Date Text
2020-03-22 04:50:20STEP ADDED BY MISTAKE.
2020-03-22 04:49:29THE FOLLOWING COMMENTS ARE FROM THE PLUMBING PLAN
 REVIEW THAT WAS DONE ON 4/9/2019 THAT HAVE NOT BEEN
 PROPERLY ADDRESSED:
 PLUMBING:
 COMMENT # 2 - PLACE A NOTE ON THE PLANS THAT THE
 RESIDENTIAL TOWER UNITS AND THE COMMON AREAS SHALL
 COMPLY WITH THE FAIR HOUSING ACT REQUIREMENTS AND ANSI
 A117.1 - 1986. THE NOTE THAT WAS PLACED ON THE PLAN
 REFERS TO THE FLORIDA BUILDING CODE ACCESSIBILITY 2014.
 2ND REQUEST.
 COMMENT #32 -ON THE PLUMBING SHEETS, LABEL AND TAG ALL
 RISERS ON ALL FLOOR PLANS. THERE ARE NUMEROUS RISERS
 THAT HAVE NO LABELS OR TAGS AND THERE ARE OTHERS THAT
 HAVE INCOMPLETE INFORMATION ( RISERS ARE LABELED WITH
 NO TAG OR TAGGED WITH NO LABEL). WPB AMEND. TO FBC SEC.
 107.2.1.
 COMMENT #35 - THE PLANS SHOW AIR ADMITTANCE VALVES
 INSTALLED ON SOME OF THE KITCHEN SINKS.WHERE THE
 HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR BRANCH
 INTERVALS FROM THE TOP OF THE STACK, THE HORIZONTAL
 BRANCH SHALL BE PROVIDED WITH A RELIEF VENT THAT SHALL
 CONNECT TO A VENT STACK OR STACK VENT , OR EXTEND
 OUTDOORS TO THE OPEN AIR. I DID NOT SEE WHERE THIS WAS
 DONE. PROVIDE THE SHEET/DRAWING NUMBER(S) THAT WAS
 REVISED TO SHOW COMPLIANCE. WPB AMEND. TO FBC SEC.
 107.2.1, 2014 FBC-PLUMBING SEC. 918.3.1.
 COMMENT # 38 - PROVIDE A COMPLETE SANITARY ISOMETRIC
 DIAGRAM FOR THE UNDERGROUND / UNDERSLAB COLLECTION
 SYSTEM. THE DRAWING SUBMITTED ON SHT. P.720 IS
 INSUFFICIENT AND DEFICIENT IN THE NECESSARY INFORMATION
 TO PERFORM A COMPREHENSIVE REVIEW ON THE DRAWING.WPB
 AMEND. TO FBC SEC. 107.3.5.1.3.
 COMMENT #40 - PLACE A NOTE ON THE PLANS THAT ACCESS
 SHALL BE PROVIDED TO THE WATER SUPPLY SHUTOFF VALVES
 FOR THE STACKABLE WASHING MACHINES IN THE RESIDENTIAL
 UNITS. 2014 FBC-PLUMBING SEC. 606.3. THE RESPONSE
 NARRATIVE FROM THE DESIGN PROFESSIONAL STATES THAT A
 NOTE WAS ADDED TO THE PLANS BUT I COULD NOT LOCATE THIS
 NOTE. PROVIDE THE SHEET/ DRAWING NUMBER WHERE THE NOTE
 CAN BE FOUND. WPB AMEND. TO FBC SEC. 107.2.1.
 COMMENT # 42 - THE ENLARGED PLUMBING FLOOR PLANS APPEAR
 TO HAVE TAGS ON THE STACKS THAT ARE INCOMPLETE.ENSURE
 THAT ALL STACKS/RISERS ARE FULLY LABELED AND TAGGED TO
 MATCH THE ISOMETRIC DRAWING AND FULL FLOOR PLANS.
  
 NEW PLUMBING COMMENTS:
  
 1) PLACE A NOTE ON THE PLANS THAT THE BACKFLOW
 PREVENTERS WILL REQUIRE A SEPARATE PERMIT AND SHALL
 COMPLY WITH 2014 FBC-PLUMBING SEC.605.2.1 AND THE CITY
 OF WEST PALM BEACH CROSS-CONNECTION CONTROL MANUAL.
 2) PLACE A NOTE ON THE PLUMBING PLANS THAT A SEPARATE
 PERMIT IS REQUIRED FOR THE GREASE INTERCEPTORS.
 3) SHT.A1.602 - DETAIL #1 - WOMEN'S RESTROOM - SHOW THE
 INSIDE CLEAR DIMENSIONS (L X W) OF THE HANDICAP
 ACCESSIBLE TOILET COMPARTMENTS AND SHOW THE LENGTH OF
 THE STANDARD TOILET COMPARTMENTS ON THE PLAN. WPB
 AMEND. TO FBC SEC. 107.2.1.
 4) SHT. A1.602 - DETAIL #1 - WOMEN'S RESTROOM - SHOW
 THE LENGTH AND WIDTH DIMENSIONS OF THE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT ON THE PLANS. COMPLY WITH
 2014 FBC- ACCESS. SECS.604.8.2.1, 604.8.2.2, 604.8.2.3.
 5) SHT. A1.602 - DETAIL #2 - SHOW THE LENGTH OF THE
 AMBULATORY ACCESSIBLE TOILET COMPARTMENT IN THE MEN?S
 RESTROOM. COMPLY WITH 2014 FBC- ACCESS. SECS.604.8.2.1,
 604.8.2.2, 604.8.2.3.
 6) SHT. L5-711 - DETAIL #6 - SUBMIT ADDITIONAL
 DOCUMENTATION FOR THE POOL DECK SHOWER. IF THIS SHOWER
 IS IN THE RESIDENTIAL TOWER POOL AREA, IT SHALL COMPLY
 WITH ANSI A117.1-1986. IF IT IS IN THE HOTEL, THE
 SHOWER CONTROLS SHALL COMPLY WITH THE 2014 FBC-ACCESS.
 SEC. 308 FOR REACH RANGES AND SEC.309 FOR OPERABLE
 PARTS.
 7) SHT. L5-711 - DETAIL #7- SUBMIT ADDITIONAL
 INFORMATION FOR THE WATER FOUNTAIN AT THE POOL DECK. IF
 THIS DRINKING FOUNTAIN IS IN THE RESIDENTIAL TOWER POOL
 AREA, IT SHALL COMPLY WITH ANSI A117.1-1986. IF IT IS
 IN THE HOTEL, THE DRINKING FOUNTAIN SHALL COMPLY WITH
 SECS. 211 AND 602 OF THE 2014 FBC-ACCESS.
 8) SHT. A0.101 - HEADING III - CODE DATA - THERE IS AN
 ITEM STATING, "SWIMMING POOL TABLE NOT REQUIRED PER FBC
 2014 424.1.6.1". THERE IS NO SUCH CODE SECTION IN THE
 2014 FBC. SECTION. 424 IS FOR CHILDREN'S PLAY
 STRUCTURES. CLARIFY.
 9) SHT. A0.101 - APPLICABLE CODES - THE LIST REFERS TO
 THE 2010 EDITION OF THE PLUMBING AND MECHANICAL CODES.
 THIS PROJECT FALLS UNDER THE 2014 EDITIONS OF THE
 PLUMBING AND MECHANICAL CODES. CLARIFY.
 10) SHT. A0.201 - FAIR HOUSING REQUIREMENTS - NOTE #4
 REFERS TO "FBC SECTION 11-4.26.3." THERE IS NO SUCH
 CODE SECTION IN THE 2014 EDITION OF THE FBC. CLARIFY.
 11) SHT. A0.202 - FBC- ACC FIXTURE MOUNTING HEIGHTS AND
 GRAB BAR MOUNTING REQUIREMENTS - GRAB BARS SHALL BE
 MEASURED FROM THE FINISH FLOOR TO THE TOP OF THE
 GRIPPING SURFACE PER 2014 FBC-ACCESS. SEC. 609.4.
 12) SHT. A0.202 - FBC -ACC FIXTURE MOUNTING HEIGHTS -
 SHOW THE HEIGHT OF THE WATER CLOSET ABOVE THE FINISH
 FLOOR. COMPLY WITH 2014 FBC-ACCESS. SEC. 604.4.
 13) SHTS. A0.201, A0.202, & A0.203 - THE DETAILS ARE
 LABELED AS ADA. THESE DETAILS ARE TO BE LABELED AS
 FLORIDA ACCESSIBILITY CODE. THE ADA IS NOT ENFORCED.
 FLORIDA'S ACCESSIBILITY CODE IS A DEPT. OF JUSTICE
 CERTIFIED CODE AS BEING SUBSTANTIALLY EQUIVALENT TO THE
 ADA STANDARDS.
 14) SHT.A0.203 - SHOWER ELEVATIONS - THE SHOWER SPRAY
 UNIT SHALL BE LOCATED NO MORE THAN 48 INCHES ABOVE THE
 SHOWER FLOOR. THE ELEVATION SHOWS 5 FEET. 2014
 FBC-ACCESS. SEC. 608.5.2, 608.5.3.
 15) SHT. A1.107 - MEN'S RESTROOM #0757 & WOMEN'S
 RESTROOM #0756 - THE DOORS FOR THE AMBULATORY
 ACCESSIBLE COMPARTMENTS CANNOT SWING INTO THE MINIMUM
 REQUIRED COMPARTMENT AREA. 2014 FBC-ACCESS.
 SEC.604.8.2.2.
 16) SHT.A1.107 - MEN'S RESTROOM # 0730 - AN AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT IS REQUIRED PER 2014
 FBC-ACCESS. SEC.213.3.1.
 17) SHT. A1.256 - OFFICE TOWER FLOOR PLAN - ROOF LEVEL
 - SUBMIT INFORMATION FOR THE CHEMICAL TREATMENT SYSTEM.
 SUBMIT MSDS SHEETS FOR THE CHEMICALS BEING USED. SUBMIT
 INFORMATION ON THE AMOUNTS OF EACH CHEMICAL BEING USED,
 WHERE THEY ARE BEING STORED, THE TYPES OF CONTAINERS
 THE CHEMICALS ARE STORED IN, ETC. COMPLIANCE WITH SEC.
 414 & 415 OF THE 2014 FBC MAY BE REQUIRED.
 18) SHT. A1-501 - FAIR HOUSING NOTE #3 REFERS TO SEC.
 11-4.26.3. THERE IS NO SUCH SECTION IN THE FAIR HOUSING
 DESIGN MANUAL. CLARIFY.
 19) SHT. A1.503 - DETAIL #2 - HOTEL SUITE 3.1A OR 3.1B
 - THE SEAT IN THE SHOWER SHALL COMPLY WITH FBC-ACCESS.
 SEC. 610.3. AS SHOWN, IT DOES NOT COMPLY.
 20) SHT. A1.600 - DETAIL #1 - WOMEN'S RESTROOM - THE
 PLAN STATES A CLEAR FLOOR SPACE OF 60 INCHES WIDE, BUT
 THE PLAN ALSO SHOWS THE WIDTH OF THIS SPACE AS 4 FEET,
 11 INCHES. CLARIFY. COMPLY WITH FBC-ACCESS.
 SEC.604.3.1.
 21) SHT.A1.600 - DETAIL #1 - MEN'S RESTROOM - ONE OF
 THE URINALS IS SHOWN AS 1 FOOT 2 INCHES FROM A WALL TO
 THE CENTERLINE OF THE URINAL. A MINIMUM OF 15 INCHES
 FROM A WALL TO THE CENTER OF THE URINAL IS REQUIRED.
 FBC-PLUMBING SEC.405.3.1.
 22) SHT.A1.601 - DETAIL # 1 - GROUND LEVEL BATHROOM
 #0121 - THE DOOR TO ONE OF THE TOILET ROOMS IS SWINGING
 INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY.
 FBC-ACCESS. SEC. 603.2.3. SEE EXCEPTIONS.
 23) SHT. A1.601 - THE DOOR IS IN FRONT OF THE WATER
 CLOSET. THE WATER CLOSET CANNOT OVERLAP THE REQUIRED
 MANEUVERING CLEARANCE FOR THE DOOR INSIDE THE ROOM.
 SHOW THE REQUIRED MANEUVERING CLEARANCE FOR THE DOOR IN
 ACCORDANCE WITH FBC-ACCESS. 404.2.4.
 24) SHT. A1.600 - GROUND LEVEL BATHROOM #0132- IS THIS
 A UNISEX TOILET ROOM OR GENDER SPECIFIC? CLARIFY.
 25) SHT. A1.601 - DETAIL #6 -LEVEL 02 BATHROOM 0240 -
 THE BENCHES IN THE MEN'S AND WOMEN'S RESTROOM SHALL
 COMPLY WITH FBC-ACCESS. SEC.903.
 26) SHT. A1.601 - DETAIL #6 - LEVEL 02 BATHROOM 0240 -
 ONE LAVATORY OUTSIDE OF THE STALL IN THE MEN?S AND
 WOMEN?S RESTROOM SHALL COMPLY WITH FBC-ACCESS. SEC.606.
 27) SHT. A1.602 - DETAIL #1 - LEVEL 07 BATHROOM #0759
 -IDENTIFY THE AMBULATORY ACCESSIBLE COMPARTMENT ON THE
 PLANS AND SHOW THE GRAB BARS AND PLACE THE DIMENSIONS
 OF THE STALL ON THE PLANS. COMPLY WITH FBC-ACCESS.
 SEC.604.8.2.
 28) SHOW THE LENGTH OF THE STANDARD TOILET COMPARTMENTS
 ON THE PLANS. COMPLY WITH FBC-PLUMBING SEC.405.3.1.
 29) SHT. A1.602 - DETAIL #1 - LEVEL 07 BATHROOM #0759 -
 ONE LAVATORY OUTSIDE OF THE STALL IN THE WOMEN?S
 RESTROOM SHALL COMPLY WITH FBC-ACCESS. SEC.606.
 30) SHT. A1.602 - DETAIL #2 - LEVEL 8 BATHROOM 08119 -
 IDENTIFY THE HANDICAP ACCESSIBLE URINAL. SHOW THE
 REQUIRED CLEAR FLOOR SPACE ON THE PLAN. FBC-ACCESS.
 SECS. 605, 305.
 31) SHT. A4.300 - DETAIL #2- SUBMIT A DETAIL FOR THE
 OVERFLOW SCUPPER FOR THE OPEN DECK ON LEVEL 6 -PODIUM.
 SHOW THE DIMENSIONS OF THE SCUPPER.
 31) SHT. A5.110 - DETAILS #7 & #8 - THERE ARE SYMBOLS
 IN THESE STAIR ENCLOSURES THAT LOOK LIKE DRAINS.
 CLARIFY. COMPLY WITH FBC-BUILDING SEC. 1022.5.
 32) SHT. A1.118 - DETAILS A & B - DRAINS ARE SHOWN IN
 THE STAIR ENCLOSURE. THESE ARE NOT PERMITTED PER
 FBC-BUILDING SEC. 1022.5.
 33) SANITIZING UNIT FOR THE TRASH CHUTE WILL REQUIRE A
 HIGHER DEGREE OF BACKFLOW PROTECTION OTHER THAN A
 VACUUM BREAKER PER FBC-PLUMBING SEC.608.1, 608.5.
 34) SHT. A7.501 - PROVIDE DETAILS IF THERE ARE SEPARATE
 SHUTOFF VALVES FOR THE TUBS AND IF SO, HOW IS ACCESS
 GOING TO BE PROVIDED TO THE SHUTOFF VALVES?
 FBC-PLUMBING SEC.606.2.
 35) SHT. A7.502 - DETAIL #2 - THE HIGH POINT AT THE
 SHOWER SHALL NOT EXCEED 1/2 OF AN INCH PER FBC-ACCESS.
 SEC. 303, 608.7.
 36) SHT. A0.204 - GROUND LEVEL - MERCANTILE - THE
 PLUMBING FIXTURE TABLE NOTES 1 DRINKING FOUNTAIN AND 1
 WATER COOLER TO BE PROVIDED. A MINIMUM OF TWO DRINKING
 FOUNTAINS ARE REQUIRED PER FBC- PLUMBING SEC. 410.2,
 FBC-ACCESS. SEC. 211.2. A SERVICE SINK IS ALSO REQUIRED
 PER FBC-PLUMBING TABLE 403.1. THE SUBSTITUTION FOR
 WATER COOLERS SHALL COMPLY WITH FBC-PLUMBING SEC.410.3.
 37).37) WHERE ONE DRINKING FOUNTAIN IS LISTED AS BEING
 REQUIRED, A MINIMUM OF TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED IN ACCORDANCE WITH FBC-PLUMBING SEC.410.2 AND
 FBC-ACCESS. SEC. 211.2.
 38) 8TH LEVEL AMENITIES - ASSEMBLY-2-BAR- PROVIDE THE
 OCCUPANT LOAD AND FIXTURE REQUIREMENTS FOR THIS AREA.
 THE PLAN NOTES "PENDING" CLARIFY.
 39) THE SUBSTITUTION FOR WATER COOLERS SHALL COMPLY
 WITH FBC-PLUMBING SEC. 410.3.
 40) THERE IS A FOOTNOTE AT THE BOTTOM OF THE PLUMBING
 FIXTURE CHART ON SHT. A0.204 THAT REFERS TO FBC SEC.
 403.6 FOR THE EXCEPTION OF SANITARY FACILITIES FOR
 PUBLIC SWIMMING POOLS. SECTION 403.6 OF THE
 2014FBC-BUILDING REFERS TO ELEVATORS IN HIGH RISE
 BUILDINGS. THE CORRECT CODE SECTION IS 454.1.6
 EXCEPTION. PLEASE EXPLAIN HOW ALL THE LIVING UNITS CAN
 BE WITHIN A 200 FEET HORIZONTAL RADIUS OF THE NEAREST
 WATER'S EDGE.
 41) SHT. A1.269 A - THE COVERED DWELLING UNITS THAT
 HAVE DOUBLE BASINS SHALL HAVE THE CLEAR FLOOR SPACE
 CENTERED ON ONE OF THE BASINS PER THE FAIR HOUSING
 DESIGN MANUAL.
 42) SHT. A1.502A - THIS SHEET HAS FAIR HOUSING NOTES ON
 IT. THIS SHEET IS FOR THE HOTEL ROOMS. THE FAIR HOUSING
 ACT DOES NOT APPLY. THIS IS THE FBC-ACCESS. DELETE THIS
 FAIR HOUSING NOTE FROM THE PLAN. WPB AMEND. TO FBC SEC.
 107.2.1. SEE SHEETS A1.507 AND A1.508 ALSO.
 43) A1.603 - INDICATE ON THE PLANS IN WHICH BUILDING
 THESE SANITARY FACILITIES ARE LOCATED WPB AMEND. TO FBC
 SEC. 107.2.1.
 44) A1.603 - DETAIL # 1 - LEVEL 07 BATHROOM 0760. -
 SHOW THE REQUIRED AMBULATORY ACCESSIBLE COMPARTMENT ON
 THE PLANS. SHOW THE GRAB BARS AND ALL DIMENSIONS.
 45) A1.603 - SHOW THE LOCATION AND THE CLEAR FLOOR
 SPACE FOR THE ACCESSIBLE URINAL AND THE REQUIRED
 HANDICAP LAVATORY OUTSIDE THE TOILET COMPARTMENT.
 FBC-ACCESS. SEC.213.3.4, 213.3.3.
 46) SHT. A1.603 - DETAIL # 5 - LEVEL 8 BATHROOM 0835 -
 THE DOOR ON THE HANDICAP ACCESSIBLE STALL IS SWINGING
 INTO THE COMPARTMENT. DOORS SHALL NOT SWING INTO THE
 MINIMUM REQUIRED COMPARTMENT AREA. FBC-ACCESS. SEC.
 604.8.1.2.
 47) SHT. A1.604 - DETAIL #1 - LEVEL 07 BATHROOM 0742
 AND 0741 - THE DOOR OF THE AMBULATORY STALL CANNOT
 SWING INTO THE MINIMUM REQUIRED COMPARTMENT AREA.
 FBC-ACCESS. SEC 604.8.2.2.
 48) A1.604 - DETAIL #1 - SHOW THE REQUIRED ACCESSIBLE
 LAVATORY OUTSIDE THE TOILET COMPARTMENT PER FBC-ACCESS.
 SEC.213.3.4 AND SHOW THE REQUIRED CLEAR FLOOR SPACE.
 49) SHT. A1.604 - DETAIL #7 - TWO OF THE TOILET STALLS
 SHOW A WIDTH OF 29 INCHES. THE MINIMUM WIDTH IS 30
 INCHES. FBC-PLUMBING SEC.405.3.1.
 50) SHT. A1.604 - DETAIL #7 - SHOW THE REQUIRED
 ACCESSIBLE LAVATORY AND CLEAR FLOOR SPACE FOR A
 LAVATORY OUTSIDE THE TOILET COMPARTMENT. FBC-ACCESS.
 213.3.4. SHOW THE GRAB BARS FOR THE WATER CLOSET IN THE
 HANDICAP ACCESSIBLE COMPARTMENT.
 51) SHT. A1.605 - SHOW THE LOCATION OF THE COMPARTMENT
 DOOR ON THE FLOOR PLAN. COMPLY WITH FBC-ACCESS.
 SEC.604.8.1.2.
 52) SHT. A1.606 - DETAIL #13 - THE WATER CLOSET SHALL
 BE LOCATED 18 INCHES TO THE CENTERLINE FROM THE EDGE OF
 THE BATHTUB PER THE FHA DESIGN MANUAL.
 53) DIAPER CHANGING STATIONS ARE REQUIRED IN THE
 RESTROOMS SERVING THE POOLS. IDENTIFY THIS ITEM IN THE
 RESTROOMS SERVING THE POOLS. FBC-BUILDING SEC.
 454.1.6.1.
 54) SHT. P100 SHOWS A 12-INCH RAINWATER LINE BY COLUMN
 #6 BUT THIS LINE IS NOT SHOWN ON SHT. C.03. CLARIFY.
 55) SHT. P.100 - THERE IS A 4-INCH CONDENSATE LINE BY
 COLUMN LINE #6, A 6-INCH CONDENSATE LINE BY COLUMN LINE
 8, AND A 4-INCH CONDENSATE LINE BY COLUMN LINE #1 THAT
 STATES "FOR CONTINUATION REFER TO CIVIL DRAWINGS."
 THESE LINES ARE NOT SHOWN ON THE CIVIL DRAWINGS. REFER
 TO THE SPECIFIC CIVIL DRAWING WHERE THESE LINES CAN BE
 FOUND OR SUBMIT THE APPLICABLE DRAWINGS IF THEY ARE NOT
 IN THIS SUBMITTAL. WPB AMEND. TO FBC SEC. 107.2.1.
 56) SHT. P100 - SHOW THE LOCATION OF THE WATER SERVICE
 ON THIS PLAN BY COLUMN LINE #10. WPB AMEND. TO FBC SEC.
 107.2SUBMIT DETAILS FOR THE GAS/OIL SEPARATOR. THE
 SEPARATOR SHALL COMPLY WITH FBC-PLUMBING SEC. 1003.4.2.
 57) SUBMIT DETAILS OF THE ELEVATOR SUMP/ SUMP PIPING.
 WPB AMEND. TO FBC SEC. 107.2.1.
 58) SHT.P101 - THE PIPING SYSTEM IS EXTREMELY DIFFICULT
 TO REVIEW. MOST OF THE PIPING SYSTEMS ARE NOT
 IDENTIFIED, PIPELINES HAVE NO CONTINUATION POINTS, ETC.
 THE SHEET IS NOT COMPLETE ENOUGH FOR REVIEW. WPB AMEND.
 TO FBC SEC. 107.2.1.
 59) IDENTIFY THE STAIR NUMBERS ON THE PLUMBING SHEETS.
 THIS WILL HELP IN DETERMINING THE LOCATION OF PIPE
 SYSTEMS ON THE RE-REVIEW. WPB AMEND. TO FBC- SEC.
 107.2.1.
 60) ON THE MAJORITY OF THE PLUMBING DRAWINGS THERE ARE
 SYMBOLS INDICATING PIPES GOING VERTICAL BUT THERE ARE
 NO PIPES ATTACHED, LINES AND RISERS HAVE NO
 IDENTIFICATION TAGS AS TO WHAT THEY ARE, PIPES GOING
 NOWHERE, NO CONTINUATION LINES, NUMEROUS SYMBOLS
 (CIRCLES) ON THE DRAWINGS WITH NO IDENTIFICATION, PIPE
 LINES SO CONGESTED TOGETHER THEY ARE ILLEGIBLE, AND
 SECTIONS OF PIPE TO NOWHERE. PLEASE CLEAN THESE
 DRAWINGS UP SO A PROPER REVIEW CAN BE DONE. WPB AMEND.
 TO FBC SEC. 107.2.1.
 61) SHT. P102C SHOWS A 1-INCH CD LINE FROM A FCU. FROM
 WHERE? WHERE DOES IT BEGIN AND TERMINATE? INDICATE ON
 THE PLANS.
 62) THE PLUMBING SHEETS SHOULD BE IDENTIFIED AS TO
 BEING FOR THE HOTEL/ OFFICE OR THE RESIDENTIAL TOWER.
 WPB AMEND. TO FBC SEC. 107.2.1.
 63) PLACE A PROPER KEY PLAN ON THE PLAN SHEETS. THE
 SAME KEY PLAN IS ON EVERY SHEET. WPB AMEND. TO FBC SEC.
 107.2.1.
 64) SHT. P1.05 - THIS SHEET NEEDS TO BE REPLACED. AS
 IS, IT IS NOT REVIEWABLE.
 65) SHT. P1.06 - THE PIPELINES AND PIPE SYMBOLS ARE SO
 CONGESTED THIS SHEET CANNOT BE REVIEWED.
 66) SHT. P.223 - THERE ARE GRAY HEART SHAPED DESIGNS ON
 THIS SHEET AND OTHER SHEETS THAT ARE MAKING THE REVIEW
 DIFFICULT. SUBMIT REVISED SHEETS.
 67) SHT. P.233 - PIPELINES ARE SO CONGESTED AT THE
 RESTROOMS THAT THE PLANS CANNOT BE REVIEWED. SUBMIT A
 REVISE PLAN THAT IS LEGIBLE. WPB AMEND. TO FBC SEC.
 107.2.1.
 68) SHT. P.252 - THERE ARE SYMBOLS FOR PIPES GOING UP
 AND NO RISER TAGS, NO IDENTIFICATION, LINES TERMINATING
 NOWHERE, NO RISER TAGS. MOST OF THE SUBMITTED PLANS
 MIRROR THIS CONDITION AND CANNOT BE PROPERLY REVIEWED.
 69) SHT. P.262 SHOWS A 6-INCH ROOF DRAIN FOR THE
 COOLING TOWER BLOWDOWN. COOLING TOWER WATER IS
 PROHIBITED FROM DISCHARGING TO THE STORMWATER SYSTEM
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES CHAPTER
 90, ARTICLE III, SEC. 90-126 (B) (5).
 70) THE DOMESTIC WATER RISERS FOR THE RESIDENTIAL UNITS
 SHOW INCOMPLETE SECTIONS OF PIPING GOING NOWHERE, PIPE
 LINES ARE NOT IDENTIFIED AS TO USE, SOME PLUMBING
 FIXTURES ARE NOT IDENTIFIED ON THE RISERS, THE WATER
 PIPING FOR SOME OF THE FIXTURES ARE NOT SHOWN ON THE
 WATER RISERS. THIS COMMENT IS TYPICAL FOR MOST OF THE
 WATER RISERS. EACH RISER SHALL BE CHECKED FOR ACCURACY
 AND REVISED AS NECESSARY. WPB AMEND. TO FBC SEC.
 107.2.1, 107.3.5.1.3.
 71) SHT. P.509 - DETAIL #1, #2, #3 SHOWS NPCW TO POOL
 AND SPA FILL SYSTEM. WHAT IS THE SOURCE OF THE
 NON-POTABLE COLD WATER? NON-POTABLE WATER PIPING SHALL
 BE IDENTIFIED IN ACCORDANCE WITH 2014FBC-PLUMBING
 SEC.608.8 ? 608.8.10. SUBMIT DETAILS FOR COMPLIANCE.
 THIS APPLIES TO ANY OTHER PORTIONS OF THE BUILDINGS
 THAT WILL UTILIZE NON-POTABLE WATER.
 72) SHT. P.701 - THE 4-INCH CW-X TO 3-INCH CW-3 OFFICE
 TOWER MAIN SHOWS TYPICAL 1 INCH AND 2-INCH BRANCHES OFF
 THE MAIN. WHAT DO THESE BRANCHES SUPPLY? IF THEY ARE
 FUTURE, THERE SHALL BE A VALVE AND CAP AND DESIGNATED
 AS FUTURE.
 73) SHT. P.701 - THERE SHALL BE A FULL-OPEN VALVE AT
 THE BASE OF THE 4-INCH CW-X RISER FOR THE OFFICE TOWER
 PER FBC-PLUMBING SEC.606.1 (4).
 74) SHT. P.701 - A FULL OPEN VALVE IS REQUIRED ON THE
 TOP OF THE HOT WATER RECIRCULATION LINES PER
 FBC-PLUMBING SEC. 606.1 (5).
 75) SHT. P.702 - THERE IS A 2 - INCH COLD WATER LINE
 LABELED AS CW-1 ON LEVEL 1 THAT TERMINATES TO A TEE
 WITH 2 BRANCHES. THERE ARE NO PIPE SIZES ON THESE
 BRANCHES OR WHAT THEY SUPPLY. CLARIFY.
 76) SHT. P.702 - THERE ARE BRANCHES OFF THE WATER
 RISERS THAT SOME HAVE NO SIZES OR THE AREA THEY SUPPLY.
 REFER TO LEVELS 2-8. SUPPLY THE REQUIRED INFO. WPB
 AMEND. TO FBC SEC. 107.3.5.1.3.
 77) SHT. P.705 & P.705A - SOME OF THE SANITARY
 ISOMETRICS SHOW THE WATER CLOSET AS S-TRAPPED. CLARIFY.
 78) SHT. P.705 - DETAIL #2 - CLARIFY THE VENTING FOR
 THE KITCHEN SINK. THE DETAIL IS CONFUSING. CLARIFY. IF
 AN AIR ADMITTANCE VALVE IS BEING USED, IT MUST HAVE A
 RELIEF IF THE HORIZONTAL BRANCH IS LOCATED MORE THAN
 FOUR BRANCH INTERVALS FROM THE TOP OF THE STACK.
 FBC-PLUMBING SEC. 918.3.1.
 79) SHT. P.705 - DETAIL #3 - THE WASTE STACK IS LABELED
 AS A VENT STACK AND THE VENT STACK IS LABELED AS A
 WASTE STACK. CLARIFY.
 80) SHT. P.705 - DETAIL #7 - CLEARLY SHOW THE WATER
 CLOSET CONNECTION LAVATORY CONNECTION TO THE STACKS.
 THERE IS PIPE MISSING ON THIS RISER.
 80) SHT. P.705 - DETAIL #5 - WHAT ELSE IS CONNECTED TO
 THE SANITARY DRAIN? THERE IS NOTHING SHOWN. IS IT A
 TUB, SHOWER? CLARIFY.
 81) SHT. P7.06 - DETAILS #1, #2, #3 & #5 - CLEAN UP THE
 RISERS. THERE ARE SECTIONS OF PIPE MISSING. THE RISER
 IS INCOMPLETE.
 82) THE SANITARY AND VENT RISER FOR THE HOTEL ONLY GOES
 UP TO THE LEVEL 7 PODIUM. WHAT ABOUT THE REST OF THE
 UPPER FLOORS? SUBMIT A COMPLETE SANITARY VENT AND RISER
 SHEET SHOWING ALL FLOORS. WPB AMEND. TO FBC SEC.
 107.2.1, 107.3.5.1.3.
 83) SHTS. P 7.06 (DETAIL #5), P.707 (DETAILS #1-#5),
 P.708 (DETAILS #4 & #6) P.709 ? (DETAILS #$ & #6) -
 CLARIFY THE PIPING CONNECTIONS TO THE STACK. THE RISERS
 ARE CONGESTED AND VERY DIFFICULT TO REVIEW. THERE ARE
 SECTIONS OF PIPING TO NOWHERE. RISER TAGS ARE MISSING,
 PIPELINES AND SECTIONS OF PIPE ARE MISSING, HOT AND
 COLD-WATER LINES NOT IDENTIFIED ON THE RISERS, WATER
 PIPING MISSING FOR THE WATER CLOSET ON DETAILS #4 & #6.
 84) SHT. P.707 - DETAILS #1,2,3,4 &5 - RISER TAG
 NUMBERS ARE MISSING, IDENTIFICATION ARROWS POINTING TO
 NOTHING, STRAY LINES ON THE RISE. CLEAN UP THE RISERS.
 SHT. P.709 - DETAIL #4 - RISER IS INCOMPLETE.
 85) SHT. P701A - SUBMIT A PIPING DETAIL OF THE TMV AND
 THE PIPING CONNECTED THERETO. THE PIPING SHALL COMPLY
 WITH FBC-PLUMBING SEC.607.2.2.
 86) SHT.P.701B - THE VERTICAL 4-INCH LINE CW-X IS SHOWN
 AS 4 INCHES ON LEVEL 18 AND ALSO SHOWN AS 3 INCHES ON
 LEVEL 19. CLARIFY.
 87) SHT. P702A - THE 6-INCH LINE CW-X IS ALSO SHOWN AS
 3 INCH. CLARIFY,
 88) SHT.P703A - THE RISER TAGS REFER TO SHEETS P.502
 AND P.503. THE RISERS ARE NOT SHOWN ON THESE SHEETS.
 CLARIFY.
 89) SHT. P.709A - RISERS SS/2, SS/3, WS/2 - THE WATER
 CLOSET, BATHTUB AND SHOWER ARE NOT PROPERLY VENTED.
 FBC-PLUMBING SEC. 901.2.1.
 90) SHT. P.710 - DETAILS #1 THROUGH #6 - THERE ARE
 WATER LINES MISSING, HOT AND COLD-WATER LINES CALLED
 OUT AND NOTHING IS SHOWN, FIXTURES MISSING, PARTIAL
 SANITARY LINES SHOWN, THE RISERS ARE INCOMPLETE,
 IDENTIFY ALL FIXTURES ON THE WATER RISERS.
 91) SHT. P.711 - DETAILS #1 THROUGH #5 - THERE ARE
 WATER LINES MISSING, HOT AND COLD-WATER LINES CALLED
 OUT AND NOTHING IS SHOWN, FIXTURES MISSING, PARTIAL
 SANITARY LINES SHOWN, THE RISERS ARE INCOMPLETE,
 IDENTIFY ALL FIXTURES ON THE WATER RISERS.
 92) SHT.P.712 - THE LAVATORY IS MISSING FROM THE
 SANITARY RISER ON DETAIL - "C".
 93) SUBMIT WATER RISER DIAGRAM FOR THE TOILET ROOMS ON
 SHT. P.712. WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 94) SHT. P.720 - SUBMIT A COMPLETE UNDER
 SLAB/UNDERGROUND SANITARY RISER DIAGRAM FOR REVIEW. ALL
 THE RISERS SHALL BE IDENTIFIED BY RISER NUMBER TAGS,
 PIPE SIZES SHALL BE SHOWN, FIXTURE UNIT LOADS, SLOPE OF
 PIPE, REQUIRED CLEANOUTS, GREASE WASTE PIPING AND ALL
 POINTS OF CONNECTION. THE SUBMITTED SHEET P.720 IS
 UNACCEPTABLE, SEVERELY DEFICIENT AND CANNOT BE
 REVIEWED. WPB AMEND. TO FBC-SEC. 107.3.5.1.3.
 95) SHT. P.730 - SUBMIT A COMPLETE UNDER
 SLAB/UNDERGROUND STORM RISER DIAGRAM FOR REVIEW. ALL
 THE RISERS SHALL BE IDENTIFIED BY RISER NUMBER TAGS,
 PIPE SIZES SHALL BE SHOWN, REQUIRED CLEANOUTS AND ALL
 POINTS OF CONNECTION. THE SUBMITTED SHEETT. IS
 UNACCEPTABLE AND DEFICIENT.
 WPB AMEND. TO FBC-SEC. 107.3.5.1.3.
 96) INDICATE ON THE RAINWATER PLANS THE PITCH OF THE
 PIPE USED FOR THE ABOVEGROUND HORIZONTAL STORM DRAIN
 PIPING AND THE RAINFALL RATE USED IN THE DESIGN OF THE
 STORMWATER SYSTEM. FBC-PLUMBING SEC.1106.1.
 97) SHT. P.732 - DETAIL #2 - THE RAINWATER RISER IS
 INCOMPLETE. THERE ARE LINES MISSING AND CONNECTION
 POINTS MISSING.
 98) SHT.P.734 - THERE ARE SECTIONS OF THE RISER DIAGRAM
 MISSING AND PIPE SIZES MISSING ON SOME OF THE LINES.
 PIPING IS NOT IDENTIFIED, PORTIONS OF THE RISER ARE TOO
 CONGESTED AND DIFFICULT TO REVIEW, NP CONTINUATION
 POINTS .SUBMIT A REVISED SHEET FOR REVIEW.
 99) SHT. P.503A - THERE ARE ARROWS CALLING OUT VENT
 PIPES, WASTE STACKS, AND CONDENSATE RISERS AND NOTHING
 IS SHOWN. CLARIFY.
 100) SHT. P.505 - THERE IS A RISER TAG DW/P702A
 POINTING TO A RISER LOCATION BUT THERE IS NOTHING
 THERE. CLARIFY.
 101) CLEANOUTS ARE REQUIRED IN THE BASE OF EACH WASTE
 OR SOIL STACK PER FBC-PLUMBING SEC.708.3.4. BUILDING
 SEWERS SHALL BE PROVIDE WITH CLEANOUTS EVERY 100 FEET
 IN ACCORDANCE WITH FBC-PLUMBING SEC.708.3.2.
 102) SHT. P.511 - DETAIL #1 - ONE OF THE WATER CLOSETS
 IS MISSING ON THE SANITARY RISER.
 103) SHT. P.511 - ALL HOSE BIBBS SHALL BE SEPARATELY
 VALVED PER FBC-PLUMBING SEC. 606.2 (2).
 104) SHT.P.511 - DETAIL #5 - A LAVATORY IN THE MEN'S
 RESTROOM IS MISSING ON THE WATER RISER.
 SHT. P.511 - DETAIL #6 - SHOWS VENTS ON THE FLOOR
 DRAINS. AS DRAWN, THESE VENTS WILL BE IN THE MIDDLE OF
 THE FLOOR OF THE RESTROOM. CLARIFY.
 105) SHT. P.513 - DETAIL #1 - REVISE THE DRAWING TO
 CLEARLY SHOW THE BANK OF LAVATORIES IN EACH RESTROOM.
 THERE IS AN OVERLAY THAT MAKES IT DIFFICULT TO REVIEW.
 THERE IS ALSO A PARTIAL SANITARY DIAGRAM ON THE LEFT
 SIDE OF THE PAGE THAT GOES NOWHERE.
 106) SHT. P.513 - THE WATER RISER FOR THE LEVEL 8
 RESTROOM #0822 IS OVERLAYED ONTO THE SANITARY RISER SO
 A REVIEW COULD NOT BE DONE. SUBMIT A CLEAN PAGE FOR
 REVIEW.
 107) SHT. P.513 - DETAILS #4 & #5 - THE LAYOUT OF THE
 FIXTURES ON THE WATER RISER FOR THE LEVEL 7 TOILET
 ROOMS #07-58/07-59 DOES NOT MATCH THE LAYOUT ON THE
 SANITARY RISER. IT APPEARS THE WATER RISER IS FOR THE
 LEVEL 8 TOILET ROOM. CLARIFY.
 108) SHT. P.514 - DETAILS #3 & #1-THE PLAN VIEW SHOWS 4
 WATER CLOSETS IN A ROW AND THE WATER RISER SHOWS 5.
 CLARIFY.
 109) ) SHT.P.514 - DETAIL #3 - THE HANDICAP WATER
 CLOSET IS NOT SHOWN ON THE WATER RISER. CLARIFY.
 110) SHT. P.514 - DETAIL #5 - SHOW THE CONTINUATION
 POINT OF THE 6-INCH SANITARY RISER ON THE PLANS.
 111) SHT. P.514 -DETAIL #5 - THE FLOOR DRAINS ARE NOT
 SHOWN ON THE SANITARY ISOMETRIC. CLARIFY.
 112) SHT. P.514 - THERE ARE VENTS SHOWN ON THE FLOOR
 DRAINS. AS, DRAWN, THE VENTS WILL BE LOCATED IN THE
 MIDDLE OF THE FLOR. CLARIFY.
 113) SHT. P.514 - DETAIL #3 - THERE ARE 5 WATER CLOSETS
 IN A ROW SHOWN ON THE WATER RISER AND FOUR ON THE FLOOR
 PLAN AND THE ACCESSIBLE WATER CLOSET IN THE MEN?S
 RESTROOM IS NOT SHOWN ON THE WATER RISER. CLARIFY.
 114) SHT. P.514 - DETAIL #6 - THE LAVATORY IN THE
 HANDICAP ACCESSIBLE TOILET COMPARTMENT IS NOT SHOWN ON
 THE SANITARY RISER. CLARIFY.
 115) SHT. P.802 - SHOW PROVISIONS FOR THERMAL EXPANSION
 FOR THE HOT WATER SYSTEM. FBC-PLUMBING SEC. 607.3.
 116) SHT.P8.02 - DETAIL #7 REFERS TO DETAIL #3 OF THIS
 SAME SHEET FOR WATER HEATER INFO. DETAIL #3 IS
 CONDENSATE DRAIN DETAIL. THE CORRECT DETAIL IS # 7.
 REVISE THE NOTE.
 117) SHT. P.803 - DETAIL #1 & #2 - THE BACKFLOW
 PREVENTION DEVICES SHALL BE LEAD FREE AND BE ON THE
 UNIVERSITY OF SOUTHERN CALIFORNIA'S FOUNDATION FOR
 CROSS CONNECTION CONTROL LIST OF APPROVED DEVICES.
 118) SHT. P8.03 - DETAIL #9 - SUBMIT DETAILS AS TO HOW
 THE WOOD BLOCK IS BEING ATTACHED TO THE ROOF. WPB
 AMEND. TO FBC SEC. 107.2.1.
 119) SHT. P.803 - DETAILS #1 & #2 - PLACE A NOTE BY THE
 BACKFLOW DETAILS THAT A SEPARATE PERMIT IS REQUIRED FOR
 THE BACKFLOW PREVENTERS.
 120) SHT. P.804 - DETAIL #3 - THE NOTES ARE BARELY
 LEGIBLE. THERE IS AN OVERLAY OF OTHER NOTES. CLARIFY.
 WPB AMEND. TO FBC-SEC. 107.2.1.
 121) SHT. P.804 - DETAIL #3 - THE OIL SEPARATOR SHALL
 COMPLY WITH FBC-PLUMBING SEC. 1003.4.2, 1003.4.2.1.
 122) SHT. P.510 - DETAIL #6 - THERE IS A LAVATORY
 MISSING FROM THE SANITARY RISER IN THE MEN-S RESTROOM
 #0121.CLARIFY.
 123) SHT. P.510 - DETAIL #6 - TWO LAVATORIES ARE
 MISSING FROM THE SANITARY RISER. CLARIFY.
 124) SHT. P.510 - DETAIL #3 - TOILET ROOMS 01-51 &
 01-52 - THE DRINKING FOUNTAIN IS MISSING ON THE
 SANITARY RISER. CLARIFY.
 125) SHT. P.510 - DETAIL #6 SHOWS A FLAT, DRY VENT ON
 THE FLOOR DRAIN. COMPLY WITH FBC-PLUMBING SEC.905.3.
 126) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE MEMBRANE SYSTEM FOR
 THE SHOWERS. THE SYSTEM BEING USED SHALL COMPLY WITH
 THE APPLICABLE CODE SECTIONS IN THE FBC-PLUMBING CODE
 SECS.417.5, 417.5.2, 417.5.2.5, 417.5.2.6.
 127) THE PLUMBING SPECIFICATIONS SECTION 22 1323 - PART
 2 - SECTION 2.01 (GREASE INTERCEPTOR) :TAG # GT-1 -
 SECTION C -ACCESSORIES: CALLS OUT A 4-INCH INFLUENT AND
 EFFLUENT TWO-WAY CLEANOUT, BUT ALSO CALLS OUT A 6-INCH
 SAMPLING PORT. THIS WOULD CREATE AN OBSTRUCTION TO FLOW
 AND VIOLATES FBC-PLUMBING SEC.706.2. THIS SECTION ALSO
 CALLS OUT A SCHIER INTERCEPTOR WITH 6-INCH INLET AND
 OUTLET. CLARIFY.
 128) SHOW THE CAPACITY OF THE GREASE INTERCEPTORS ON
 THE CIVIL AND PLUMBING SHEETS. WPB AMEND TO FBC SEC.
 107.2.1.
 129) SHT. P.802 - DETAIL #4 - A FULL OPEN VALVE SHALL
 BE INSTALLED ON THE DISCHARGE SIDE OF THE CHECK VALVE
 AND SHALL BE INSTALLED IN THE PUMP / EJECTOR DISCHARGE
 PIPING BETWEEN THE PUMP OR EJECTOR AND THE GRAVITY
 DRAINAGE SYSTEM PER FBC-PLUMBING 712.2.
 130)) SHT. P.802 - DETAIL #8 SHOWS A 6-INCH TRAP
 DISCHARGING INTO A 4-INCH LINE. CLARIFY.
 131) SHT.P.803 - DETAILS #1 & #2 - THE BACKFLOW DEVICES
 SHALL BE LEAD FREE AND THE BACKFLOW DEVICES MUST BE ON
 THE UNIVERSITY OF SOUTHERN CALIFORNIA'S (USC) LIST OF
 APPROVED DEVICES. A SEPARATE PERMIT IS REQUIRED FOR THE
 BACKFLOW DEVICES.
 132) RIGID SUPPORT SWAY BRACING SHALL BE PROVIDED AT
 CHANGES IN DIRECTION GREATER THAN 45 DEGREES FOR PIPE
 SIZES 4 INCHES AND LARGER PER FBC-PLUMBING SEC.308.6.
 SUBMIT DETAILS FOR THE BRACING.
 133) FOR PIPE SIZES GREATER THAN 4 INCHES (102 MM),
 RESTRAINTS SHALL BE PROVIDED FOR DRAIN PIPES AT ALL
 CHANGES IN DIRECTION AND AT ALL CHANGES IN DIAMETER
 GREATER THAN TWO PIPE SIZES. BRACES, BLOCKS, RODDING
 AND OTHER SUITABLE METHODS AS SPECIFIED BY THE COUPLING
 MANUFACTURER SHALL BE UTILIZED.
 134) THE PLUMBING SHEETS DO NOT BEAR THE DIGITAL
 SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE PER WPB AMEND. TO FBC SEC.107.3.4,
 FL. ADMIN. CODE RULE 61G15-23.004, 61G15-23.005.
 135) THE SUPPLY LINES AND FITTINGS FOR THE RESIDENTIAL
 DISHWASHERS SHALL BE INSTALLED SO AS TO PREVENT
 BACKFLOW. PLUMBING FIXTURE FITTINGS SHALL PROVIDE
 BACKFLOW PROTECTION IN ACCORDANCE WITH ASME
 A112.18.1/CSA B125.1.FBC-PLUMBING SEC. 608.2.
 136) SHT. P.803 - DETAIL #3 SHOWS JOINTS UNDER THE SLAB
 - PLUMBING SPECIFICATIONS SEC.221110 - PART 2 - 2.02
 STATES THAT "ENTRANCE PIPING TO THE BUILDING TO
 TERMINATE ABOVE GRADE." THE DETAIL ON P.803 SHOWS
 FLANGED FITTINGS UNDER THE SLAB. CLARIFY. IF THIS
 PIPING ARRANGEMENT IS TO REMAIN, SUBMIT DETAILS ON
 FITTING RESTRAINTS AND THRUST BLOCK INFORMATION. WPB
 AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR