| Date |
Text |
| 2019-03-13 13:43:42 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET ALS 1.00 - THERE ARE INDICATIONS REGARDING THE |
| | CONTENTS OF THE COMMAND ROOM. |
| | |
| | PER NFPA 1 AND 101 THERE ARE ADDITIONAL REQUIRMENTS NOT |
| | LISTED. FOR CLARIFICATION PURPOSES THE EXACT CODE |
| | LANGUAGE IS PROVIDED: |
| | |
| | THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1, |
| | CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN |
| | THE FOLLOWING FEATURES: |
| | |
| | 1. SHALL BE A MINIMUM OF 200 FT SQUARED WITH A MINIMUM |
| | DIMENSION OF 10 FT. |
| | 2. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM. |
| | 3. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| | ACCESS TO THE PUBLIC TELEPHONE SYSTEM |
| | 4. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL |
| | FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF |
| | EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING |
| | EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION |
| | OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE |
| | BARRIERS AND SMOKE PARTITIONS |
| | 5. A WORK TABLE. |
| | 6. IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN |
| | FOR THE BUILDING. |
| | 7. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM |
| | CONTROL UNIT. |
| | 8. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF |
| | THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL |
| | 9. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION |
| | SYSTEMS. |
| | 10. CONTROLS FOR UNLOCKING STAIRWAY DOORS |
| | SIMULTANEOUSLY |
| | 11. SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY |
| | PANELS |
| | 12. EMERGENCY AND STANDBY POWER STATUS INDICATORS |
| | 13. FIRE PUMP STATUS INDICATORS |
| | 14. GENERATOR SUPERVISION DEVICES AND MANUAL START AND |
| | TRANSFER FEATURES. |
| | 15. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED |
| | BY OTHER SECTIONS OF THIS CODE |
| | 16. CONTROLS REQUIRED FOR SMOKE CONTROL |
| | 17. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME |
| | A17.1. |
| | 18. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR |
| | SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS |
| | PROVIDED |
| | |
| | NFPA 101, CHAPTER 11, SPECIAL STRUCTURES AND HIGH RISE |
| | BUILDINGS |
| | |
| | 11.8.6* EMERGENCY COMMAND CENTER. |
| | 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED |
| | IN A LOCATION APPROVED BY THE FIRE DEPARTMENT. |
| | 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE |
| | FOLLOWING: |
| | (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS |
| | (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION |
| | SERVICE PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER |
| | SECTION OF THIS CODE |
| | (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION |
| | PANELS |
| | (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS |
| | (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME |
| | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS |
| | (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE |
| | PROVIDED IN ACCORDANCE WITH ASME A17.1/CSA B44 |
| | (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS |
| | (8) EMERGENCY GENERATOR STATUS INDICATORS |
| | (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING |
| | SYSTEM |
| | (10) FIRE PUMP STATUS INDICATORS |
| | (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| | ACCESS TO THE |
| | PUBLIC TELEPHONE SYSTEM |
| | (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY |
| | 11.8.8 |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 2) SHEET ALS1.102 THRU 1.104 - THE HOTEL SIDE FIRE |
| | LOBBY DOOR,EAST SIDE, INDICATES A SWING AGAINST THE |
| | EXIT PATH OF TRAVEL. |
| | |
| | PER NFPA 101, CH 7, MEANS OF EGRESS |
| | |
| | 7.2.1.4.2 DOOR LEAF SWING DIRECTION. DOOR LEAVES |
| | REQUIRED TO BE |
| | OF THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING |
| | IN THE |
| | DIRECTION OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING |
| | CONDITIONS: |
| | (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD |
| | OF 50 OR |
| | MORE, EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS: |
| | (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE |
| | REQUIRED TO |
| | SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED |
| | BY 7.2.4.3.8.1 OR 7.2.4.3.8.2. |
| | (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED |
| | TO |
| | SWING IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING |
| | HEALTH |
| | CARE OCCUPANCIES, AS PROVIDED IN CHAPTER 19. |
| | (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT |
| | ENCLOSURE, UNLESS |
| | THE DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT |
| | OPENS |
| | DIRECTLY INTO AN EXIT ENCLOSURE |
| | (3) WHERE THE DOOR OPENING SERVES A HIGH HAZARD |
| | CONTENTS AREA |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES. |
| | |
| | |
| | |
| | |
| | 3) SHEET A 1.102 & A 6.103 - THERE ARE NO CLEAR |
| | INDICATIONS OF THE TRASH CHUTE ROOM DOOR NUMBER OR TYPE |
| | ON THIS THESE SHEETS OR ANY OTHER SHEET. |
| | |
| | PLEASE REVIEW AND CORRECT OR CLARIFY |
| | |
| | |
| | |
| | 3A) SHEET A 1.102 - THE DOOR TO THE TRASH CHUTE OPENS |
| | TOO FAR INTO THE EXIT CORRIDOR. |
| | |
| | PER NFPA 101, CH 7 MEANS OF EGRESS & CH 9 |
| | |
| | 7.2.1.4.3* DOOR LEAF ENCROACHMENT. |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS |
| | SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED |
| | WIDTH OF AN AISLE, |
| | A CORRIDOR, A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, |
| | UNLESS BOTH |
| | OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING |
| | BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENT OF |
| | 7.2.1.4.3.2. |
| | |
| | |
| | 9.5 WASTE CHUTES, INCINERATORS, AND LAUNDRY CHUTES. |
| | 9.5.1 ENCLOSURE. |
| | 9.5.1.1 WASTE CHUTES AND LAUNDRY CHUTES SHALL BE |
| | SEPARATELY |
| | ENCLOSED BY WALLS OR PARTITIONS IN ACCORDANCE WITH THE |
| | PROVISIONS |
| | OF SECTION 8.3. |
| | 9.5.1.2 CHUTE INTAKE OPENINGS SHALL BE PROTECTED IN |
| | ACCORDANCE |
| | WITH SECTION 8.3. |
| | 9.5.1.3 THE DOORS OF CHUTES SPECIFIED IN 9.5.1.2 SHALL |
| | OPEN ONLY TO |
| | A ROOM THAT IS DESIGNED AND USED EXCLUSIVELY FOR |
| | ACCESSING THE |
| | CHUTE OPENING. |
| | 9.5.1.4 CHUTE SERVICE OPENING ROOMS SHALL BE SEPARATED |
| | FROM OTHER |
| | SPACES IN ACCORDANCE WITH SECTION 8.7. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES AND NARRATIVE. |
| | |
| | |
| | |
| | 4) SHEET A1.105 - THERE ARE INDICATIONS OF LIFT IN SOME |
| | OF THE PARKING GARAGE. |
| | |
| | WHAT DOES REPRESENT AND HOW WILL IT EFFECT THE FIRE |
| | PROTECTION SYSTEMS? |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS WITH SPECIFIC CODE |
| | REFERENCES. |
| | |
| | |
| | |
| | 5) SHEET A1.108 - THERE IS AN INDICATION OF AN EXIT |
| | SIGN(TENNIS COURT SIDE) AND EXIT DOOR FIRE RESISTANCE |
| | CALCULATION(45) LEADING TO THE CORRIDOR BY THE HOTEL |
| | POOL EQUIPMENT ROOM. |
| | |
| | THERE IS NO INDICATION OF A DOOR. |
| | |
| | SHEET E108B INDICATES A DOUBLE DOOR AT THE WALL WITH AN |
| | EXIT SIGN. |
| | |
| | PLEASE REVIEW AND CORRECT OR CLARIFY. |
| | |
| | |
| | |
| | |
| | 6) SHEET A1.109, ALS 1.110 & A1.241- THERE IS AN |
| | INDICATION OF THE FIRE LOBBY DOOR SWINGING IN THE PATH |
| | OF TRAVEL ON A1.109 AND AGAINST THE PATH OF TRAVEL ON |
| | THE OTHER TWO SHEETS. |
| | |
| | IT IS REQUIRED TO SWING IN THE PATH OF TRAVEL PER NPA |
| | 101, CH 7 AS NOTED ABOVE. |
| | |
| | PLEASE REVIEW,CORRECT AND /OR CLARIFY. |
| | |
| | |
| | |
| | |
| | 7) ALL APPLICABLE A & ALS SHEETS - THERE IS AN |
| | INCORRECT TOTAL CALCULATION INDICATED FOR A 44" DOOR |
| | OPENING. THE CODE REQUIRES THE LOAD CALCULATIONS TO BE |
| | ROUNDED UP; 146.7 SHOULD BE ROUNDED UP TO 147 ON ALL |
| | APPLICABLE SHEETS. |
| | |
| | 7.3.3* EGRESS CAPACITY. |
| | 7.3.3.1 EGRESS CAPACITY FOR APPROVED COMPONENTS OF |
| | MEANS OF |
| | EGRESS SHALL BE BASED ON THE CAPACITY FACTORS SHOWN IN |
| | TABLE |
| | 7.3.3.1, UNLESS OTHERWISE PROVIDED IN 7.3.3.2 |
| | |
| | PLEASE REVIEW AND CORRECT |
| | |
| | |
| | |
| | 8) ALL APPLICABLE A & ALS SHEETS - THERE IS AN |
| | INCORRECT TOTAL CALCULATION INDICATED FOR A 60" STAIR |
| | WIDTH; 218(.2 WAS USED . THE CODE REQUIRES THE LOAD |
| | CALCULATIONS TO BE .03; 200 SHOULD ON ALL APPLICABLE |
| | SHEETS. |
| | |
| | 7.3.3* EGRESS CAPACITY. |
| | 7.3.3.1 EGRESS CAPACITY FOR APPROVED COMPONENTS OF |
| | MEANS OF |
| | EGRESS SHALL BE BASED ON THE CAPACITY FACTORS SHOWN IN |
| | TABLE |
| | 7.3.3.1, UNLESS OTHERWISE PROVIDED IN 7.3.3.2 |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 9) SHEET A1.109 , A1.110 & ALS1.110 - THERE ARE |
| | INDICATIONS OF CONFLICTS WITH THE CORE DOOR FIRE |
| | RATINGS, DOOR LOCATION AND DOOR SWING. |
| | |
| | THE LS SHEET SHOWS TWO DOORS, NR, IN THE H.K. ROOM WITH |
| | NO RATING ON THE BACK WALL. |
| | |
| | THE MECH ROOM DOOR IS 20 MIN IN A 2 HOUR WALL. |
| | |
| | THE LS SHEET DOOR SWING ON THE FIRE LOBBY SHOWS IN THE |
| | PATH OF TRAVEL WHILE OTHER SHEETS SHOW OPPISITE. |
| | |
| | PLEASE REVIEW AND CORRECT OR CLARIFY. |
| | |
| | |
| | |
| | 10) SHEET ALS1.111 - THERE IS AN INDICATION OF NR |
| | DOUBLE DOORS AT THE MECH ROOM. THESE DOORS ARE REQUIRED |
| | TO BE RATED. |
| | |
| | PER NFPA 101, CH 38 |
| | |
| | 38.3.2 PROTECTION FROM HAZARDS. |
| | 38.3.2.1* GENERAL. HAZARDOUS AREAS INCLUDING, BUT NOT |
| | LIMITED TO, |
| | AREAS USED FOR GENERAL STORAGE, BOILER OR FURNACE |
| | ROOMS, AND |
| | MAINTENANCE SHOPS THAT INCLUDE WOODWORKING AND PAINTING |
| | AREAS |
| | SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 8.7. |
| | 38.3.2.2* HIGH HAZARD CONTENTS AREAS. HIGH HAZARD |
| | CONTENTS |
| | AREAS, AS CLASSIFIED IN SECTION 6.2, SHALL MEET ALL OF |
| | THE FOLLOWING |
| | CRITERIA: |
| | (1) THE AREA SHALL BE SEPARATED FROM OTHER PARTS OF THE |
| | BUILDING BY |
| | FIRE BARRIERS HAVING A MINIMUM 1-HOUR FIRE RESISTANCE |
| | RATING, |
| | WITH ALL OPENINGS THEREIN PROTECTED BY SELF-CLOSING |
| | FIRE DOOR |
| | ASSEMBLIES HAVING A MINIMUM 3?4-HOUR FIRE PROTECTION |
| | RATING. |
| | (2) THE AREA SHALL BE PROTECTED BY AN AUTOMATIC |
| | EXTINGUISHING |
| | SYSTEM IN ACCORDANCE WITH 9.7.1.1(1) OR 9.7.1.2. |
| | |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES. |
| | |
| | |
| | |
| | |
| | 11) SHEET ALS1.114 - THERE ARE INDICATIONS AT THE FIRE |
| | LOBBY & STAIR #1 EXIT DOORS OBSTRUCTING EACH OTHER. |
| | |
| | PER NFPA 101 CH 7 |
| | 7.2.1.4.3* DOOR LEAF ENCROACHMENT. |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS |
| | SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED |
| | WIDTH OF AN AISLE, |
| | A CORRIDOR, A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, |
| | UNLESS BOTH |
| | OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING |
| | BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENT OF |
| | 7.2.1.4.3.2. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES AND NARRATIVE. |
| | |
| | |
| | |
| | 12) SHEET ALS1.114 - THERE ARE INDICATION THAT EACH |
| | STAIR IS INDICATED AS STAIR # 1. SHEET ALS1.101 |
| | INDICATES THEM DIFFERENTLY. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY. |
| | |
| | |
| | |
| | |
| | 13) ENGINEERING DOCUMENTATION - THERE IS NO SPECIFIC |
| | ENGINEEERING DOCUMENTATION REGARDING THE SMOKE CONTROL |
| | FOR THIS PROJECT. |
| | |
| | PER NFPA 101, CH 9 |
| | |
| | 9.3 SMOKE CONTROL. |
| | 9.3.1 INSTALLATION. WHERE REQUIRED BY ANOTHER SECTION |
| | OF THIS |
| | CODE, SMOKE CONTROL SYSTEMS SHALL BE DESIGNED, |
| | INSTALLED, |
| | INSPECTED, TESTED, AND MAINTAINED IN ACCORDANCE WITH |
| | NFPA 92, |
| | STANDARD FOR SMOKE CONTROL SYSTEMS; NFPA 204, STANDARD |
| | FOR |
| | SMOKE AND HEAT VENTING; OR NATIONALLY RECOGNIZED |
| | STANDARDS, |
| | ENGINEERING GUIDES, OR RECOMMENDED PRACTICES, AS |
| | APPROVED BY |
| | THE AUTHORITY HAVING JURISDICTION. |
| | 9.3.2 SYSTEM DESIGN. THE ENGINEER OF RECORD SHALL |
| | CLEARLY IDENTIFY |
| | THE INTENT OF THE SYSTEM, THE DESIGN METHOD USED, THE |
| | APPROPRIATENESS OF THAT METHOD, AND THE REQUIRED MEANS |
| | OF |
| | INSPECTING, TESTING, AND MAINTAINING THE SYSTEM. |
| | |
| | PLEASE REVIEW AND PROVIDE THE SPECIFIC DOCUMENTATION. |
| | |
| | |
| | |
| | 14) DOOR SCHEDULES - IT IS DIFFICULT TO CONFIRM WITH |
| | ANY CERTAINTY THE CORRECT RATING AND HARDWARES OF THE |
| | DOORS DUE TO NO ONE SHEET OF EACH FLOOR HAS ALL THE |
| | DOORS NUMBERS MARKED, |
| | |
| | PLEASE MARK THE DOORS ON THE ALS SHEETS TO BETTER MARK |
| | EACH DOOR NUMBER WITH THE RATING THAT CAN BE CLEARLY |
| | AND ACCURATELY CHECKED AGAINST THE DOOR SCHEDULE. |
| | |
| | PLEASE REVIEW AND CORRECT OR HELP TO CLARIFY |
| | VERIFICATIONS. |
| | |
| | |
| | |
| | |
| | 15) SHEET ALS1.10 & ALS1.108 - THERE IS AN INDICATION |
| | OF A LARGE STAIRCASE CONNECTING THESE TO FLOOR LEVELS. |
| | THERE ARE NO INDICATIONS OF HOW THIS CONVENIENCE |
| | OPENING WILL BE PROTECTED. |
| | |
| | PER NFPA 101, CH 8 |
| | |
| | 8.6.9 CONVENIENCE OPENINGS. |
| | 8.6.9.1 WHERE PERMITTED BY CHAPTERS 11 THROUGH 43, |
| | UNENCLOSED |
| | VERTICAL OPENINGS NOT CONCEALED WITHIN THE BUILDING |
| | CONSTRUCTION SHALL |
| | BE PERMITTED AS FOLLOWS: |
| | (1) SUCH OPENINGS SHALL CONNECT NOT MORE THAN TWO |
| | ADJACENT STORIES |
| | (ONE FLOOR PIERCED ONLY). |
| | (2) SUCH OPENINGS SHALL BE SEPARATED FROM UNPROTECTED |
| | VERTICAL |
| | OPENINGS SERVING OTHER FLOORS BY A BARRIER COMPLYING |
| | WITH 8.6.5. |
| | (3) SUCH OPENINGS SHALL BE SEPARATED FROM CORRIDORS. |
| | (4) *IN OTHER THAN APPROVED, EXISTING CONVENIENCE |
| | OPENINGS, SUCH |
| | OPENINGS SHALL BE SEPARATED FROM OTHER FIRE OR SMOKE |
| | COMPARTMENTS ON THE SAME FLOOR. |
| | (5) IN NEW CONSTRUCTION, THE CONVENIENCE OPENING SHALL |
| | BE SEPARATED |
| | FROM THE CORRIDOR REFERENCED IN 8.6.9.1(3) BY A SMOKE |
| | PARTITION, |
| | UNLESS CHAPTERS 11 THROUGH 43 REQUIRE THE CORRIDOR TO |
| | HAVE A FIRE |
| | RESISTANCE RATING. |
| | (6) *SUCH OPENINGS SHALL NOT SERVE AS A REQUIRED MEANS |
| | OF EGRESS. |
| | |
| | 8.6.9.2 WHERE PERMITTED BY CHAPTERS 11 THROUGH 43, |
| | UNENCLOSED |
| | VERTICAL OPENINGS CREATED BY CONVENIENCE STAIRWAYS |
| | SHALL COMPLY WITH |
| | ALL OF THE FOLLOWING: |
| | (1) THE CONVENIENCE STAIR OPENINGS SHALL NOT SERVE AS |
| | REQUIRED |
| | MEANS OF EGRESS. |
| | (2) THE BUILDING SHALL BE PROTECTED THROUGHOUT BY AN |
| | APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH |
| | SECTION 9.7. |
| | (3) *THE CONVENIENCE STAIR OPENINGS SHALL BE PROTECTED |
| | IN |
| | ACCORDANCE WITH THE METHOD DETAILED FOR THE PROTECTION |
| | OF |
| | VERTICAL OPENINGS IN NFPA 13, STANDARD FOR THE |
| | INSTALLATION OF |
| | SPRINKLER SYSTEMS. |
| | (4) IN NEW CONSTRUCTION, THE AREA OF THE FLOOR OPENING |
| | SHALL NOT |
| | EXCEED TWICE THE HORIZONTAL PROJECTED AREA OF THE |
| | STAIRWAY. |
| | (5) FOR NEW CONSTRUCTION, SUCH OPENINGS SHALL NOT |
| | CONNECT MORE THAN |
| | FOUR CONTIGUOUS STORIES, UNLESS OTHERWISE PERMITTED BY |
| | CHAPTERS |
| | 11 THROUGH 43. |
| | |
| | PLEASE REVIEW, CORRECT AND PROVIDE DETAILS. |
| | |
| | |
| | |
| | |
| | 16) SHEET ALS1.108 - THERE IS AN INDICATION OF AN EXIT |
| | SIGN AT THE TOP OF THE STAIRWAY NOTED ABOVE; HOWEVER, |
| | PER 8.6.9.2 (1) THE STAIR SHALL NOT SERVE AS A REQUIRED |
| | MEANS OF EGRESS. |
| | |
| | THIS STAIR APPEARS TO SERVE AS A REQUIRED MEANS OF |
| | EGRESS. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES AND NARRATIVE. |
| | |
| | |
| | |
| | |
| | 17) SHEET FP 301 - THERE ARE INDICATIONS OF TWO PUMPS. |
| | THE PUMP SCHEDULES INDICATE 750 GPM WITH MAX CHURN |
| | PRESSURE OF 235. |
| | |
| | THOSE THESE ARE NOT SHOP DRAWINGS, THESE FIGURES DO NOT |
| | APPEAR TO BE ABLE TO SUPPORT FIRE DEMANDS ON UPPER |
| | FLOORS, NOR SEPARATE FIRE LOCATED IN DIFFERENT TOWERS |
| | AT THE SAME TIME. |
| | |
| | PLEASE REIVEW AND CORRECT OR JUSTIFY WITH THE EOR |
| | NARRATIVE. |
| | |
| | |
| | |
| | 18) SHEET A1.105 & E - THERE IS AN INDICATION OF A |
| | GENERATOR ROOM; HOWEVER, THERE ARE NO INDICATIONS OF |
| | WHAT TYPE, CLASS, ETC. |
| | |
| | PER NFPA 110 |
| | |
| | CHAPTER 4 CLASSIFICATION OF EMERGENCY POWER SUPPLY |
| | SYSTEMS (EPSSS) |
| | 4.1* GENERAL. THE EPSS SHALL PROVIDE A SOURCE OF |
| | ELECTRICAL |
| | POWER OF REQUIRED CAPACITY, RELIABILITY, AND QUALITY TO |
| | LOADS FOR |
| | A LENGTH OF TIME AS SPECIFIED IN TABLE 4.1(A) AND |
| | WITHIN A SPECIFIED |
| | TIME FOLLOWING LOSS OR FAILURE OF THE NORMAL POWER |
| | SUPPLY |
| | AS SPECIFIED IN TABLE 4.1(B). |
| | |
| | 4.2* CLASS. THE CLASS DEFINES THE MINIMUM TIME, IN |
| | HOURS, FOR |
| | WHICH THE EPSS IS DESIGNED TO OPERATE AT ITS RATED LOAD |
| | WITHOUT |
| | BEING REFUELED OR RECHARGED. [SEE TABLE 4.1(A).] |
| | 4.3 TYPE. THE TYPE DEFINES THE MAXIMUM TIME, IN |
| | SECONDS, |
| | THAT THE EPSS WILL PERMIT THE LOAD TERMINALS OF THE |
| | TRANSFER |
| | SWITCH TO BE WITHOUT ACCEPTABLE ELECTRICAL POWER. TABLE |
| | 4.1(B) |
| | PROVIDES THE TYPES DEFINED BY THIS STANDARD. |
| | 4.4* LEVEL. THIS STANDARD RECOGNIZES TWO LEVELS OF |
| | EQUIPMENT |
| | INSTALLATION, PERFORMANCE, AND MAINTENANCE. |
| | 4.4.1* LEVEL 1 SYSTEMS SHALL BE INSTALLED WHERE FAILURE |
| | OF THE |
| | EQUIPMENT TO PERFORM COULD RESULT IN LOSS OF HUMAN LIFE |
| | OR |
| | SERIOUS INJURIES. |
| | 4.4.2* LEVEL 2 SYSTEMS SHALL BE INSTALLED WHERE FAILURE |
| | OF THE |
| | EPSS TO PERFORM IS LESS CRITICAL TO HUMAN LIFE AND |
| | SAFETY. |
| | 4.4.3 ALL EQUIPMENT SHALL BE PERMANENTLY INSTALLED. |
| | 4.4.4* LEVEL 1 AND LEVEL 2 SYSTEMS SHALL ENSURE THAT |
| | ALL LOADS |
| | SERVED BY THE EPSS ARE SUPPLIED WITH ALTERNATE POWER |
| | THAT |
| | MEETS ALL THE FOLLOWING CRITERIA: |
| | (1) OF A QUALITY WITHIN THE OPERATING LIMITS OF THE |
| | LOAD |
| | (2) FOR A DURATION SPECIFIED FOR THE CLASS AS DEFINED |
| | IN TABLE |
| | 4.1(A) |
| | (3) WITHIN THE TIME SPECIFIED FOR THE TYPE AS DEFINED |
| | IN TABLE |
| | 4.1(B) |
| | |
| | THE GENERATOR SHALL BE INSTALLED UNDER SEPARATE SHOP |
| | DRAWINGS. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS AND A NOTE OF |
| | ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 19) SHEET A 1.108 & ALS 1.108 - STAIRWAYS # 5 & 9 |
| | INDICATE EXIT SIGNS AND OPENINGS; HOWEVER, THERE ARE NO |
| | DOORS INDICATED ON THESE SHEETS OR ANY OTHER SHEET FOR |
| | THESE OPENINGS. |
| | |
| | PER NFPA 101 CH 7, EXIT STAIRWELLS ARE TO BE PROTECTED. |
| | |
| | 7.2.2.5 ENCLOSURE AND PROTECTION OF STAIRS. |
| | 7.2.2.5.1 ENCLOSURES. |
| | 7.2.2.5.1.1 ALL INSIDE STAIRS SERVING AS AN EXIT OR |
| | EXIT COMPONENT |
| | SHALL BE ENCLOSED IN ACCORDANCE WITH 7.1.3.2. |
| | |
| | 7.1.3.2 EXITS. |
| | 7.1.3.2.1 WHERE THIS CODE REQUIRES AN EXIT TO BE |
| | SEPARATED FROM OTHER |
| | PARTS OF THE BUILDING, THE SEPARATING CONSTRUCTION |
| | SHALL MEET THE |
| | REQUIREMENTS OF SECTION 8.2 AND THE FOLLOWING: |
| | (1) *THE SEPARATION SHALL HAVE A MINIMUM 1-HOUR FIRE |
| | RESISTANCE |
| | RATING WHERE THE EXIT CONNECTS THREE OR FEWER STORIES. |
| | |
| | (8) OPENINGS IN THE SEPARATION SHALL BE PROTECTED BY |
| | FIRE DOOR |
| | ASSEMBLIES EQUIPPED WITH DOOR CLOSER COMPLYING WITH |
| | 7.2.1.8. |
| | |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY. |
| | |
| | |
| | |
| | |
| | 20) OUTDOOR TERRACE/POOL/ROOFTOP AREAS - THERE DOES NOT |
| | APPEAR TO BE ANY BBQ'S PROPOSED FOR THIS PROJECT; |
| | HOWEVER, SHOULD THEY BE A FUTURE INSTALL THEY SHALL |
| | COMPLY WITH THE ALL APPLICABLE CODES INCLUDING NFPA 1 |
| | |
| | 10.10.6 COOKING EQUIPMENT. |
| | 10.10.6.1 FOR OTHER THAN ONE- AND TWO-FAMILY DWELLINGS, |
| | NO |
| | HIBACHI, GRILL, OR OTHER SIMILAR DEVICES USED FOR |
| | COOKING, HEATING, |
| | OR ANY OTHER PURPOSE SHALL BE USED OR KINDLED ON ANY |
| | BALCONY, |
| | UNDER ANY OVERHANGING PORTION, OR WITHIN 10 FT (3 M) OF |
| | ANY |
| | STRUCTURE. |
| | 10.10.6.1.1 LISTED ELECTRIC PORTABLE, TABLETOP GRILLS, |
| | NOT TO EXCEED |
| | 200 SQUARE INCHES OF COOKING SURFACE, OR OTHER SIMILAR |
| | APPARATUS |
| | SHALL BE PERMITTED. |
| | 10.10.6.2 FOR OTHER THAN ONE- AND TWO-FAMILY DWELLINGS, |
| | NO |
| | HIBACHI, GRILL, OR OTHER SIMILAR DEVICES USED FOR |
| | COOKING SHALL BE |
| | STORED ON A BALCONY. |
| | 10.10.6.3* LISTED EQUIPMENT PERMANENTLY INSTALLED IN |
| | ACCORDANCE |
| | WITH ITS LISTING, APPLICABLE CODES, AND MANUFACTURER?S |
| | INSTRUCTIONS |
| | SHALL BE PERMITTED. |
| | 10.10.7 INSTALLATION OF PATIO HEATERS. THE INSTALLATION |
| | OF PATIO |
| | HEATERS SHALL COMPLY WITH 69.3.11. |
| | |
| | SHOULD THERE BE REVISIONS, BBQ'S SHALL BE CLEARLY |
| | IDENTIFIED, LOCATED PER THE CODE AND ALL MANUFACTURES |
| | SPECIFICATIONS ATTACHED, AND COMPLY WITH THOSE |
| | SPECIFICATIONS, PRIOR TO ANY APPROVAL. |
| | |
| | PLEASE ENSURE COMPLIANCE. |
| | |
| | |
| | |
| | |
| | 21) RESIDENTIAL TOWER SHEETS - AT THE FIRE SERVICE |
| | ELEVATOR EXIT DOOR TO THE STARIWELL THE DOOR OPENS INTO |
| | THE REQUIRED EGRESS OF THE CORRIDOR DOOR AND VISA A |
| | VERSA. |
| | |
| | PER NFPA 101, CH 7 |
| | |
| | 7.2.1.4.3* DOOR LEAF ENCROACHMENT. |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS |
| | SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED |
| | WIDTH OF AN AISLE, |
| | A CORRIDOR, A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, |
| | UNLESS BOTH |
| | OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING |
| | BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENT OF |
| | 7.2.1.4.3.2. |
| | 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS |
| | SHALL NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE |
| | REQUIRED WIDTH |
| | OF AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING, |
| | UNLESS THE DOOR |
| | LEAF IS EQUIPPED WITH AN APPROVED SELF-CLOSING DEVICE |
| | AND IS NOT |
| | REQUIRED BY THE PROVISIONS OF 7.2.1.4.2 TO SWING IN THE |
| | DIRECTION OF |
| | EGRESS TRAVEL. |
| | |
| | PLEASE REVIEW AND CORRECT OT JUSTIFY/CLARIFY WITH |
| | SPECIFIC CODE REFERENCES. |
| | |
| | |
| | |
| | |
| | |
| | 23) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | |
| | 24) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |