| 2020-03-10 18:06:30 | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #18100540 |
| | 550 N QUADRILLE BLVD |
| | 3/2/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2014 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2014 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2014 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2014 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | 1) ENERGYGAUGE COMPLIANCE REPORT PAGE 47: THE COOLING |
| | TOWER MUST MEET THE MINIMUM EFFICIENCY REQUIREMENT |
| | LISTED IN TABLE C403.2.3(8) FBC EC. PLEASE CORRECT THE |
| | N/A CHECKMARK. A) PLEASE NOTE THAT THE PLANS FOR THE |
| | PROPOSED PROJECT ARE BEING DESIGNED IN ACCORDANCE WITH |
| | THE FLORIDA BUILDING CODE- 2014 FIFTH EDITION. AS A |
| | RESULT THE 2017 VERSION OF THE ENERGYGAUGE COMPLIANCE |
| | SOFTWARE CANNOT BE USED. PLEASE SUBMIT THE 2014 |
| | ENERGYGAUGE SOFTWARE VERSION. |
| | |
| | 2) THE STAIR PRESSURIZATION RATIONAL ANALYSIS SHALL BE |
| | ELECTRONICALLY SIGNED AND SEALED BY THE ENGINEER WHO |
| | PREPARED THE DOCUMENT- FL. STATUTE 471.025 AND SECTION |
| | 61G15-23.005 FLORIDA ADMINISTRATIVE CODE. IN ADDITION, |
| | THE ARCHITECT OF RECORD AND THE MECHANICAL ENGINEER OF |
| | RECORD SHALL EACH PROVIDE A REVIEW AND APPROVAL STAMP |
| | ON THE DOCUMENT- SECTION 107.2.1 WPB. PLEASE NOTE THAT |
| | SPECIAL INSPECTION AND COMMISSIONING OF THE SYSTEMS |
| | SHALL BE CONDUCTED IN ACCORDANCE WITH SECTION 909.18.1 |
| | FBC B, AND A FINAL COMMISSIONING REPORT SHALL BE |
| | PROVIDED TO THE CITY OF WEST PALM BEACH BUILDING |
| | DIVISION AND THE WPB FIRE DEPARTMENT AS A CONDITION OF |
| | RECEIVING A FINAL CERTIFICATE OF OCCUPANCY FOR THE |
| | BUILDING- SEE SECTIONS 909.3 AND 909.18.8.1- 909.20 FBC |
| | B. THE ENGINEER OF RECORD AND SMOKE CONTROL ARE ADVISED |
| | TO LOOK AT THE ISSUES LISTED BELOW. |
| | A) MISSING FROM THE REPORT IS A DETAILED NARRATIVE |
| | DESCRIPTION OF HOW THE FIRE ALARM AND PRESSURIZATIONS |
| | SYSTEMS IN THE TWO TOWERS AND PODIUM WILL COORDINATE |
| | AND INTERACT TOGETHER UNDER EMERGENCY ALARM CONDITIONS. |
| | FOR EXAMPLE- WILL ALL THE INTERIOR EXIT STAIRWAYS BE |
| | PRESSURIZED IN THE TOWERS AND THE PODIUM IF AN ALARM |
| | OCCURS IN JUST ONE AREA OF THE BUILDING SUCH AS THE |
| | PODIUM OR ONE OF THE TOWERS, OR WILL JUST THE STAIRWAYS |
| | IN THE AREA OF THE INCIDENT BE PRESSURIZED? |
| | B) STAIR 1 HAS AN EXTENSION AT THE GROUND FLOOR THAT IS |
| | MISLABELED AS A CORRIDOR, AND SHOULD BE LABELED AS AN |
| | EXIT PASSAGEWAY- SECTION 1022.3.1 FBC B. THE PASSAGEWAY |
| | SHALL BE PRESSURIZED IN THE SAME MANNER AS THE |
| | STAIRWAY- SECTION 1022.10.1 FBC B. |
| | C) ITEM 4.2 OF THE REPORT SPECIES SMOKE DETECTION AT |
| | THE ENTRANCE TO THE PRESSURIZED STAIRWELLS, AND DUCT |
| | SMOKE DETECTORS ARE SHOWN ON THE PLANS IN THE |
| | PRESSURIZATION DUCTS AND FAN HOUSINGS. PLEASE NOTE THAT |
| | SECTION 606.2.1 FBC M REQUIRES UL LISTED AND LABELED |
| | DUCT SMOKE DETECTORS IN THE RETURN DUCTS OF AIR |
| | DISTRIBUTION SYSTEMS, BUT NOT IN PRESSURIZATION SUPPLY |
| | DUCTS. PLEASE PROVIDE A WRITTEN SEQUENCE OF OPERATION |
| | FOR THE DETECTORS AND A PRODUCT SUBMITTAL. THE |
| | SUBMITTAL SHALL INDICATE THE DEVICES ARE LISTED AND |
| | LABELED FOR USE IN PRESSURIZATION SYSTEMS- SECTION |
| | 107.2.1 WPB. |
| | D) FIRE WRAPPING AND FLAMEBAR DUCTWORK ARE BEING USED |
| | THROUGHOUT THE BUILDING TO PROVIDE THE REQUIRED 2-HR. |
| | FIRE BARRIER ENCLOSURE FOR THE PRESSURIZATION DUCTS |
| | THAT ARE CONNECTING THE O/A INLETS AND FANS TO THE |
| | STAIRWAYS. 1) FIRE WRAP: PLEASE VERIFY AND ACKNOWLEDGE |
| | IN THE ANALYSIS THAT THE WRAPPING HAS THE REQUIRED UL |
| | LISTING AND LABELING TO PROVIDE THE REQUIRED FIRE |
| | RESISTANCE PER SECTION 703.2.1 FBC B. 2) FLAMEBAR: |
| | PROVIDE A COMPLETE FLAMEBAR DUCTWORK SUBMITTAL PACKAGE |
| | INCLUDING UL LISTED ASSEMBLIES AND JOB-SPECIFIC |
| | INSTALLATION DETAILS- JOINTS, CONNECTIONS, SUPPORTS. |
| | PLEASE NOTE THAT THE MECHANICS ASSEMBLING THE DUCTWORK |
| | SHALL BE CERTIFIED TO DO THE INSTALLATIONS AND THE |
| | CERTS SHALL BE ONSITE AT TIME OF INSPECTION. |
| | |
| | 3) SHEETS M.606 & M.607: PLEASE PROVIDE INDIVIDUAL O/A |
| | CFM TOTALS FOR THE OFFICE TOWER, HOTEL TOWER, AND |
| | RESIDENTIAL TOWER AND PODIUM. |
| | A) INDICATE WHAT THE "K" SYMBOL MEANS THAT IS SHOWN IN |
| | THE ZONE POPULATION COLUMN OF THE SCHEDULES. |
| | B) THE PROVIDED (ACTUAL OUTDOOR AIRFLOW RATE) CFMS IN |
| | MANY OF THE ROOMS AND SPACES SHOWN IN THE TABLES IS |
| | LESS THAN THE REQUIRED CFMS FOR EXAMPLE THE BALLROOM, |
| | PREFUNCTION, CONFERENCE, RESIDENTIAL LOBBY, TENNIS |
| | EVENT, MAIL, FITNESS, HOTEL ELEVATOR LOBBY ETC. PLEASE |
| | CORRECT THE SCHEDULES- TABLE 403.3.1.1 FBC M. |
| | C) PROVIDE VENTILATION CALCULATIONS FOR THE INDOOR |
| | TENNIS COURTS AND THE INDOOR POOL- TABLE 403.3.1.1 FBC |
| | M. |
| | |
| | 4) PLEASE NOTE THAT THE PLANS FOR THE PROPOSED PROJECT |
| | ARE BEING DESIGNED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE- 2014 FIFTH EDITION. AS A RESULT, ALL |
| | PREVIOUS REVIEW COMMENTS REQUIRING DUCT SMOKE DETECTORS |
| | IN THE SUPPLY SYSTEMS OF THE AIR HANDLERS ARE NOT |
| | APPLICABLE. WHERE REQUIRED, THE DUCT SMOKE DETECTORS |
| | SHALL BE INSTALLED IN THE RETURN AIR SYSTEMS. |
| | |
| | PODIUM |
| | |
| | 5) M201, 202, 203, 204, 205: THE REVISED PLANS ARE |
| | MISSING DUCT SIZES, AND LABELS FOR DUCTS, DIFFUSERS |
| | RETURN GRILLS, VAV'S, AHU'S, SENSORS ETC.- SECTION |
| | 107.2.1 WPB. |
| | |
| | 6) M201.A & ALSI.101: THE VESTIBULE AT STAIR #3 IS |
| | NEITHER FIRE-RATED OR VENTILATED- TABLE 1028.1 FBC B |
| | AND TABLE 403.3.1.1 FBC M. |
| | |
| | 7) M201.A: PROVIDE CONSTRUCTION DETAILS FOR THE |
| | FIRE-RATED PRESSURIZATION DUCT ENCLOSURE AT STAIR #3- |
| | SECTION 703.2.1 & 717.2.1 FBC B. |
| | |
| | 8) M201.B: SHOW THE FUTURE TERMINATION LOCATIONS AND |
| | REQUIRED CLEARANCES FOR THE KITCHEN HOOD GREASE EXHAUST |
| | DUCT, AND ALL OTHER KITCHEN EXHAUST DUCTS- SEE SECTION |
| | 506 FBC M. |
| | |
| | 9) M201B: FIRE DAMPERS MISSING AT DUCTS PENETRATING THE |
| | 1-HR FIRE RATED WALLS AT THE RECEIVING, LUGGAGE, |
| | CORRIDOR 0141, OFFICE ROOM WALLS- SECTION 607.5.2 FBC |
| | M. |
| | |
| | 10) M201.C: PROVIDE PRODUCT SUBMITTALS FOR THE DIESEL |
| | FIRE PUMP AND THE PUMP EXHAUST DUCTWORK- SECTIONS 4.2 |
| | AND 11.5.2.5 NFPA 20. PLEASE NOTE THAT THE SUBMITTALS |
| | MAY BE DEFERRED BY REQUEST. A) SHOW THE LOCATION OF THE |
| | PUMP IN THE ROOM AND REFER TO SECTION 11.3.2.4.3 NFPA |
| | 20 FOR EXHAUST REQUIREMENTS FOR RADIATOR-COOLED |
| | ENGINES. A DIRECT DUCT CONNECTION TO THE PUMP VIA A |
| | FLEXIBLE SECTION MAY BE REQUIRED. B) PLEASE ADD NOTES |
| | TO INDICATE THE VENTILATION SYSTEM FOR THE PUMP AS |
| | DESIGNED WILL BE CAPABLE OF MAINTAINING A MAXIMUM |
| | TEMPERATURE OF 120 DEGREES F IN THE ROOM, WILL PROVIDE |
| | ADEQUATE COMBUSTION AIR, AND WILL REMOVE ALL HAZARDOUS |
| | VAPORS- SECTION 11.3.2.1 NFPA 20. PLEASE NOTE THERE IS |
| | NO AC SYSTEM IN THE ROOM. |
| | |
| | 11) M201.C: PROVIDE THE SEQUENCE OF OPERATION FOR THE |
| | GENERATOR FUEL STORAGE TANK ROOM EXHAUST SYSTEM- |
| | SECTION 502.8.1.1 FBC M. |
| | |
| | 12) M.301C & M711- DIESEL FIRE PUMP AND FUEL TANK: A) |
| | PROVIDE FUEL TANK, FILL AND VENT PIPE SPECIFICATIONS, |
| | PIPE SIZING CALCULATIONS, PIPE INSTALLATION DETAILS- |
| | JOINTS AND CONNECTIONS, AND PIPE SUPPORT DETAILS- |
| | SECTION 1302, 1303, 1305 FBC M. B) SHOW THE REMOTE FILL |
| | PIPING LOCATION AND FILL PIPING RUN- SECTION 1305.6 FBC |
| | M. C) INDICATE THE REQUIRED CLEARANCES FOR THE VENT |
| | PIPING TO BUILDING OPENINGS- SECTION 1305.7 FBC M. IT |
| | APPEARS THE LOCATIONS ARE STILL INSIDE THE BUILDING |
| | FOOTPRINT WHICH IS NOT ALLOWED. |
| | |
| | 13) M301.C & M711- GENERATOR FUEL TANK: PROVIDE THE |
| | FILL AND VENT PIPING SPECIFICATIONS, PIPE SIZING |
| | CALCULATIONS, PIPE INSTALLATION DETAILS- JOINTS AND |
| | CONNECTIONS, AND PIPE SUPPORT DETAILS- SECTION 1302, |
| | 1303, 1305 FBC M. B) THE EMERGENCY VENT LINE FROM THE |
| | TANK SHALL TERMINATE OUTSIDE OF THE BUILDING- SECTION |
| | 1305.7 FBC M & SECTION 27.8.2.6 NFPA 30. C) INDICATE |
| | HOW THE LINES WILL BE PROTECTED- SECTION 1305.7 FBC M. |
| | D) INDICATE THE REQUIRED CLEARANCES FOR THE FILL AND |
| | VENT PIPING TO BUILDING OPENINGS- SECTION 1305.7 FBC M. |
| | IT APPEARS THE LOCATIONS ARE STILL INSIDE THE BUILDING |
| | FOOTPRINT WHICH IS NOT ALLOWED. |
| | |
| | 14) M.711: THE LOCATIONS OF THE 3-HR. FIRE-RATED FUEL |
| | LINE SHAFTS THROUGHOUT THE BUILDING ARE NOT SHOWN |
| | CLEARLY AND ACCURATELY ON THE LIFE SAFETY, |
| | ARCHITECTURAL, AND MECHANICAL AIR DISTRIBUTION PLANS. |
| | THE LIFE SAFETY PLANS APPEAR TO SHOW THEM IN THE SAME |
| | SHAFT WITH AN HVAC DUCT WHICH IS NOT ALLOWED. PLEASE |
| | SHOW THE LOCATIONS, NOTE THEM CLEARLY ON THE PLANS, AND |
| | PROVIDE CONSTRUCTION DETAILS FOR THE SHAFT- SECTION |
| | 713.1 FBC B. A) PLEASE EMBOLDEN THE KEY NOTES IN THE |
| | DIAGRAM. |
| | |
| | 15) M201.C: PROVIDE A SUBMITTAL FOR THE 2-HR FIRE RATED |
| | EXHAUST DUCT WRAP. PLEASE NOTE THE WRAP SHALL BE LISTED |
| | AND LABELED FOR USE ON HAZARDOUS EXHAUST DUCTS- SECTION |
| | 510.7.3 FBC M. |
| | |
| | 16) M201.C NOTE #1: THE 3' CLEARANCE TO OPERABLE |
| | OPENINGS IS ALLOWABLE FOR EXHAUST DUCTS SERVING A TYPE |
| | II HOOD ONLY. PLEASE PROVIDE MORE INFORMATION AND |
| | SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE HOOD, |
| | EXHAUST DUCT, AND THE COOKING APPLIANCE- SEE SECTIONS |
| | 506.3.13.3 AND 506.4.2 FBC M. PLEASE NOTE THAT SEPARATE |
| | PERMITS ARE REQUIRED FOR KITCHEN EXHAUST AND FIRE |
| | SUPPRESSION SYSTEMS- SECTION 107.2.1 WPB. |
| | |
| | 17) M201C: CU 5 SHALL BE INSTALLED OUTDOORS IN |
| | ACCORDANCE WITH THE LISTING AND LABELING OF THE |
| | APPLIANCE AND MANUFACTURER'S GUIDELINES- SECTION 304.1 |
| | FBC M. |
| | |
| | 18) M201.C: FIRE DAMPERS MISSING AT THE AHU-13 SUPPLY |
| | AND RETURN DUCT PENETRATIONS- SECTIONS 606.2 AND |
| | 607.6.1 FBC M.22) M202.B: FIRE DAMPER MISSING FOR THE |
| | 8X6 ERU SUPPLY DUCT PENETRATING FIRE-RATED WALL AT THE |
| | FIRE LOBBY. |
| | |
| | 19) M202A AND ALL ENCLOSED GARAGE FLOORS: THE PLANS |
| | SHOW THE GARAGE FANS WILL BE EXHAUSTING THE AIR INTO |
| | THE SPACE BETWEEN THE EXTERIOR WALLS AND THE GREEN |
| | SCREEN. PLEASE VERIFY THAT THE EXHAUST AIR WILL BE ABLE |
| | TO FLOW FREELY OUT OF THE BUILDING AND NOT BE |
| | OBSTRUCTED BY THE SCREEN. |
| | |
| | 20) M202.B, C, & D C: NO O/A PROVIDED AT THE ELEVATOR |
| | OR FIRE LOBBIES- TABLE 403.3.1.1 AND SECTION 404.3 FBC |
| | M. |
| | |
| | 21) M202.C: SHOW THE SIZE OF THE SPF/01 PRESSURIZATION |
| | DUCT- SECTION 107.2.1 WPB. |
| | |
| | 22) M202.C: FIRE DAMPER MISSING AT THE AHU-13 SUPPLY |
| | DUCT FLOOR PENETRATION- SECTION 607.6.1 FBC M. |
| | |
| | 23) M202.C & D - M206.C & D: ACCORDING TO THE SCHEDULE |
| | AHU-14 SUPPLYING AIR TO THE RESIDENTIAL UNITS (AND ALL |
| | OTHER AHU'S IN THE SCHEDULE ON SHEET M.602) IS NOT |
| | BEING EQUIPPED WITH A MOTORIZED OUTSIDE AIR DAMPER |
| | (NOTE #8 IN THE SCHEDULE). THE PLAN SHOWS AN ACD FOR |
| | AHU-14, HOWEVER PLEASE NOTE SECTION C403.2.4.4 FBC EC |
| | REQUIRES OUTDOOR AIR SUPPLY DUCTS TO BE EQUIPPED WITH |
| | GRAVITY OR MOTORIZED DAMPERS THAT WILL AUTOMATICALLY |
| | SHUT WHEN THE SYSTEMS OR SPACES ARE NOT IN USE. PROVIDE |
| | DAMPERS FOR EACH DUCT SUPPLYING O/A TO THE VHP'S. |
| | |
| | 24) M202 C & D- M206.C & D, M605, M707: REFER TO |
| | SECTION 504.8 FBC M AND PROVIDE THE FOLLOWING DETAILS |
| | AND INFORMATION CONCERNING THE CLOTHES DRYER EXHAUST |
| | SYSTEMS- TYPE OF DUCTWORK, SEQUENCE OF OPERATION FOR |
| | THE EXHAUST FANS, AND HOW MAKEUP AIR IS BEING PROVIDED. |
| | A) PROVIDE AIR BALANCE CALCULATIONS FOR THE RESIDENTIAL |
| | UNITS THAT INCLUDE THE CLOTHES DRYER AND TOILET EXHAUST |
| | SYSTEMS. |
| | |
| | 25) M203.B, C, & D C: NO O/A PROVIDED AT THE ELEVATOR |
| | OR FIRE LOBBIES- TABLE 403.3.1.1 AND SECTION 404.3 FBC |
| | M. |
| | |
| | 26) M203.B, 204.B, 205.B, 206.B: IT APPEARS THAT |
| | FIRE-WRAPPING IS BEING USED TO CREATE CONTINUOUS |
| | VERTICAL TO HORIZONTAL SHAFTS FOR THE ERU-01 SUPPLY |
| | DUCTS AND THE RETURN/SMOKE PURGE DUCTS. PLEASE PROVIDE |
| | A UL LISTED ASSEMBLY SHOWING THE FIRE WRAPPING USED IN |
| | THIS CONFIGURATION- PLEASE SEE SECTION 703.2.1 FBC B. |
| | |
| | 27) M203.B- M206.B: SECTION C403.2.4.4 FBC EC REQUIRES |
| | OUTDOOR AIR SUPPLY DUCTS TO BE EQUIPPED WITH GRAVITY OR |
| | MOTORIZED DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN THE |
| | SYSTEMS OR SPACES ARE NOT IN USE. PROVIDE DAMPERS FOR |
| | EACH DUCT SUPPLYING O/A TO THE FCU'S. |
| | |
| | 28) M204.C, & D: NO O/A PROVIDED AT THE ELEVATOR OR |
| | FIRE LOBBIES- TABLE 403.3.1.1 AND SECTION 404.3 FBC M. |
| | |
| | 29) M205.B: CU-2 SHALL BE INSTALLED OUTDOORS IN |
| | ACCORDANCE WITH THE LISTING AND LABELING OF THE |
| | APPLIANCE AND MANUFACTURER'S GUIDELINES- SECTION 304.1 |
| | FBC M. |
| | |
| | 30) M205.B: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| | THE WATER HEATER INTAKE VENT AND EXHAUST FLUE |
| | FIRE-WRAPPING- SECTION 304.1 FBC M. THE SPECS SHALL |
| | SHOW THE PRODUCT CAN BE USED FOR THIS TYPE OF |
| | INSTALLATION IN LIEU OF A FIRE-RATED SHAFT |
| | |
| | 31) M205.D: NO O/A PROVIDED AT THE ELEVATOR OR FIRE |
| | LOBBIES- TABLE 403.3.1.1 AND SECTION 404.3 FBC M. |
| | |
| | 32) M205.C & M206.C: IT APPEARS FD'S ARE MISSING AT THE |
| | AHU-14 SUPPLY AND RETURN DUCT FLOOR/CEILING |
| | PENETRATIONS. |
| | |
| | 33) M205.C: PLEASE CLARIFY THE PURPOSE OF THE FSD SHOWN |
| | IN THE MIDDLE OF THE 24X20 SUPPLY DUCT FROM AHU-14. |
| | |
| | 34) M205.C & M206.C POOL EQUIPMENT ROOM: A) PROVIDE A |
| | POOL EQUIPMENT SCHEDULE AND SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE POOL HEATERS AND DIRECT VENT |
| | EXHAUST AND INTAKE DUCTS- SECTION 301.3 FBC FG. B) |
| | PROVIDE A GAS PIPING PLAN AND ISOMETRIC DRAWING- |
| | SECTION 402.1 FBC FG. C) THE AIR INTAKE LOUVER SHALL |
| | COMMUNICATE DIRECTLY TO THE OUTDOORS AND CANNOT DRAW |
| | VENTILATION AIR FROM THE ENCLOSED GARAGE SPACE- TABLE |
| | 403.3.1.1 FOOTNOTE B. D) REFER TO SECTION 414.1.3 FBC B |
| | AND PROVIDE A LIST OF POOL TREATMENT CHEMICALS AND |
| | THEIR QUANTITIES TO BE USED AND STORED IN THE ROOM. E) |
| | INDICATE THE SEQUENCE OF OPERATION FOR EF 62 AND THE |
| | TYPE OF EXHAUST DUCTWORK TO BE INSTALLED- REFER TO |
| | SECTIONS 510.2- 510.9 FBC M. F) INDICATE THE REQUIRED |
| | CLEARANCES FOR THE EXHAUST OUTLET- SECTION 501.3.1 FBC |
| | M. G) SHOW COMPLIANCE WITH SECTION 305.3.2 FBC FG: |
| | CONNECTION OF A PARKING GARAGE WITH ANY ROOM IN WHICH |
| | THERE IS A FUEL-FIRED APPLIANCE SHALL BE BY MEANS OF A |
| | VESTIBULE PROVIDING A TWO-DOORWAY SEPARATION, EXCEPT |
| | THAT A SINGLE DOOR IS PERMITTED WHERE THE SOURCES OF |
| | IGNITION IN THE APPLIANCE ARE ELEVATED IN ACCORDANCE |
| | WITH SECTION 305.3. |
| | |
| | 35) M206.A, EMERGENCY GENERATOR: THE EXHAUST DUCT FROM |
| | EF-53 SHALL RUN INDEPENDENTLY AND DIRECTLY TO THE |
| | EXTERIOR OF THE BUILDING, AND SHALL NOT CONNECT INTO |
| | THE RADIATOR EXHAUST PLENUM- SECTION 510.6.7 FBC M. |
| | PLEASE NOTE THAT THE GENERATOR WILL BE UNDER SEPARATE |
| | PERMIT. A COMPLETE SEPARATE PLAN AND SUBMITTAL PACKAGE |
| | WILL BE REQUIRED INCLUDING AN ENLARGED DRAWING OF THE |
| | EPSS (EMERGENCY GENERATOR) ROOM SHOWING THE LOCATIONS |
| | OF THE GENERATOR AND SUB-BASE TANK, FUEL OIL PIPE AND |
| | EXHAUST PIPE RUNS AND TERMINATION LOCATIONS, AND ALL |
| | OTHER ASSOCIATED EQUIPMENT INCLUDING EMERGENCY |
| | ELECTRICAL PANELS ETC. PLEASE INCLUDE THE REQUIRED |
| | CLEARANCE DISTANCE MEASUREMENTS FOR ALL EQUIPMENT VENT |
| | PIPING RUNS AND SPECIFICATIONS INCLUDING FILL PIPING |
| | LOCATIONS. THE SUBMITTAL PACKAGE SHALL INCLUDE: |
| | A) MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR AND |
| | THE 190-GALLON FUEL TANK, FUEL PIPING, ENGINE EXHAUST |
| | PIPE, MUFFLER, AND ALL OTHER ASSOCIATED SYSTEM |
| | COMPONENTS- SECTION 304.1 FBC M |
| | B) THE UL 2200 CERTIFICATE OF COMPLIANCE FOR THE |
| | GENERATOR- SECTION 915.1 FBC M. |
| | C) THE MANUFACTURER'S SPECIFICATIONS AND/OR UL |
| | CERTIFICATE SHALL INDICATE THE GENERATOR IS COMPLIANT |
| | WITH THE NFPA 37 AND NFPA 110 STANDARD AND IS |
| | CLASSIFIED AS A LEVEL 1 EPSS- SECTION 4.4.1 NFPA 110. |
| | D) PRODUCT CUT SHEET FOR THE FUEL TANK THAT INCLUDES |
| | THE TANK'S UL LISTING- UL 142 OR UL 2085- SEE SECTION |
| | 21.4.2.1.1 NFPA 30. |
| | E) GENERATOR EXHAUST PIPE SPECIFICATIONS AND PROVIDE AN |
| | EXHAUST PIPE DIAGRAM SHOWING THE TOTAL SYSTEM RUN AND |
| | LENGTH MEASUREMENT, AND TERMINATION LOCATION PLEASE |
| | INCLUDE ALL COMPONENTS OF THE SYSTEM INCLUDING THE |
| | SILENCER, AND ANY CONTRACTOR SUPPLIED PIPING- SEE |
| | SECTIONS 8.1 ? 8.4 NFPA 37, AND SECTION 501.3.1 FBC M. |
| | F) BACKPRESSURE CALCULATIONS FOR THE GENERATOR EXHAUST |
| | PIPE RUN- SECTION 304.1 FBC M. |
| | G) DETAILS AND SPECIFICATIONS FOR NORMAL AND EMERGENCY |
| | RELIEF VENTING OF THE TANK, INCLUDING VENT PIPING RUNS |
| | AND TERMINATION LOCATIONS AT THE EXTERIOR OF THE |
| | BUILDING- SECTION 24.13 NFPA 30. |
| | |
| | 36) M206.A: REFER TO SECTION 7.7.1 NFPA 110- 2016 AND |
| | VERIFY THAT THE VENTILATION AIRFLOW IN THE |
| | GENERATOR/TANK (EPS) ROOM IS DESIGNED TO LIMIT THE |
| | MAXIMUM AIR TEMPERATURE IN THE ROOM TO THE MAXIMUM |
| | AMBIENT AIR TEMPERATURE REQUIRED BY THE GENERATOR |
| | MANUFACTURER. CONSIDERATION SHALL BE GIVEN TO ALL THE |
| | HEAT EMITTED TO THE ROOM BY THE ENERGY CONVERTER, |
| | EXHAUST PIPES, AND ALL OTHER HEAT PRODUCING EQUIPMENT- |
| | SECTION 7.7.1.1. DESIGN OF THE HEATING, COOLING, AND |
| | VENTILATION SYSTEM SHALL AMONG OTHER THINGS, INCLUDE |
| | PROVISIONS FOR FACTORS SUCH AS HEAT, COLD, HUMIDITY, |
| | LOUVERS, ETC.- SECTION |
| | 'S SPECS FOR THE BOILERS AND WATER HEATERS- SECTIONS |
| | 402.1, 503.1, AND 624.1 FBC FG. |
| | |
| | 38) M206.B: PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN |
| | AIR SYSTEM OF ERU-01- SECTION 606.2.1 FBC M. |
| | |
| | 39) M206.C: NOTE THE REQUIRED CLEARANCES FOR THE |
| | COMBUSTION AIR INTAKE DUCTS PER MANUFACTURER'S |
| | SPECIFICATIONS, AND PER SECTION 304.1 (8) FBC FG. |
| | |
| | 40) M206.C: SHOW O/A SUPPLY TO THE RESIDENTIAL UNITS OR |
| | INDICATE NATURAL VENTILATION IN THE NOTES- SECTION 402 |
| | FBC M. |
| | |
| | 41) M206.C: PLEASE PLACE NOTES ON THE PLAN TO INDICATE |
| | THE WHAT TYPE OF HORIZONTAL 2-HR FIRE-RATED ENCLOSURES |
| | WILL BE INSTALLED FOR THE DRYER AND TOILET EXHAUST |
| | DUCTS AND INDICATE WHERE THE DETAILS ARE FOUND IN THE |
| | PLANS- SECTION 107.2.1 WPB. |
| | |
| | 42) M206.C: THE REVISED PLAN SHOWS SPF-13 PRESSURIZING |
| | THE CORRIDOR BUT NOT THE STAIRWAY WHICH IS NOW SHOWN |
| | CLOSED OFF WITH DOORS- SECTION 909.6 FBC B AND 513.6 |
| | FBC M. |
| | |
| | 43) M207.A: THE VENTILATION CALCULATIONS SHOWN AT THE |
| | TOP OF THE PAGE ARE NOT IN COMPLIANCE WITH TABLE |
| | 403.3.1.1 FBC M. PLEASE REVISE AND PROVIDE AIR BALANCE |
| | CALCULATIONS FOR ALL ROOMS AND SPACES USING EXHAUST |
| | VENTILATION SYSTEMS- SECTION 501.4 FBC M. A) INCLUDE |
| | THE AHU SERVING THE LAP POOL IN THE CALCULATIONS. |
| | PLEASE NOTE THAT THIS APPEARS TO BE A SYSTEM OF SUPPLY |
| | AND RETURN AIR, HOWEVER THE CALCULATION INDICATES |
| | O/A/EXHAUST. PLEASE CORRECT OR PROVIDE EXHAUST IN THE |
| | ROOM. |
| | |
| | 44) M207.A POOL EQUIPMENT ROOM: A) PROVIDE A POOL |
| | EQUIPMENT SCHEDULE AND SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE POOL HEATERS AND DIRECT VENT |
| | EXHAUST AND INTAKE DUCTS- SECTION 301.3 FBC FG. B) |
| | PROVIDE A GAS PIPING PLAN AND ISOMETRIC DRAWING- |
| | SECTION 402.1 FBC FG. C) REFER TO SECTION 414.1.3 FBC B |
| | AND PROVIDE A LIST OF POOL TREATMENT CHEMICALS AND |
| | THEIR QUANTITIES TO BE USED AND STORED IN THE ROOM. D) |
| | INDICATE THE SEQUENCE OF OPERATION FOR EF 48 AND THE |
| | TYPE OF EXHAUST DUCTWORK TO BE INSTALLED- REFER TO |
| | SECTIONS 510.2- 510.9 FBC M. E) INDICATE THE REQUIRED |
| | CLEARANCES FOR THE EXHAUST OUTLET- SECTION 501.3.1 FBC |
| | M.36 |
| | |
| | 45) M207.A LAUNDRY: PLACE A NOTE INDICATING UNDER |
| | SEPARATE PERMIT AS WAS INDICATED IN THE RESPONSE |
| | NARRATIVE. |
| | |
| | 46) M207.B: PER THE NOTE, THE KITCHENS ARE UNDER |
| | SEPARATE PERMIT, HOWEVER IT WILL BE HELPFUL TO SHOW THE |
| | PROPOSED LOCATIONS OF KITCHEN HOOD EXHAUST DUCT |
| | TERMINATIONS ON THE PLAN (THERE IS NO NOTE INDICATING A |
| | SCRUBBER IS TO BE USED PER THE RESPONSE NARRATIVE). |
| | PLEASE BE ADVISED THAT THE REQUIREMENT FOR KITCHEN |
| | EXHAUST MAKEUP AIR TEMPERATURE UNDER SECTION 508.1.1 |
| | WILL BE ENFORCED UNDER THE SEPARATE PERMIT. |
| | |
| | 47) M207.B: LABEL THE ELEVATOR RELIEF VENT- SECTION |
| | 107.2.1 WPB. |
| | |
| | 48) M208.A & B: THE RR-4 RETURN FROM THE TENNIS COURTS |
| | APPEARS TO BE CONNECTED TO TWO SUPPLY DIFFUSERS. WHICH |
| | SYSTEM(S) ARE THESE DUCTS CONNECTED TO?- SECTION |
| | 107.2.1 WPB. |
| | |
| | 49) M208.B HOTEL POOL EQUIPMENT ROOM: A) PROVIDE A POOL |
| | EQUIPMENT SCHEDULE AND SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE POOL HEATERS AND DIRECT VENT |
| | EXHAUST AND INTAKE DUCTS- SECTION 301.3 FBC FG. B) |
| | PROVIDE A GAS PIPING PLAN AND ISOMETRIC DRAWING- |
| | SECTION 402.1 FBC FG. C) REFER TO SECTION 414.1.3 FBC B |
| | AND PROVIDE A LIST OF POOL TREATMENT CHEMICALS AND |
| | THEIR QUANTITIES TO BE USED AND STORED IN THE ROOM. D) |
| | INDICATE THE SEQUENCE OF OPERATION FOR EF-52 AND THE |
| | TYPE OF EXHAUST DUCTWORK TO BE INSTALLED- REFER TO |
| | SECTIONS 510.2- 510.9 FBC M. E) INDICATE THE REQUIRED |
| | CLEARANCES FOR THE POOL ROOM EXHAUST OUTLET- SECTION |
| | 501.3.1 FBC M, AND THE POOL HEATER INTAKE OPENINGS AND |
| | EXHAUST OUTLETS. |
| | |
| | 50) M208.C: NO VENTILATION PROVIDED TO THE ELEVATOR |
| | LOBBY. |
| | HOTEL TOWER |
| | |
| | 51) M209, 210, 211, 212: PROVIDE A DETAIL SHOWING THE |
| | FCU INSTALLATION IN THE CLOSET INCLUDING THE RETURN AIR |
| | SYSTEM, AND REQUIRED CLEARANCE AND ACCESS FOR SERVICE |
| | AND REPLACEMENT OF THE UNIT- SECTION 306.1 FBC M. |
| | |
| | 52) M209-M211 TENNIS COURT SYSTEMS: PLEASE CORRECT THE |
| | REFERENCES TO PLAN SHEETS M.224 AND M.226 WHICH ARE NOT |
| | RELATED TO THE TENNIS COURT SYSTEMS- SECTION 107.2.1 |
| | WPB. |
| | |
| | 53) M209 & M210: THE DRYERS APPEAR TO BE REMOVED FROM |
| | THE HOTEL FLOOR PLANS. PLEASE REMOVE GENERAL NOTE #3 |
| | CONCERNING THE MAKEUP AIR IN THE CLOSETS. |
| | |
| | 54) M209, M210, M211, & M212: THE KITCHEN EXHAUST SHALL |
| | RUN INDEPENDENTLY AND NOT BE CONNECTED TO THE TOILET |
| | EXHAUST DUCT SYSTEM- SECTIONS 501.2 & 505.1 FBC M. |
| | |
| | OFFICE TOWER |
| | |
| | 55) M.701 AND ALL OFFICE FLOOR PLAN SHEETS: PROVIDE |
| | DUCT SMOKE DETECTORS AT EACH FLOOR LEVEL OF THE ERU-03 |
| | RETURN AIR RISER- SECTION 606.2.3 FBC M. PROVIDE DS |
| | SYMBOLS ON THE PLANS TO INDICATE THE LOCATIONS. |
| | |
| | 56) M.218: THE MECHANICAL ROOM VENTILATION CALCULATIONS |
| | ARE NOT IN COMPLIANCE WITH SECTION 1105.6.3.1 FOR |
| | NORMAL CONDITIONS, AND SECTION 1105.6.3.2 FOR EMERGENCY |
| | CONDITIONS. PLEASE CORRECT THE CALCULATIONS AND PROVIDE |
| | A SEQUENCE OF OPERATION FOR EF-58. |
| | |
| | 57) M.218 & M.603: PROVIDE THE MISSING PERFORMANCE DATA |
| | FOR THE COOLING TOWERS IN THE SCHEDULE. |
| | |
| | 58) M.218: PROVIDE SITE SPECIFIC STRUCTURAL ENGINEERING |
| | FOR INSTALLATION OF THE COOLING TOWERS, CONDENSER |
| | UNITS, ROOFTOP AND ALL OTHER EXPOSED MECHANICAL |
| | EQUIPMENT AND APPLIANCES- SECTION 301.15 FBC M. PLEASE |
| | NOTE THE ENGINEERING MAY BE DEFERRED AND CAN BE NOTED |
| | AS SUCH ON THE PLAN SHEET. |
| | |
| | 59) M.219: IT APPEARS THAT AN AC-4 AND AC-9 ARE TO BE |
| | INSTALLED INSIDE THE ELEVATOR HOISTWAYS WHICH IS |
| | PROHIBITED- SECTION 303.8 FBC M. |
| | |
| | 60) THERE ARE NO COOLING AND HEATING CALCULATIONS FOR |
| | ERU-03 & OAU-1. |
| | |
| | RESIDENTIAL TOWER |
| | |
| | 61) M.220: PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN |
| | AIR SYSTEM OF AHU-12- SECTION 606.2.1 FBC M. |
| | |
| | 62) M.222: CHANGE THE REFERENCE TO SHEET M.228 TO |
| | M.229- SECTION 107.2.1 WPB. |
| | |
| | 63) M.222: PROVIDE CONSTRUCTION DETAILS FOR THE 2-HR |
| | FIRE-RATED ELEVATOR RELIEF DUCT ENCLOSURE- SECTION |
| | 703.2.1 FBC B. |
| | |
| | 64) M.227: PROVIDE SITE SPECIFIC STRUCTURAL ENGINEERING |
| | FOR INSTALLATION OF THE COOLING TOWERS, GENERATOR, OAU |
| | AND ROOFTOP DUCTWORK, CONDENSING UNITS, AND ALL OTHER |
| | MECHANICAL EQUIPMENT AND APPLIANCES- SECTION 301.15 FBC |
| | M. PLEASE NOTE THE ENGINEERING MAY BE DEFERRED AND CAN |
| | BE NOTED AS SUCH ON THE PLAN SHEET. |
| | |
| | 65) M.228: PROVIDE SITE SPECIFIC STRUCTURAL ENGINEERING |
| | FOR INSTALLATION OF ROOFTOP CONDENSING UNITS, AND ALL |
| | OTHER EXPOSED MECHANICAL EQUIPMENT AND APPLIANCES- |
| | SECTION 301.15 FBC M. PLEASE NOTE THE ENGINEERING MAY |
| | BE DEFERRED AND CAN BE NOTED AS SUCH ON THE PLAN SHEET. |
| | |
| | 66) M.228: IT APPEARS THAT AN AC-4 IS TO BE INSTALLED |
| | INSIDE THE ELEVATOR HOISTWAY WHICH IS PROHIBITED- |
| | SECTION 303.8 FBC M. |
| | |
| | 67) M.229: LABEL THE MAIN RETURN AIR GRILL AND OPENING |
| | SIZE- SECTION 601.5 FBC M. |
| | |
| | 68) M.229: INDICATE THE HEIGHT OF EF-A10 FROM THE |
| | FINISHED FLOOR- SEE SECTION 306.5 FBC M. |
| | |
| | 69) M.229: PROVIDE A MECHANICAL ROOF PLAN FOR THE |
| | TENNIS COURT STRUCTURE WHICH SHOWS THE LOCATIONS OF THE |
| | CONDENSING UNITS, GRAVITY INTAKES AND EXHAUST FANS AS |
| | CALLED OUT ON M.229. A) PROVIDE ENGINEERING FOR ALL |
| | ROOFTOP MECHANICAL INSTALLATIONS- MAY BE DEFERRED WITH |
| | A NOTE ON THE PLAN. B) PROVIDE CLEARANCE DISTANCE |
| | MEASUREMENTS FOR ALL SERVICEABLE MECHANICAL EQUIPMENT |
| | TO ROOF EDGES- SEE SECTION 304.11 FBC M. |
| | |
| | 70) M.259- M261 RESIDENTIAL UNITS: PLEASE PROVIDE |
| | DETAILS OR NOTES ON THE PLAN INDICATING COMPLIANCE WITH |
| | THE FOLLOWING ITEMS. |
| | A) IDENTIFY ALL ROOMS ON THE PLANS. |
| | B) PROVIDE A FRONT VIEW DRAWING OF THE AIR HANDLER IN |
| | THE CLOSET SHOWING REQUIRED CLEARANCES, CONDENSATE |
| | DISPOSAL DETAILS, SUPPLY PLENUM AND RETURN AIR |
| | CONNECTIONS. |
| | C) INDICATE DIFFUSER AND RETURN GRILL DIMENSIONS OR |
| | PROVIDE A SCHEDULE ON THE PLAN. PLEASE NOTE BALANCED |
| | RETURN AIR IS REQUIRED- TRANSFER DUCTS SHALL BE SIZED |
| | 1-1/2 TIMES THE AREA OF THE SUPPLY DUCT TO THE ROOM, |
| | RETURN GRILLS SHALL BE SIZED AT 50 CFMS PER 100 SQ. |
| | INCHES, AND ALL AIR SUPPLIED TO MASTER BEDROOMS SHALL |
| | BE RETURNED- SEE SECTION 601.5 FBC M |
| | D) PROVIDE COOKING APPLIANCE SCHEDULES AND SUBMIT |
| | MANUFACTURER?S SPECIFICATIONS FOR EACH COOKING |
| | APPLIANCE. MAY BE DEFERRED AND NOTED AS SUCH ON THE |
| | PLANS. |
| | E) PROVIDE EXHAUST VENTILATION FOR THE KITCHENS AT A |
| | RATE OF 100 CFM INTERMITTENT OR 25 CFMS CONTINUOUS- |
| | TABLE 403.3.1.1. |
| | F) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE CLOTHES |
| | DRYERS AND THE DRYER EXHAUST BOOSTER FAN. PLEASE NOTE |
| | THAT THERE IS NO REQUIREMENT FOR BOOSTER FANS IN THE |
| | FBC-14 MECHANICAL CODE. DRYERS SHALL BE EXHAUSTED IN |
| | ACCORDANCE WITH MANUFACTURER?S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS- SECTION 504.1 FBC M. |
| | G) PROVIDE A SUBMITTAL FOR THE X-VENT BOXES. |
| | |
| | 71) M.501: PROVIDE DUCT CONNECTION, SUPPORT AND HANGING |
| | DETAILS PER THE CURRENT SMACNA HVAC DUCT CONSTRUCTION |
| | STANDARD- METAL AND FLEXIBLE 2005, AND SMACNA FIBROUS |
| | GLASS DUCT- 2010. |
| | |
| | 72) PLEASE PROVIDE COMPLETE CONDENSATE DISPOSAL PLANS |
| | INCLUDING RISER DRAWINGS FOR THE TOWER AND PODIUM |
| | SYSTEMS- SECTION 307.2.1 FBC M. |
| | |
| | 73) PLEASE LABEL ALL ELEVATOR EQUIPMENT ROOMS ON THE |
| | PLANS AND SHOW THE REQUIRED VENTILATION SYSTEMS- |
| | SECTION 3006.2 FBC B. |
| | |
| | ENERGY COMPLIANCE REPORT |
| | |
| | 74) THE PROJECT IS BEING DESIGNED UNDER THE 2014 |
| | FLORIDA BUILDING CODES. SUBMIT THE 2014 ENERGYGAUGE |
| | COMPLIANCE REPORT. |
| | |
| | 75) M.218 & M.603: THE SYSTEM FULL LOAD AND IPLV |
| | COMPLIANCE DATA FOR THE CHILLERS IN THE SCHEDULE DOES |
| | NOT MATCH THE DATA IN THE ENERGY REPORT- SEE TABLE |
| | C403.2.3(7) FBC EC. |
| | |
| | 76) NO COMPLIANCE DATA FOR OAU-1, THE WATER HEATERS, |
| | SERVICE WATER PIPING, AIR COOLED SPLIT SYSTEMS- AC-1- |
| | 9, INDOOR POOL AHU-08, AND THE CAPACITIES FOR FCU?S |
| | 2-18, |
| | |
| | 77) M.603: THE TOTAL MBH LISTED IN THE SCHEDULE FOR |
| | AHU-12, 13, & 14 DOES NOT MATCH THE CAPACITIES LISTED |
| | IN THE REPORT. |
| | |
| | 78) M.604: THE CAPACITY LISTED FOR FCU-01 IN THE |
| | SCHEDULE DOES NOT MATCH THE REPORT. |
| | |
| | 79) M.604 VHP'S: A) MBH IN SCHEDULE FOR VHP- 2, 3 & 4 |
| | DOESN'T MATCH DATA IN THE REPORT. B) PLEASE INDICATE |
| | THE NUMBER OF EACH VHP (1-7)) TO BE INSTALLED ON THE |
| | PROJECT. |
| | |
| | 80) M.604 HHP'S: A) NO DATA IN THE REPORT FOR HHP-2, 5, |
| | 6, 7, 8, & 9. B) PLEASE INDICATE THE NUMBER OF EACH HHP |
| | (1-9)) TO BE INSTALLED ON THE PROJECT. |
| | |
| | HEAT LOAD CALCULATIONS |
| | |
| | 81) SHEET M.602: THE COOLING CAPACITIES (MBH) SHOWN IN |
| | THE AHU AND ERU SCHEDULE ARE EITHER UNDER OR OVER THE |
| | HEAT LOADS SHOWN IN CALCULATIONS- SECTION C403.2.2 FBC |
| | EC. |
| | |
| | A) AHU-01 OFFICE/LOBBY: SCHEDULE- 207 MBH, CALCS- 436 |
| | MBH. |
| | |
| | B) AHU-02 LOBBY/CAFE: SCHEDULE- 158 MBH, CALCS- 177 |
| | MBH. |
| | |
| | C) AHU-03 HOTEL LOBBY: SCHEDULE- 275 MBH, CALCS- 320 |
| | MBH |
| | |
| | D) AHU-04 RETAIL/RESTAURANT: SCHEDULE- 903 MBH, CALCS- |
| | 773 MBH |
| | |
| | E) AHU-05 DAYCARE: SCHEDULE- 126 MBH, CALCS- 193 MBH |
| | |
| | F) AHU-07A & B: SCHEDULE 1,417 MBH, CALCS- 1,650 MBH. |
| | |
| | G) AHU-08 INDOOR POOL: SCHEDULE- 359 MBH, CALCS- 251 |
| | MBH. |
| | |
| | H) AHU-09 FITNESS/SPA: SCHEDULE- 265 MBH, CALCS- 667 |
| | MBH. |
| | |
| | I) AHU-10A & B TENNIS COURT ASSEMBLY: SCHEDULE- 1,387 |
| | MBH, CALCS- 1,552 MBH. PLEASE NOTE THAT THERE IS |
| | ANOTHER CALCULATION FOR THE ?TENNIS COURT? INDICATING |
| | 890 MBH. PLEASE CLARIFY. |
| | |
| | J) AHU-12 RES/LOUNGE: SCHEDULE- 404 MBH, CALCS- 357 |
| | MBH. |
| | |
| | K) AHU-13 RES LOBBY: SCHEDULE- 453 MBH, CALCS |
| | |
| | L) ERU-1: SCHEDULE- 761 MBH, CALCS 911 MBH. |
| | |
| | M) THERE ARE NO COOLING AND HEATING CALCULATIONS FOR |
| | ERU-03 & OAU-1. |
| | |
| | |