| 2020-03-28 09:34:43 | 1) SHT. P.700A - THERE IS A NOTE ON ALL THE DETAILS |
| | THAT STATES "REFER TO SHT. P.802, DETAIL #10 FOR |
| | SEDIMENT TRAP DETAIL." THERE IS NO DETAIL #10 ON SHT. |
| | P.802 ? CLARIFY. |
| | 2) 2) SHT. P700A - DETAIL #5 - SIZE THE MAIN LINE |
| | BETWEEN THE 4 INCH AND 2 1/2 INCH SECTIONS OF PIPE THAT |
| | SUPPLIES WATER HEATERS 1B & 1C. |
| | 3) SHT. P700A - DETAILS #1 & #3 - NOTE #4 - THERE IS |
| | NOTE ON THESE DETAILS THAT REFERS TO SHT. P.802 FOR |
| | WATER HEATER DETAIL. THIS DETAIL HAS NOTHING TO DO WITH |
| | GAS WATER HEATERS. THE CORRECT SHEET IS P.804.PLEASE |
| | REVISE THE NOTE ON THE PLAN. |
| | 4) SHT. P.803 - THE GAS WATER HEATER SCHEMATICS REFER |
| | TO THE HVAC DRAWINGS FOR FLUE INFORMATION FOR THE WATER |
| | HEATERS. PLACE THE SPECIFIC MECHANICAL SHEET NUMBERS ON |
| | THE DRAWINGS WHERE THE INFORMATION CAN BE FOUND. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 5) SHT. P700 - KEYNOTE #8 - SHOWS THE CFH AS 2,012 BUT |
| | THE GAS RISER SHOWS THE CFH AS 3,075. IF THIS NUMBER OF |
| | 3, 075 IS CORRECT, THEN THE REST OF THE CFH ON THE GAS |
| | RISER IS WRONG. CLARIFY. |
| | 6) SHT. P700 - THE NUMBERING ON THE GAS TAGS ON THE GAS |
| | RISER ARE VERY LIGHT AND ALMOST ILLEGIBLE. PLEASE |
| | REVISE. |
| | 7) SHT. P.804 - SUBMIT ADDITIONAL INFORMATION |
| | (SPECIFICATIONS/ INSTALLATION MANUAL) FOR THE GAS |
| | DETECTION SYSTEM AND REFERENCE THE STANDARD ON WHICH |
| | THIS SYSTEM IS DESIGNED. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 8) SHT. P.700A - PLACE THE SPECIFIC SHEET NUMBER IN THE |
| | GAS ISOMETRICS FOR THE ORIGINATING POINTS OF THE GAS |
| | LINES. WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.5. |
| | 9) ALL GAS EQUIPMENT SHALL BE LISTED AND LABELED PER |
| | FBC-FUEL GAS SEC.301.3. |
| | 10) SUBMIT CALCULATIONS FOR COMBUSTION AIR. PROVIDE |
| | VERIFICATION & CALCULATIONS AS TO HOW THE REQUIREMENTS |
| | ARE BEING MET. PROVIDE THE CODE SECTIONS FROM THE GAS |
| | CODE THAT YOU ARE USING IN THE DESIGN OF THE COMBUSTION |
| | AIR REQUIREMENTS PER THE 2014 FBC-FUEL GAS CODE |
| | SEC.304.1, |
| | 11) SUBMIT DETAILS FOR THE TYPE OF GAS VENT MATERIAL, |
| | LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE ROOF, |
| | AND ANCHORING DETAILS OF THE GAS VENTS. FBC-FUEL GAS |
| | SECS.502 THROUGH 505. |
| | 12) THE RESPONSE NARRATIVE STATES THAT A PDF PACKAGE |
| | HAS BEEN CREATED AND SUBMITTED ALONG WITH REQUESTED |
| | DRAWINGS TO COMPLY WITH PREVIOUS COMMENT # 4 FROM THE |
| | GAS REVIEW FROM 4/9/19 REQUESTING TWO COPIES OF |
| | MANUFACTURER?S SPECIFICATIONS AND INSTALLATION MANUALS |
| | FOR ALL GAS EQUIPMENT BUT THERE ARE NO SUCH DOCUMENTS |
| | IN THIS SUBMITTAL. CLARIFY. |
| | 13) SHT. P.509 - DETAIL #2 SHOWS THE SHUTOFF VALVE |
| | OUTSIDE THE ROOM WHERE THE POOL HEATER IS LOCATED. |
| | CLARIFY. |
| | 14) SHT. P.105C SHOWS VENT PIPING FROM THE GAS |
| | REGULATOR RUNNING FOR AN EXTENSIVE DISTANCE TO ITS |
| | TERMINATION POINT. VENT PIPING SHALL NOT EXCEED THE |
| | LENGTH SPECIFIED IN THE REGULATOR MANUFACTURER?S |
| | INSTRUCTIONS. SUBMIT THE VENT INSTALLATION INSTRUCTIONS |
| | FOR ALL THE REGULATORS TO BE USED. FBC-FUEL GAS SEC. |
| | 410.3.1. |
| | 15) SHOW THE SIZE OF THE GAS REGULATOR VENTS ON THE |
| | PLANS. WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |