Plan Review Notes
Plan Review Notes For Permit 18100540
Permit Number 18100540
Review Stop G
Sequence Number 2
Notes
Date Text
2020-03-28 09:34:431) SHT. P.700A - THERE IS A NOTE ON ALL THE DETAILS
 THAT STATES "REFER TO SHT. P.802, DETAIL #10 FOR
 SEDIMENT TRAP DETAIL." THERE IS NO DETAIL #10 ON SHT.
 P.802 ? CLARIFY.
 2) 2) SHT. P700A - DETAIL #5 - SIZE THE MAIN LINE
 BETWEEN THE 4 INCH AND 2 1/2 INCH SECTIONS OF PIPE THAT
 SUPPLIES WATER HEATERS 1B & 1C.
 3) SHT. P700A - DETAILS #1 & #3 - NOTE #4 - THERE IS
 NOTE ON THESE DETAILS THAT REFERS TO SHT. P.802 FOR
 WATER HEATER DETAIL. THIS DETAIL HAS NOTHING TO DO WITH
 GAS WATER HEATERS. THE CORRECT SHEET IS P.804.PLEASE
 REVISE THE NOTE ON THE PLAN.
 4) SHT. P.803 - THE GAS WATER HEATER SCHEMATICS REFER
 TO THE HVAC DRAWINGS FOR FLUE INFORMATION FOR THE WATER
 HEATERS. PLACE THE SPECIFIC MECHANICAL SHEET NUMBERS ON
 THE DRAWINGS WHERE THE INFORMATION CAN BE FOUND. WPB
 AMEND. TO FBC SEC. 107.2.1.
 5) SHT. P700 - KEYNOTE #8 - SHOWS THE CFH AS 2,012 BUT
 THE GAS RISER SHOWS THE CFH AS 3,075. IF THIS NUMBER OF
 3, 075 IS CORRECT, THEN THE REST OF THE CFH ON THE GAS
 RISER IS WRONG. CLARIFY.
 6) SHT. P700 - THE NUMBERING ON THE GAS TAGS ON THE GAS
 RISER ARE VERY LIGHT AND ALMOST ILLEGIBLE. PLEASE
 REVISE.
 7) SHT. P.804 - SUBMIT ADDITIONAL INFORMATION
 (SPECIFICATIONS/ INSTALLATION MANUAL) FOR THE GAS
 DETECTION SYSTEM AND REFERENCE THE STANDARD ON WHICH
 THIS SYSTEM IS DESIGNED. WPB AMEND. TO FBC SEC.
 107.2.1.
 8) SHT. P.700A - PLACE THE SPECIFIC SHEET NUMBER IN THE
 GAS ISOMETRICS FOR THE ORIGINATING POINTS OF THE GAS
 LINES. WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.5.
 9) ALL GAS EQUIPMENT SHALL BE LISTED AND LABELED PER
 FBC-FUEL GAS SEC.301.3.
 10) SUBMIT CALCULATIONS FOR COMBUSTION AIR. PROVIDE
 VERIFICATION & CALCULATIONS AS TO HOW THE REQUIREMENTS
 ARE BEING MET. PROVIDE THE CODE SECTIONS FROM THE GAS
 CODE THAT YOU ARE USING IN THE DESIGN OF THE COMBUSTION
 AIR REQUIREMENTS PER THE 2014 FBC-FUEL GAS CODE
 SEC.304.1,
 11) SUBMIT DETAILS FOR THE TYPE OF GAS VENT MATERIAL,
 LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE ROOF,
 AND ANCHORING DETAILS OF THE GAS VENTS. FBC-FUEL GAS
 SECS.502 THROUGH 505.
 12) THE RESPONSE NARRATIVE STATES THAT A PDF PACKAGE
 HAS BEEN CREATED AND SUBMITTED ALONG WITH REQUESTED
 DRAWINGS TO COMPLY WITH PREVIOUS COMMENT # 4 FROM THE
 GAS REVIEW FROM 4/9/19 REQUESTING TWO COPIES OF
 MANUFACTURER?S SPECIFICATIONS AND INSTALLATION MANUALS
 FOR ALL GAS EQUIPMENT BUT THERE ARE NO SUCH DOCUMENTS
 IN THIS SUBMITTAL. CLARIFY.
 13) SHT. P.509 - DETAIL #2 SHOWS THE SHUTOFF VALVE
 OUTSIDE THE ROOM WHERE THE POOL HEATER IS LOCATED.
 CLARIFY.
 14) SHT. P.105C SHOWS VENT PIPING FROM THE GAS
 REGULATOR RUNNING FOR AN EXTENSIVE DISTANCE TO ITS
 TERMINATION POINT. VENT PIPING SHALL NOT EXCEED THE
 LENGTH SPECIFIED IN THE REGULATOR MANUFACTURER?S
 INSTRUCTIONS. SUBMIT THE VENT INSTALLATION INSTRUCTIONS
 FOR ALL THE REGULATORS TO BE USED. FBC-FUEL GAS SEC.
 410.3.1.
 15) SHOW THE SIZE OF THE GAS REGULATOR VENTS ON THE
 PLANS. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  