. PROVIDE THE SHEET/DRAWING NUMBER(S) THAT WAS |
| | REVISED TO SHOW COMPLIANCE. WPB AMEND. TO FBC SEC. |
| | 107.2.1, 2014 FBC-PLUMBING SEC. 918.3.1. |
| | COMMENT # 38 - PROVIDE A COMPLETE SANITARY ISOMETRIC |
| | DIAGRAM FOR THE UNDERGROUND / UNDERSLAB COLLECTION |
| | SYSTEM. THE DRAWING SUBMITTED ON SHT. P.720 IS |
| | INSUFFICIENT AND DEFICIENT IN THE NECESSARY INFORMATION |
| | TO PERFORM A COMPREHENSIVE REVIEW ON THE DRAWING.WPB |
| | AMEND. TO FBC SEC. 107.3.5.1.3. |
| | COMMENT #40 - PLACE A NOTE ON THE PLANS THAT ACCESS |
| | SHALL BE PROVIDED TO THE WATER SUPPLY SHUTOFF VALVES |
| | FOR THE STACKABLE WASHING MACHINES IN THE RESIDENTIAL |
| | UNITS. 2014 FBC-PLUMBING SEC. 606.3. THE RESPONSE |
| | NARRATIVE FROM THE DESIGN PROFESSIONAL STATES THAT A |
| | NOTE WAS ADDED TO THE PLANS BUT I COULD NOT LOCATE THIS |
| | NOTE. PROVIDE THE SHEET/ DRAWING NUMBER WHERE THE NOTE |
| | CAN BE FOUND. WPB AMEND. TO FBC SEC. 107.2.1. |
| | COMMENT # 42 - THE ENLARGED PLUMBING FLOOR PLANS APPEAR |
| | TO HAVE TAGS ON THE STACKS THAT ARE INCOMPLETE.ENSURE |
| | THAT ALL STACKS/RISERS ARE FULLY LABELED AND TAGGED TO |
| | MATCH THE ISOMETRIC DRAWING AND FULL FLOOR PLANS. |
| | |
| | NEW PLUMBING COMMENTS: |
| | |
| | 1) PLACE A NOTE ON THE PLANS THAT THE BACKFLOW |
| | PREVENTERS WILL REQUIRE A SEPARATE PERMIT AND SHALL |
| | COMPLY WITH 2014 FBC-PLUMBING SEC.605.2.1 AND THE CITY |
| | OF WEST PALM BEACH CROSS-CONNECTION CONTROL MANUAL. |
| | 2) PLACE A NOTE ON THE PLUMBING PLANS THAT A SEPARATE |
| | PERMIT IS REQUIRED FOR THE GREASE INTERCEPTORS. |
| | 3) SHT.A1.602 - DETAIL #1 - WOMEN'S RESTROOM - SHOW THE |
| | INSIDE CLEAR DIMENSIONS (L X W) OF THE HANDICAP |
| | ACCESSIBLE TOILET COMPARTMENTS AND SHOW THE LENGTH OF |
| | THE STANDARD TOILET COMPARTMENTS ON THE PLAN. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 4) SHT. A1.602 - DETAIL #1 - WOMEN'S RESTROOM - SHOW |
| | THE LENGTH AND WIDTH DIMENSIONS OF THE AMBULATORY |
| | ACCESSIBLE TOILET COMPARTMENT ON THE PLANS. COMPLY WITH |
| | 2014 FBC- ACCESS. SECS.604.8.2.1, 604.8.2.2, 604.8.2.3. |
| | 5) SHT. A1.602 - DETAIL #2 - SHOW THE LENGTH OF THE |
| | AMBULATORY ACCESSIBLE TOILET COMPARTMENT IN THE MEN?S |
| | RESTROOM. COMPLY WITH 2014 FBC- ACCESS. SECS.604.8.2.1, |
| | 604.8.2.2, 604.8.2.3. |
| | 6) SHT. L5-711 - DETAIL #6 - SUBMIT ADDITIONAL |
| | DOCUMENTATION FOR THE POOL DECK SHOWER. IF THIS SHOWER |
| | IS IN THE RESIDENTIAL TOWER POOL AREA, IT SHALL COMPLY |
| | WITH ANSI A117.1-1986. IF IT IS IN THE HOTEL, THE |
| | SHOWER CONTROLS SHALL COMPLY WITH THE 2014 FBC-ACCESS. |
| | SEC. 308 FOR REACH RANGES AND SEC.309 FOR OPERABLE |
| | PARTS. |
| | 7) SHT. L5-711 - DETAIL #7- SUBMIT ADDITIONAL |
| | INFORMATION FOR THE WATER FOUNTAIN AT THE POOL DECK. IF |
| | THIS DRINKING FOUNTAIN IS IN THE RESIDENTIAL TOWER POOL |
| | AREA, IT SHALL COMPLY WITH ANSI A117.1-1986. IF IT IS |
| | IN THE HOTEL, THE DRINKING FOUNTAIN SHALL COMPLY WITH |
| | SECS. 211 AND 602 OF THE 2014 FBC-ACCESS. |
| | 8) SHT. A0.101 - HEADING III - CODE DATA - THERE IS AN |
| | ITEM STATING, "SWIMMING POOL TABLE NOT REQUIRED PER FBC |
| | 2014 424.1.6.1". THERE IS NO SUCH CODE SECTION IN THE |
| | 2014 FBC. SECTION. 424 IS FOR CHILDREN'S PLAY |
| | STRUCTURES. CLARIFY. |
| | 9) SHT. A0.101 - APPLICABLE CODES - THE LIST REFERS TO |
| | THE 2010 EDITION OF THE PLUMBING AND MECHANICAL CODES. |
| | THIS PROJECT FALLS UNDER THE 2014 EDITIONS OF THE |
| | PLUMBING AND MECHANICAL CODES. CLARIFY. |
| | 10) SHT. A0.201 - FAIR HOUSING REQUIREMENTS - NOTE #4 |
| | REFERS TO "FBC SECTION 11-4.26.3." THERE IS NO SUCH |
| | CODE SECTION IN THE 2014 EDITION OF THE FBC. CLARIFY. |
| | 11) SHT. A0.202 - FBC- ACC FIXTURE MOUNTING HEIGHTS AND |
| | GRAB BAR MOUNTING REQUIREMENTS - GRAB BARS SHALL BE |
| | MEASURED FROM THE FINISH FLOOR TO THE TOP OF THE |
| | GRIPPING SURFACE PER 2014 FBC-ACCESS. SEC. 609.4. |
| | 12) SHT. A0.202 - FBC -ACC FIXTURE MOUNTING HEIGHTS - |
| | SHOW THE HEIGHT OF THE WATER CLOSET ABOVE THE FINISH |
| | FLOOR. COMPLY WITH 2014 FBC-ACCESS. SEC. 604.4. |
| | 13) SHTS. A0.201, A0.202, & A0.203 - THE DETAILS ARE |
| | LABELED AS ADA. THESE DETAILS ARE TO BE LABELED AS |
| | FLORIDA ACCESSIBILITY CODE. THE ADA IS NOT ENFORCED. |
| | FLORIDA'S ACCESSIBILITY CODE IS A DEPT. OF JUSTICE |
| | CERTIFIED CODE AS BEING SUBSTANTIALLY EQUIVALENT TO THE |
| | ADA STANDARDS. |
| | 14) SHT.A0.203 - SHOWER ELEVATIONS - THE SHOWER SPRAY |
| | UNIT SHALL BE LOCATED NO MORE THAN 48 INCHES ABOVE THE |
| | SHOWER FLOOR. THE ELEVATION SHOWS 5 FEET. 2014 |
| | FBC-ACCESS. SEC. 608.5.2, 608.5.3. |
| | 15) SHT. A1.107 - MEN'S RESTROOM #0757 & WOMEN'S |
| | RESTROOM #0756 - THE DOORS FOR THE AMBULATORY |
| | ACCESSIBLE COMPARTMENTS CANNOT SWING INTO THE MINIMUM |
| | REQUIRED COMPARTMENT AREA. 2014 FBC-ACCESS. |
| | SEC.604.8.2.2. |
| | 16) SHT.A1.107 - MEN'S RESTROOM # 0730 - AN AMBULATORY |
| | ACCESSIBLE TOILET COMPARTMENT IS REQUIRED PER 2014 |
| | FBC-ACCESS. SEC.213.3.1. |
| | 17) SHT. A1.256 - OFFICE TOWER FLOOR PLAN - ROOF LEVEL |
| | - SUBMIT INFORMATION FOR THE CHEMICAL TREATMENT SYSTEM. |
| | SUBMIT MSDS SHEETS FOR THE CHEMICALS BEING USED. SUBMIT |
| | INFORMATION ON THE AMOUNTS OF EACH CHEMICAL BEING USED, |
| | WHERE THEY ARE BEING STORED, THE TYPES OF CONTAINERS |
| | THE CHEMICALS ARE STORED IN, ETC. COMPLIANCE WITH SEC. |
| | 414 & 415 OF THE 2014 FBC MAY BE REQUIRED. |
| | 18) SHT. A1-501 - FAIR HOUSING NOTE #3 REFERS TO SEC. |
| | 11-4.26.3. THERE IS NO SUCH SECTION IN THE FAIR HOUSING |
| | DESIGN MANUAL. CLARIFY. |
| | 19) SHT. A1.503 - DETAIL #2 - HOTEL SUITE 3.1A OR 3.1B |
| | - THE SEAT IN THE SHOWER SHALL COMPLY WITH FBC-ACCESS. |
| | SEC. 610.3. AS SHOWN, IT DOES NOT COMPLY. |
| | 20) SHT. A1.600 - DETAIL #1 - WOMEN'S RESTROOM - THE |
| | PLAN STATES A CLEAR FLOOR SPACE OF 60 INCHES WIDE, BUT |
| | THE PLAN ALSO SHOWS THE WIDTH OF THIS SPACE AS 4 FEET, |
| | 11 INCHES. CLARIFY. COMPLY WITH FBC-ACCESS. |
| | SEC.604.3.1. |
| | 21) SHT.A1.600 - DETAIL #1 - MEN'S RESTROOM - ONE OF |
| | THE URINALS IS SHOWN AS 1 FOOT 2 INCHES FROM A WALL TO |
| | THE CENTERLINE OF THE URINAL. A MINIMUM OF 15 INCHES |
| | FROM A WALL TO THE CENTER OF THE URINAL IS REQUIRED. |
| | FBC-PLUMBING SEC.405.3.1. |
| | 22) SHT.A1.601 - DETAIL # 1 - GROUND LEVEL BATHROOM |
| | #0121 - THE DOOR TO ONE OF THE TOILET ROOMS IS SWINGING |
| | INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY. |
| | FBC-ACCESS. SEC. 603.2.3. SEE EXCEPTIONS. |
| | 23) SHT. A1.601 - THE DOOR IS IN FRONT OF THE WATER |
| | CLOSET. THE WATER CLOSET CANNOT OVERLAP THE REQUIRED |
| | MANEUVERING CLEARANCE FOR THE DOOR INSIDE THE ROOM. |
| | SHOW THE REQUIRED MANEUVERING CLEARANCE FOR THE DOOR IN |
| | ACCORDANCE WITH FBC-ACCESS. 404.2.4. |
| | 24) SHT. A1.600 - GROUND LEVEL BATHROOM #0132- IS THIS |
| | A UNISEX TOILET ROOM OR GENDER SPECIFIC? CLARIFY. |
| | 25) SHT. A1.601 - DETAIL #6 -LEVEL 02 BATHROOM 0240 - |
| | THE BENCHES IN THE MEN'S AND WOMEN'S RESTROOM SHALL |
| | COMPLY WITH FBC-ACCESS. SEC.903. |
| | 26) SHT. A1.601 - DETAIL #6 - LEVEL 02 BATHROOM 0240 - |
| | ONE LAVATORY OUTSIDE OF THE STALL IN THE MEN?S AND |
| | WOMEN?S RESTROOM SHALL COMPLY WITH FBC-ACCESS. SEC.606. |
| | 27) SHT. A1.602 - DETAIL #1 - LEVEL 07 BATHROOM #0759 |
| | -IDENTIFY THE AMBULATORY ACCESSIBLE COMPARTMENT ON THE |
| | PLANS AND SHOW THE GRAB BARS AND PLACE THE DIMENSIONS |
| | OF THE STALL ON THE PLANS. COMPLY WITH FBC-ACCESS. |
| | SEC.604.8.2. |
| | 28) SHOW THE LENGTH OF THE STANDARD TOILET COMPARTMENTS |
| | ON THE PLANS. COMPLY WITH FBC-PLUMBING SEC.405.3.1. |
| | 29) SHT. A1.602 - DETAIL #1 - LEVEL 07 BATHROOM #0759 - |
| | ONE LAVATORY OUTSIDE OF THE STALL IN THE WOMEN?S |
| | RESTROOM SHALL COMPLY WITH FBC-ACCESS. SEC.606. |
| | 30) SHT. A1.602 - DETAIL #2 - LEVEL 8 BATHROOM 08119 - |
| | IDENTIFY THE HANDICAP ACCESSIBLE URINAL. SHOW THE |
| | REQUIRED CLEAR FLOOR SPACE ON THE PLAN. FBC-ACCESS. |
| | SECS. 605, 305. |
| | 31) SHT. A4.300 - DETAIL #2- SUBMIT A DETAIL FOR THE |
| | OVERFLOW SCUPPER FOR THE OPEN DECK ON LEVEL 6 -PODIUM. |
| | SHOW THE DIMENSIONS OF THE SCUPPER. |
| | 31) SHT. A5.110 - DETAILS #7 & #8 - THERE ARE SYMBOLS |
| | IN THESE STAIR ENCLOSURES THAT LOOK LIKE DRAINS. |
| | CLARIFY. COMPLY WITH FBC-BUILDING SEC. 1022.5. |
| | 32) SHT. A1.118 - DETAILS A & B - DRAINS ARE SHOWN IN |
| | THE STAIR ENCLOSURE. THESE ARE NOT PERMITTED PER |
| | FBC-BUILDING SEC. 1022.5. |
| | 33) SANITIZING UNIT FOR THE TRASH CHUTE WILL REQUIRE A |
| | HIGHER DEGREE OF BACKFLOW PROTECTION OTHER THAN A |
| | VACUUM BREAKER PER FBC-PLUMBING SEC.608.1, 608.5. |
| | 34) SHT. A7.501 - PROVIDE DETAILS IF THERE ARE SEPARATE |
| | SHUTOFF VALVES FOR THE TUBS AND IF SO, HOW IS ACCESS |
| | GOING TO BE PROVIDED TO THE SHUTOFF VALVES? |
| | FBC-PLUMBING SEC.606.2. |
| | 35) SHT. A7.502 - DETAIL #2 - THE HIGH POINT AT THE |
| | SHOWER SHALL NOT EXCEED 1/2 OF AN INCH PER FBC-ACCESS. |
| | SEC. 303, 608.7. |
| | 36) SHT. A0.204 - GROUND LEVEL - MERCANTILE - THE |
| | PLUMBING FIXTURE TABLE NOTES 1 DRINKING FOUNTAIN AND 1 |
| | WATER COOLER TO BE PROVIDED. A MINIMUM OF TWO DRINKING |
| | FOUNTAINS ARE REQUIRED PER FBC- PLUMBING SEC. 410.2, |
| | FBC-ACCESS. SEC. 211.2. A SERVICE SINK IS ALSO REQUIRED |
| | PER FBC-PLUMBING TABLE 403.1. THE SUBSTITUTION FOR |
| | WATER COOLERS SHALL COMPLY WITH FBC-PLUMBING SEC.410.3. |
| | 37).37) WHERE ONE DRINKING FOUNTAIN IS LISTED AS BEING |
| | REQUIRED, A MINIMUM OF TWO DRINKING FOUNTAINS SHALL BE |
| | PROVIDED IN ACCORDANCE WITH FBC-PLUMBING SEC.410.2 AND |
| | FBC-ACCESS. SEC. 211.2. |
| | 38) 8TH LEVEL AMENITIES - ASSEMBLY-2-BAR- PROVIDE THE |
| | OCCUPANT LOAD AND FIXTURE REQUIREMENTS FOR THIS AREA. |
| | THE PLAN NOTES "PENDING" CLARIFY. |
| | 39) THE SUBSTITUTION FOR WATER COOLERS SHALL COMPLY |
| | WITH FBC-PLUMBING SEC. 410.3. |
| | 40) THERE IS A FOOTNOTE AT THE BOTTOM OF THE PLUMBING |
| | FIXTURE CHART ON SHT. A0.204 THAT REFERS TO FBC SEC. |
| | 403.6 FOR THE EXCEPTION OF SANITARY FACILITIES FOR |
| | PUBLIC SWIMMING POOLS. SECTION 403.6 OF THE |
| | 2014FBC-BUILDING REFERS TO ELEVATORS IN HIGH RISE |
| | BUILDINGS. THE CORRECT CODE SECTION IS 454.1.6 |
| | EXCEPTION. PLEASE EXPLAIN HOW ALL THE LIVING UNITS CAN |
| | BE WITHIN A 200 FEET HORIZONTAL RADIUS OF THE NEAREST |
| | WATER'S EDGE. |
| | 41) SHT. A1.269 A - THE COVERED DWELLING UNITS THAT |
| | HAVE DOUBLE BASINS SHALL HAVE THE CLEAR FLOOR SPACE |
| | CENTERED ON ONE OF THE BASINS PER THE FAIR HOUSING |
| | DESIGN MANUAL. |
| | 42) SHT. A1.502A - THIS SHEET HAS FAIR HOUSING NOTES ON |
| | IT. THIS SHEET IS FOR THE HOTEL ROOMS. THE FAIR HOUSING |
| | ACT DOES NOT APPLY. THIS IS THE FBC-ACCESS. DELETE THIS |
| | FAIR HOUSING NOTE FROM THE PLAN. WPB AMEND. TO FBC SEC. |
| | 107.2.1. SEE SHEETS A1.507 AND A1.508 ALSO. |
| | 43) A1.603 - INDICATE ON THE PLANS IN WHICH BUILDING |
| | THESE SANITARY FACILITIES ARE LOCATED WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 44) A1.603 - DETAIL # 1 - LEVEL 07 BATHROOM 0760. - |
| | SHOW THE REQUIRED AMBULATORY ACCESSIBLE COMPARTMENT ON |
| | THE PLANS. SHOW THE GRAB BARS AND ALL DIMENSIONS. |
| | 45) A1.603 - SHOW THE LOCATION AND THE CLEAR FLOOR |
| | SPACE FOR THE ACCESSIBLE URINAL AND THE REQUIRED |
| | HANDICAP LAVATORY OUTSIDE THE TOILET COMPARTMENT. |
| | FBC-ACCESS. SEC.213.3.4, 213.3.3. |
| | 46) SHT. A1.603 - DETAIL # 5 - LEVEL 8 BATHROOM 0835 - |
| | THE DOOR ON THE HANDICAP ACCESSIBLE STALL IS SWINGING |
| | INTO THE COMPARTMENT. DOORS SHALL NOT SWING INTO THE |
| | MINIMUM REQUIRED COMPARTMENT AREA. FBC-ACCESS. SEC. |
| | 604.8.1.2. |
| | 47) SHT. A1.604 - DETAIL #1 - LEVEL 07 BATHROOM 0742 |
| | AND 0741 - THE DOOR OF THE AMBULATORY STALL CANNOT |
| | SWING INTO THE MINIMUM REQUIRED COMPARTMENT AREA. |
| | FBC-ACCESS. SEC 604.8.2.2. |
| | 48) A1.604 - DETAIL #1 - SHOW THE REQUIRED ACCESSIBLE |
| | LAVATORY OUTSIDE THE TOILET COMPARTMENT PER FBC-ACCESS. |
| | SEC.213.3.4 AND SHOW THE REQUIRED CLEAR FLOOR SPACE. |
| | 49) SHT. A1.604 - DETAIL #7 - TWO OF THE TOILET STALLS |
| | SHOW A WIDTH OF 29 INCHES. THE MINIMUM WIDTH IS 30 |
| | INCHES. FBC-PLUMBING SEC.405.3.1. |
| | 50) SHT. A1.604 - DETAIL #7 - SHOW THE REQUIRED |
| | ACCESSIBLE LAVATORY AND CLEAR FLOOR SPACE FOR A |
| | LAVATORY OUTSIDE THE TOILET COMPARTMENT. FBC-ACCESS. |
| | 213.3.4. SHOW THE GRAB BARS FOR THE WATER CLOSET IN THE |
| | HANDICAP ACCESSIBLE COMPARTMENT. |
| | 51) SHT. A1.605 - SHOW THE LOCATION OF THE COMPARTMENT |
| | DOOR ON THE FLOOR PLAN. COMPLY WITH FBC-ACCESS. |
| | SEC.604.8.1.2. |
| | 52) SHT. A1.606 - DETAIL #13 - THE WATER CLOSET SHALL |
| | BE LOCATED 18 INCHES TO THE CENTERLINE FROM THE EDGE OF |
| | THE BATHTUB PER THE FHA DESIGN MANUAL. |
| | 53) DIAPER CHANGING STATIONS ARE REQUIRED IN THE |
| | RESTROOMS SERVING THE POOLS. IDENTIFY THIS ITEM IN THE |
| | RESTROOMS SERVING THE POOLS. FBC-BUILDING SEC. |
| | 454.1.6.1. |
| | 54) SHT. P100 SHOWS A 12-INCH RAINWATER LINE BY COLUMN |
| | #6 BUT THIS LINE IS NOT SHOWN ON SHT. C.03. CLARIFY. |
| | 55) SHT. P.100 - THERE IS A 4-INCH CONDENSATE LINE BY |
| | COLUMN LINE #6, A 6-INCH CONDENSATE LINE BY COLUMN LINE |
| | 8, AND A 4-INCH CONDENSATE LINE BY COLUMN LINE #1 THAT |
| | STATES "FOR CONTINUATION REFER TO CIVIL DRAWINGS." |
| | THESE LINES ARE NOT SHOWN ON THE CIVIL DRAWINGS. REFER |
| | TO THE SPECIFIC CIVIL DRAWING WHERE THESE LINES CAN BE |
| | FOUND OR SUBMIT THE APPLICABLE DRAWINGS IF THEY ARE NOT |
| | IN THIS SUBMITTAL. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 56) SHT. P100 - SHOW THE LOCATION OF THE WATER SERVICE |
| | ON THIS PLAN BY COLUMN LINE #10. WPB AMEND. TO FBC SEC. |
| | 107.2SUBMIT DETAILS FOR THE GAS/OIL SEPARATOR. THE |
| | SEPARATOR SHALL COMPLY WITH FBC-PLUMBING SEC. 1003.4.2. |
| | 57) SUBMIT DETAILS OF THE ELEVATOR SUMP/ SUMP PIPING. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | 58) SHT.P101 - THE PIPING SYSTEM IS EXTREMELY DIFFICULT |
| | TO REVIEW. MOST OF THE PIPING SYSTEMS ARE NOT |
| | IDENTIFIED, PIPELINES HAVE NO CONTINUATION POINTS, ETC. |
| | THE SHEET IS NOT COMPLETE ENOUGH FOR REVIEW. WPB AMEND. |
| | TO FBC SEC. 107.2.1. |
| | 59) IDENTIFY THE STAIR NUMBERS ON THE PLUMBING SHEETS. |
| | THIS WILL HELP IN DETERMINING THE LOCATION OF PIPE |
| | SYSTEMS ON THE RE-REVIEW. WPB AMEND. TO FBC- SEC. |
| | 107.2.1. |
| | 60) ON THE MAJORITY OF THE PLUMBING DRAWINGS THERE ARE |
| | SYMBOLS INDICATING PIPES GOING VERTICAL BUT THERE ARE |
| | NO PIPES ATTACHED, LINES AND RISERS HAVE NO |
| | IDENTIFICATION TAGS AS TO WHAT THEY ARE, PIPES GOING |
| | NOWHERE, NO CONTINUATION LINES, NUMEROUS SYMBOLS |
| | (CIRCLES) ON THE DRAWINGS WITH NO IDENTIFICATION, PIPE |
| | LINES SO CONGESTED TOGETHER THEY ARE ILLEGIBLE, AND |
| | SECTIONS OF PIPE TO NOWHERE. PLEASE CLEAN THESE |
| | DRAWINGS UP SO A PROPER REVIEW CAN BE DONE. WPB AMEND. |
| | TO FBC SEC. 107.2.1. |
| | 61) SHT. P102C SHOWS A 1-INCH CD LINE FROM A FCU. FROM |
| | WHERE? WHERE DOES IT BEGIN AND TERMINATE? INDICATE ON |
| | THE PLANS. |
| | 62) THE PLUMBING SHEETS SHOULD BE IDENTIFIED AS TO |
| | BEING FOR THE HOTEL/ OFFICE OR THE RESIDENTIAL TOWER. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | 63) PLACE A PROPER KEY PLAN ON THE PLAN SHEETS. THE |
| | SAME KEY PLAN IS ON EVERY SHEET. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 64) SHT. P1.05 - THIS SHEET NEEDS TO BE REPLACED. AS |
| | IS, IT IS NOT REVIEWABLE. |
| | 65) SHT. P1.06 - THE PIPELINES AND PIPE SYMBOLS ARE SO |
| | CONGESTED THIS SHEET CANNOT BE REVIEWED. |
| | 66) SHT. P.223 - THERE ARE GRAY HEART SHAPED DESIGNS ON |
| | THIS SHEET AND OTHER SHEETS THAT ARE MAKING THE REVIEW |
| | DIFFICULT. SUBMIT REVISED SHEETS. |
| | 67) SHT. P.233 - PIPELINES ARE SO CONGESTED AT THE |
| | RESTROOMS THAT THE PLANS CANNOT BE REVIEWED. SUBMIT A |
| | REVISE PLAN THAT IS LEGIBLE. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 68) SHT. P.252 - THERE ARE SYMBOLS FOR PIPES GOING UP |
| | AND NO RISER TAGS, NO IDENTIFICATION, LINES TERMINATING |
| | NOWHERE, NO RISER TAGS. MOST OF THE SUBMITTED PLANS |
| | MIRROR THIS CONDITION AND CANNOT BE PROPERLY REVIEWED. |
| | 69) SHT. P.262 SHOWS A 6-INCH ROOF DRAIN FOR THE |
| | COOLING TOWER BLOWDOWN. COOLING TOWER WATER IS |
| | PROHIBITED FROM DISCHARGING TO THE STORMWATER SYSTEM |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES CHAPTER |
| | 90, ARTICLE III, SEC. 90-126 (B) (5). |
| | 70) THE DOMESTIC WATER RISERS FOR THE RESIDENTIAL UNITS |
| | SHOW INCOMPLETE SECTIONS OF PIPING GOING NOWHERE, PIPE |
| | LINES ARE NOT IDENTIFIED AS TO USE, SOME PLUMBING |
| | FIXTURES ARE NOT IDENTIFIED ON THE RISERS, THE WATER |
| | PIPING FOR SOME OF THE FIXTURES ARE NOT SHOWN ON THE |
| | WATER RISERS. THIS COMMENT IS TYPICAL FOR MOST OF THE |
| | WATER RISERS. EACH RISER SHALL BE CHECKED FOR ACCURACY |
| | AND REVISED AS NECESSARY. WPB AMEND. TO FBC SEC. |
| | 107.2.1, 107.3.5.1.3. |
| | 71) SHT. P.509 - DETAIL #1, #2, #3 SHOWS NPCW TO POOL |
| | AND SPA FILL SYSTEM. WHAT IS THE SOURCE OF THE |
| | NON-POTABLE COLD WATER? NON-POTABLE WATER PIPING SHALL |
| | BE IDENTIFIED IN ACCORDANCE WITH 2014FBC-PLUMBING |
| | SEC.608.8 ? 608.8.10. SUBMIT DETAILS FOR COMPLIANCE. |
| | THIS APPLIES TO ANY OTHER PORTIONS OF THE BUILDINGS |
| | THAT WILL UTILIZE NON-POTABLE WATER. |
| | 72) SHT. P.701 - THE 4-INCH CW-X TO 3-INCH CW-3 OFFICE |
| | TOWER MAIN SHOWS TYPICAL 1 INCH AND 2-INCH BRANCHES OFF |
| | THE MAIN. WHAT DO THESE BRANCHES SUPPLY? IF THEY ARE |
| | FUTURE, THERE SHALL BE A VALVE AND CAP AND DESIGNATED |
| | AS FUTURE. |
| | 73) SHT. P.701 - THERE SHALL BE A FULL-OPEN VALVE AT |
| | THE BASE OF THE 4-INCH CW-X RISER FOR THE OFFICE TOWER |
| | PER FBC-PLUMBING SEC.606.1 (4). |
| | 74) SHT. P.701 - A FULL OPEN VALVE IS REQUIRED ON THE |
| | TOP OF THE HOT WATER RECIRCULATION LINES PER |
| | FBC-PLUMBING SEC. 606.1 (5). |
| | 75) SHT. P.702 - THERE IS A 2 - INCH COLD WATER LINE |
| | LABELED AS CW-1 ON LEVEL 1 THAT TERMINATES TO A TEE |
| | WITH 2 BRANCHES. THERE ARE NO PIPE SIZES ON THESE |
| | BRANCHES OR WHAT THEY SUPPLY. CLARIFY. |
| | 76) SHT. P.702 - THERE ARE BRANCHES OFF THE WATER |
| | RISERS THAT SOME HAVE NO SIZES OR THE AREA THEY SUPPLY. |
| | REFER TO LEVELS 2-8. SUPPLY THE REQUIRED INFO. WPB |
| | AMEND. TO FBC SEC. 107.3.5.1.3. |
| | 77) SHT. P.705 & P.705A - SOME OF THE SANITARY |
| | ISOMETRICS SHOW THE WATER CLOSET AS S-TRAPPED. CLARIFY. |
| | 78) SHT. P.705 - DETAIL #2 - CLARIFY THE VENTING FOR |
| | THE KITCHEN SINK. THE DETAIL IS CONFUSING. CLARIFY. IF |
| | AN AIR ADMITTANCE VALVE IS BEING USED, IT MUST HAVE A |
| | RELIEF IF THE HORIZONTAL BRANCH IS LOCATED MORE THAN |
| | FOUR BRANCH INTERVALS FROM THE TOP OF THE STACK. |
| | FBC-PLUMBING SEC. 918.3.1. |
| | 79) SHT. P.705 - DETAIL #3 - THE WASTE STACK IS LABELED |
| | AS A VENT STACK AND THE VENT STACK IS LABELED AS A |
| | WASTE STACK. CLARIFY. |
| | 80) SHT. P.705 - DETAIL #7 - CLEARLY SHOW THE WATER |
| | CLOSET CONNECTION LAVATORY CONNECTION TO THE STACKS. |
| | THERE IS PIPE MISSING ON THIS RISER. |
| | 80) SHT. P.705 - DETAIL #5 - WHAT ELSE IS CONNECTED TO |
| | THE SANITARY DRAIN? THERE IS NOTHING SHOWN. IS IT A |
| | TUB, SHOWER? CLARIFY. |
| | 81) SHT. P7.06 - DETAILS #1, #2, #3 & #5 - CLEAN UP THE |
| | RISERS. THERE ARE SECTIONS OF PIPE MISSING. THE RISER |
| | IS INCOMPLETE. |
| | 82) THE SANITARY AND VENT RISER FOR THE HOTEL ONLY GOES |
| | UP TO THE LEVEL 7 PODIUM. WHAT ABOUT THE REST OF THE |
| | UPPER FLOORS? SUBMIT A COMPLETE SANITARY VENT AND RISER |
| | SHEET SHOWING ALL FLOORS. WPB AMEND. TO FBC SEC. |
| | 107.2.1, 107.3.5.1.3. |
| | 83) SHTS. P 7.06 (DETAIL #5), P.707 (DETAILS #1-#5), |
| | P.708 (DETAILS #4 & #6) P.709 ? (DETAILS #$ & #6) - |
| | CLARIFY THE PIPING CONNECTIONS TO THE STACK. THE RISERS |
| | ARE CONGESTED AND VERY DIFFICULT TO REVIEW. THERE ARE |
| | SECTIONS OF PIPING TO NOWHERE. RISER TAGS ARE MISSING, |
| | PIPELINES AND SECTIONS OF PIPE ARE MISSING, HOT AND |
| | COLD-WATER LINES NOT IDENTIFIED ON THE RISERS, WATER |
| | PIPING MISSING FOR THE WATER CLOSET ON DETAILS #4 & #6. |
| | 84) SHT. P.707 - DETAILS #1,2,3,4 &5 - RISER TAG |
| | NUMBERS ARE MISSING, IDENTIFICATION ARROWS POINTING TO |
| | NOTHING, STRAY LINES ON THE RISE. CLEAN UP THE RISERS. |
| | SHT. P.709 - DETAIL #4 - RISER IS INCOMPLETE. |
| | 85) SHT. P701A - SUBMIT A PIPING DETAIL OF THE TMV AND |
| | THE PIPING CONNECTED THERETO. THE PIPING SHALL COMPLY |
| | WITH FBC-PLUMBING SEC.607.2.2. |
| | 86) SHT.P.701B - THE VERTICAL 4-INCH LINE CW-X IS SHOWN |
| | AS 4 INCHES ON LEVEL 18 AND ALSO SHOWN AS 3 INCHES ON |
| | LEVEL 19. CLARIFY. |
| | 87) SHT. P702A - THE 6-INCH LINE CW-X IS ALSO SHOWN AS |
| | 3 INCH. CLARIFY, |
| | 88) SHT.P703A - THE RISER TAGS REFER TO SHEETS P.502 |
| | AND P.503. THE RISERS ARE NOT SHOWN ON THESE SHEETS. |
| | CLARIFY. |
| | 89) SHT. P.709A - RISERS SS/2, SS/3, WS/2 - THE WATER |
| | CLOSET, BATHTUB AND SHOWER ARE NOT PROPERLY VENTED. |
| | FBC-PLUMBING SEC. 901.2.1. |
| | 90) SHT. P.710 - DETAILS #1 THROUGH #6 - THERE ARE |
| | WATER LINES MISSING, HOT AND COLD-WATER LINES CALLED |
| | OUT AND NOTHING IS SHOWN, FIXTURES MISSING, PARTIAL |
| | SANITARY LINES SHOWN, THE RISERS ARE INCOMPLETE, |
| | IDENTIFY ALL FIXTURES ON THE WATER RISERS. |
| | 91) SHT. P.711 - DETAILS #1 THROUGH #5 - THERE ARE |
| | WATER LINES MISSING, HOT AND COLD-WATER LINES CALLED |
| | OUT AND NOTHING IS SHOWN, FIXTURES MISSING, PARTIAL |
| | SANITARY LINES SHOWN, THE RISERS ARE INCOMPLETE, |
| | IDENTIFY ALL FIXTURES ON THE WATER RISERS. |
| | 92) SHT.P.712 - THE LAVATORY IS MISSING FROM THE |
| | SANITARY RISER ON DETAIL - "C". |
| | 93) SUBMIT WATER RISER DIAGRAM FOR THE TOILET ROOMS ON |
| | SHT. P.712. WPB AMEND. TO FBC SEC. 107.3.5.1.3. |
| | 94) SHT. P.720 - SUBMIT A COMPLETE UNDER |
| | SLAB/UNDERGROUND SANITARY RISER DIAGRAM FOR REVIEW. ALL |
| | THE RISERS SHALL BE IDENTIFIED BY RISER NUMBER TAGS, |
| | PIPE SIZES SHALL BE SHOWN, FIXTURE UNIT LOADS, SLOPE OF |
| | PIPE, REQUIRED CLEANOUTS, GREASE WASTE PIPING AND ALL |
| | POINTS OF CONNECTION. THE SUBMITTED SHEET P.720 IS |
| | UNACCEPTABLE, SEVERELY DEFICIENT AND CANNOT BE |
| | REVIEWED. WPB AMEND. TO FBC-SEC. 107.3.5.1.3. |
| | 95) SHT. P.730 - SUBMIT A COMPLETE UNDER |
| | SLAB/UNDERGROUND STORM RISER DIAGRAM FOR REVIEW. ALL |
| | THE RISERS SHALL BE IDENTIFIED BY RISER NUMBER TAGS, |
| | PIPE SIZES SHALL BE SHOWN, REQUIRED CLEANOUTS AND ALL |
| | POINTS OF CONNECTION. THE SUBMITTED SHEETT. IS |
| | UNACCEPTABLE AND DEFICIENT. |
| | WPB AMEND. TO FBC-SEC. 107.3.5.1.3. |
| | 96) INDICATE ON THE RAINWATER PLANS THE PITCH OF THE |
| | PIPE USED FOR THE ABOVEGROUND HORIZONTAL STORM DRAIN |
| | PIPING AND THE RAINFALL RATE USED IN THE DESIGN OF THE |
| | STORMWATER SYSTEM. FBC-PLUMBING SEC.1106.1. |
| | 97) SHT. P.732 - DETAIL #2 - THE RAINWATER RISER IS |
| | INCOMPLETE. THERE ARE LINES MISSING AND CONNECTION |
| | POINTS MISSING. |
| | 98) SHT.P.734 - THERE ARE SECTIONS OF THE RISER DIAGRAM |
| | MISSING AND PIPE SIZES MISSING ON SOME OF THE LINES. |
| | PIPING IS NOT IDENTIFIED, PORTIONS OF THE RISER ARE TOO |
| | CONGESTED AND DIFFICULT TO REVIEW, NP CONTINUATION |
| | POINTS .SUBMIT A REVISED SHEET FOR REVIEW. |
| | 99) SHT. P.503A - THERE ARE ARROWS CALLING OUT VENT |
| | PIPES, WASTE STACKS, AND CONDENSATE RISERS AND NOTHING |
| | IS SHOWN. CLARIFY. |
| | 100) SHT. P.505 - THERE IS A RISER TAG DW/P702A |
| | POINTING TO A RISER LOCATION BUT THERE IS NOTHING |
| | THERE. CLARIFY. |
| | 101) CLEANOUTS ARE REQUIRED IN THE BASE OF EACH WASTE |
| | OR SOIL STACK PER FBC-PLUMBING SEC.708.3.4. BUILDING |
| | SEWERS SHALL BE PROVIDE WITH CLEANOUTS EVERY 100 FEET |
| | IN ACCORDANCE WITH FBC-PLUMBING SEC.708.3.2. |
| | 102) SHT. P.511 - DETAIL #1 - ONE OF THE WATER CLOSETS |
| | IS MISSING ON THE SANITARY RISER. |
| | 103) SHT. P.511 - ALL HOSE BIBBS SHALL BE SEPARATELY |
| | VALVED PER FBC-PLUMBING SEC. 606.2 (2). |
| | 104) SHT.P.511 - DETAIL #5 - A LAVATORY IN THE MEN'S |
| | RESTROOM IS MISSING ON THE WATER RISER. |
| | SHT. P.511 - DETAIL #6 - SHOWS VENTS ON THE FLOOR |
| | DRAINS. AS DRAWN, THESE VENTS WILL BE IN THE MIDDLE OF |
| | THE FLOOR OF THE RESTROOM. CLARIFY. |
| | 105) SHT. P.513 - DETAIL #1 - REVISE THE DRAWING TO |
| | CLEARLY SHOW THE BANK OF LAVATORIES IN EACH RESTROOM. |
| | THERE IS AN OVERLAY THAT MAKES IT DIFFICULT TO REVIEW. |
| | THERE IS ALSO A PARTIAL SANITARY DIAGRAM ON THE LEFT |
| | SIDE OF THE PAGE THAT GOES NOWHERE. |
| | 106) SHT. P.513 - THE WATER RISER FOR THE LEVEL 8 |
| | RESTROOM #0822 IS OVERLAYED ONTO THE SANITARY RISER SO |
| | A REVIEW COULD NOT BE DONE. SUBMIT A CLEAN PAGE FOR |
| | REVIEW. |
| | 107) SHT. P.513 - DETAILS #4 & #5 - THE LAYOUT OF THE |
| | FIXTURES ON THE WATER RISER FOR THE LEVEL 7 TOILET |
| | ROOMS #07-58/07-59 DOES NOT MATCH THE LAYOUT ON THE |
| | SANITARY RISER. IT APPEARS THE WATER RISER IS FOR THE |
| | LEVEL 8 TOILET ROOM. CLARIFY. |
| | 108) SHT. P.514 - DETAILS #3 & #1-THE PLAN VIEW SHOWS 4 |
| | WATER CLOSETS IN A ROW AND THE WATER RISER SHOWS 5. |
| | CLARIFY. |
| | 109) ) SHT.P.514 - DETAIL #3 - THE HANDICAP WATER |
| | CLOSET IS NOT SHOWN ON THE WATER RISER. CLARIFY. |
| | 110) SHT. P.514 - DETAIL #5 - SHOW THE CONTINUATION |
| | POINT OF THE 6-INCH SANITARY RISER ON THE PLANS. |
| | 111) SHT. P.514 -DETAIL #5 - THE FLOOR DRAINS ARE NOT |
| | SHOWN ON THE SANITARY ISOMETRIC. CLARIFY. |
| | 112) SHT. P.514 - THERE ARE VENTS SHOWN ON THE FLOOR |
| | DRAINS. AS, DRAWN, THE VENTS WILL BE LOCATED IN THE |
| | MIDDLE OF THE FLOR. CLARIFY. |
| | 113) SHT. P.514 - DETAIL #3 - THERE ARE 5 WATER CLOSETS |
| | IN A ROW SHOWN ON THE WATER RISER AND FOUR ON THE FLOOR |
| | PLAN AND THE ACCESSIBLE WATER CLOSET IN THE MEN?S |
| | RESTROOM IS NOT SHOWN ON THE WATER RISER. CLARIFY. |
| | 114) SHT. P.514 - DETAIL #6 - THE LAVATORY IN THE |
| | HANDICAP ACCESSIBLE TOILET COMPARTMENT IS NOT SHOWN ON |
| | THE SANITARY RISER. CLARIFY. |
| | 115) SHT. P.802 - SHOW PROVISIONS FOR THERMAL EXPANSION |
| | FOR THE HOT WATER SYSTEM. FBC-PLUMBING SEC. 607.3. |
| | 116) SHT.P8.02 - DETAIL #7 REFERS TO DETAIL #3 OF THIS |
| | SAME SHEET FOR WATER HEATER INFO. DETAIL #3 IS |
| | CONDENSATE DRAIN DETAIL. THE CORRECT DETAIL IS # 7. |
| | REVISE THE NOTE. |
| | 117) SHT. P.803 - DETAIL #1 & #2 - THE BACKFLOW |
| | PREVENTION DEVICES SHALL BE LEAD FREE AND BE ON THE |
| | UNIVERSITY OF SOUTHERN CALIFORNIA'S FOUNDATION FOR |
| | CROSS CONNECTION CONTROL LIST OF APPROVED DEVICES. |
| | 118) SHT. P8.03 - DETAIL #9 - SUBMIT DETAILS AS TO HOW |
| | THE WOOD BLOCK IS BEING ATTACHED TO THE ROOF. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 119) SHT. P.803 - DETAILS #1 & #2 - PLACE A NOTE BY THE |
| | BACKFLOW DETAILS THAT A SEPARATE PERMIT IS REQUIRED FOR |
| | THE BACKFLOW PREVENTERS. |
| | 120) SHT. P.804 - DETAIL #3 - THE NOTES ARE BARELY |
| | LEGIBLE. THERE IS AN OVERLAY OF OTHER NOTES. CLARIFY. |
| | WPB AMEND. TO FBC-SEC. 107.2.1. |
| | 121) SHT. P.804 - DETAIL #3 - THE OIL SEPARATOR SHALL |
| | COMPLY WITH FBC-PLUMBING SEC. 1003.4.2, 1003.4.2.1. |
| | 122) SHT. P.510 - DETAIL #6 - THERE IS A LAVATORY |
| | MISSING FROM THE SANITARY RISER IN THE MEN-S RESTROOM |
| | #0121.CLARIFY. |
| | 123) SHT. P.510 - DETAIL #6 - TWO LAVATORIES ARE |
| | MISSING FROM THE SANITARY RISER. CLARIFY. |
| | 124) SHT. P.510 - DETAIL #3 - TOILET ROOMS 01-51 & |
| | 01-52 - THE DRINKING FOUNTAIN IS MISSING ON THE |
| | SANITARY RISER. CLARIFY. |
| | 125) SHT. P.510 - DETAIL #6 SHOWS A FLAT, DRY VENT ON |
| | THE FLOOR DRAIN. COMPLY WITH FBC-PLUMBING SEC.905.3. |
| | 126) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS FOR THE MEMBRANE SYSTEM FOR |
| | THE SHOWERS. THE SYSTEM BEING USED SHALL COMPLY WITH |
| | THE APPLICABLE CODE SECTIONS IN THE FBC-PLUMBING CODE |
| | SECS.417.5, 417.5.2, 417.5.2.5, 417.5.2.6. |
| | 127) THE PLUMBING SPECIFICATIONS SECTION 22 1323 - PART |
| | 2 - SECTION 2.01 (GREASE INTERCEPTOR) :TAG # GT-1 - |
| | SECTION C -ACCESSORIES: CALLS OUT A 4-INCH INFLUENT AND |
| | EFFLUENT TWO-WAY CLEANOUT, BUT ALSO CALLS OUT A 6-INCH |
| | SAMPLING PORT. THIS WOULD CREATE AN OBSTRUCTION TO FLOW |
| | AND VIOLATES FBC-PLUMBING SEC.706.2. THIS SECTION ALSO |
| | CALLS OUT A SCHIER INTERCEPTOR WITH 6-INCH INLET AND |
| | OUTLET. CLARIFY. |
| | 128) SHOW THE CAPACITY OF THE GREASE INTERCEPTORS ON |
| | THE CIVIL AND PLUMBING SHEETS. WPB AMEND TO FBC SEC. |
| | 107.2.1. |
| | 129) SHT. P.802 - DETAIL #4 - A FULL OPEN VALVE SHALL |
| | BE INSTALLED ON THE DISCHARGE SIDE OF THE CHECK VALVE |
| | AND SHALL BE INSTALLED IN THE PUMP / EJECTOR DISCHARGE |
| | PIPING BETWEEN THE PUMP OR EJECTOR AND THE GRAVITY |
| | DRAINAGE SYSTEM PER FBC-PLUMBING 712.2. |
| | 130)) SHT. P.802 - DETAIL #8 SHOWS A 6-INCH TRAP |
| | DISCHARGING INTO A 4-INCH LINE. CLARIFY. |
| | 131) SHT.P.803 - DETAILS #1 & #2 - THE BACKFLOW DEVICES |
| | SHALL BE LEAD FREE AND THE BACKFLOW DEVICES MUST BE ON |
| | THE UNIVERSITY OF SOUTHERN CALIFORNIA'S (USC) LIST OF |
| | APPROVED DEVICES. A SEPARATE PERMIT IS REQUIRED FOR THE |
| | BACKFLOW DEVICES. |
| | 132) RIGID SUPPORT SWAY BRACING SHALL BE PROVIDED AT |
| | CHANGES IN DIRECTION GREATER THAN 45 DEGREES FOR PIPE |
| | SIZES 4 INCHES AND LARGER PER FBC-PLUMBING SEC.308.6. |
| | SUBMIT DETAILS FOR THE BRACING. |
| | 133) FOR PIPE SIZES GREATER THAN 4 INCHES (102 MM), |
| | RESTRAINTS SHALL BE PROVIDED FOR DRAIN PIPES AT ALL |
| | CHANGES IN DIRECTION AND AT ALL CHANGES IN DIAMETER |
| | GREATER THAN TWO PIPE SIZES. BRACES, BLOCKS, RODDING |
| | AND OTHER SUITABLE METHODS AS SPECIFIED BY THE COUPLING |
| | MANUFACTURER SHALL BE UTILIZED. |
| | 134) THE PLUMBING SHEETS DO NOT BEAR THE DIGITAL |
| | SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE PER WPB AMEND. TO FBC SEC.107.3.4, |
| | FL. ADMIN. CODE RULE 61G15-23.004, 61G15-23.005. |
| | 135) THE SUPPLY LINES AND FITTINGS FOR THE RESIDENTIAL |
| | DISHWASHERS SHALL BE INSTALLED SO AS TO PREVENT |
| | BACKFLOW. PLUMBING FIXTURE FITTINGS SHALL PROVIDE |
| | BACKFLOW PROTECTION IN ACCORDANCE WITH ASME |
| | A112.18.1/CSA B125.1.FBC-PLUMBING SEC. 608.2. |
| | 136) SHT. P.803 - DETAIL #3 SHOWS JOINTS UNDER THE SLAB |
| | - PLUMBING SPECIFICATIONS SEC.221110 - PART 2 - 2.02 |
| | STATES THAT "ENTRANCE PIPING TO THE BUILDING TO |
| | TERMINATE ABOVE GRADE." THE DETAIL ON P.803 SHOWS |
| | FLANGED FITTINGS UNDER THE SLAB. CLARIFY. IF THIS |
| | PIPING ARRANGEMENT IS TO REMAIN, SUBMIT DETAILS ON |
| | FITTING RESTRAINTS AND THRUST BLOCK INFORMATION. WPB |
| | AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |