| 2020-03-04 11:09:38 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. CORRECTED. |
| | 7. CORRECTED. |
| | 8. CORRECTED. |
| | 9. CORRECTED. |
| | 10. CORRECTED. |
| | 11. CORRECTED. |
| | 12. CORRECTED. |
| | 13. CORRECTED. |
| | 14. CORRECTED. |
| | 15. CORRECTED. |
| | 16. CORRECTED. |
| | 17. CORRECTED. |
| | 18. SHEETS E.506 AND E.803, SPECIFY WIRES SIZES FOR |
| | GROUNDING SYSTEM TO CONFIRM CODE COMPLIANCE. NEC 250; |
| | WPB FBC 107.2.1 (THESE SHEETS SEEM TO BE A AN EXACT |
| | DUPLICATE, WHY ARE BOTH SHEETS NEEDED? SHEET E.506 IS |
| | NOT SHOWN IN THE LEGEND OF SHEETS ON E.603. ALSO, THE |
| | MAIN BONDING JUMPER SHOULD BE SIZED AT 12.5% OF TOTAL |
| | FEEDER SIZE WHEN USING PARALLEL FEEDS. PROVIDE |
| | CORRECTION. NEC 250.102(C)(1)) |
| | 19. PROVIDE ACCURATE LOAD CALCULATION FOR ALL SERVICES. |
| | NEC 220; WPB FBC 107.2.1 (LOAD CALCULATION FOR HOTEL / |
| | GUEST ROOMS INCLUDES 166,588 VA FOR UNITS WITHOUT |
| | COOKING. I ADDED THE LOAD FOR ALL OF THESE UNITS AND |
| | CAME UP WITH 845,034 VA. PROVIDE CLARIFICATION AND/OR |
| | CORRECTION.) |
| | 20. CORRECTED. |
| | 21. CORRECTED. |
| | 22. CORRECTED. |
| | 23. PROVIDE COMPLETED PANEL SCHEDULE FOR EACH PANEL, |
| | INDICATING ANY NEW OR ALTERED CIRCUITS, THE WIRE AND |
| | BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR GFCI |
| | PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE. MANY |
| | PANELS SCHEDULES PROVIDED ARE BLANK OR HAVE LIMITED |
| | INFORMATION. NEC 210.8, 210.12, 210.19, 210.20, 215.5, |
| | 408.4 (SHHET E.616, 3 PANELS SHOWS CIRCUITS BEING FED, |
| | BUT NO LOAD FOR THOSE CIRCUITS. PANELS N2H8, N2H9, AND |
| | N2H12. PROVIDE CORRECTION.) |
| | 24. CORRECTED. |
| | 25. CORRECTED. |
| | 26. CORRECTED. |
| | 27. CORRECTED. |
| | |
| | NEW COMMENTS: |
| | |
| | 28. SHEET E.207D, RESTROOM 0756 AND 0757, THE |
| | RECEPTACLE OUTLET IS NOT GFCI PROTECTED. PROVIDE |
| | CORRECTION. NEC 210.8 |
| | 29. SHEET E.107D AND E.108D, THERE SHOULD BE A MINUMUM |
| | OF 3 FOOT CANDLES OF LIGHT AT THE POOL WATER SURFACE |
| | AND THE POOL WET DECK SURFACE FOR OUTDOOR POOLS, AND 10 |
| | FOOT CANDLES FOR INDOOR POOLS. PROVIDE COMPLIANCE. FBC |
| | 454.1.4.2 |
| | 30. SHEET E.301 AND E.303, KEYNOTE 1 SHOWS A RECEPTACLE |
| | OUTLET FOR A TV IN A WATERPROOF ENCLOSURE. A RECEPTACLE |
| | OUTLET IS NOT PERMITTED IN THE TUB OR SHOWER SPACE. |
| | PROVIDE CORRECTION. NEC 406.9(C) |
| | 31. SHEETS E.306, 307, 308, 309, 310, AND 311 ALL SHOW |
| | INCORRECT WIRING OF BATHROOM CIRCUITS IN MODELS C1, D2, |
| | B3.1, D3, D1, E1, B5, D4, AND B6. THERE MAY BE SOME |
| | THAT I MISSED. A MINIMUM OF ONE 20 AMPERE BRANCH |
| | CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE |
| | OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS. |
| | WHEN AN INDIVIDUAL CIRCUIT IS RAN TO A BATHROOM AND |
| | THIS CIRCUIT IS USED FOR LIGHTING AND RECEPTACLE |
| | OUTLETS, THIS CIRCUIT CANNOT BE USED IN ANOTHER |
| | BATHROOM. IF THE CIRCUIT IS USED ONLY FOR THE |
| | RECEPTACLE OUTLETS, IT CAN BE USED TO FEED OTHER |
| | RECEPTACLE OUTLETS IN A DIFFERENT BATHROOM. SEVERAL |
| | LOCATIONS SHOW CIRCUIT 14 OR 26, SOMETIMES BOTH, BEING |
| | USED FOR LIGHTING AND RECEPTACLE OUTLETS IN MULTILPLE |
| | BATHROOMS. PROVIDE CORRECTION. NEC 210.11(C)(3) |
| | 32. SHEET E.501 SHOWS A 1200 AMP SERVICE FOR FUTURE |
| | RETAIL USE. THIS DOES NOT HAVE A DESIGNATION THE SAME |
| | AS OTHER MAINS DO. PLEASE CLARIFY THE NAME OF THIS |
| | MAIN. WPB FBC 107.2.1 |
| | 33. SHEET E.502A, BUSWAY RISER HA, 11TH FLOOR |
| | DISCONNECT IS SHOWN AS A 300 AMP BREAKER WITH A 200 AMP |
| | FEEDER TO THE DOWNSTREAM PANEL. PROVIDE CLARIFICATION |
| | AND/OR CORRECTION. NEC 215.2, 240.4, 310.15(B)(16); WPB |
| | FBC 107.2.1 |
| | 34. SHEET E.603, PANEL SCHEDULE LEGEND. THE LEGEND FOR |
| | SHEETS E.604, E.606, E.607, E.610, E.611, E.616, AND |
| | E.622 DO NOT MATCH WHAT IS ON THOSE PAGES. SHEET E.506 |
| | IS NOT IN THE LEGEND. PROVIDE CORRECTIONS. WPB FBC |
| | 107.2.1 |
| | 35. SHEET E.614, PANEL SWBNRR IS SHOWN AS A 1000 AMP |
| | PANEL. THE RISER DIAGRAM SHOWS THIS AS A 2500 AMP |
| | PANEL. THE LOADS SPECIFIED IN PANEL SCHEDULE ARE |
| | DIFFERENT THAN WHAT IS SHOWN ON RISER. PROVIDE |
| | CLARIFICATION AND/OR CORRECTION. WPB FBC 107.2.1; NEC |
| | 215.2, 240.4, 310.15(B)(16) |
| | 36. SHEET E.615, PANEL DN4H1 IS SHOWN AS AN 800 AMP |
| | PANEL WITH A LOAD OF 945 AMPS. PROVIDE CLARIFICATION |
| | AND/OR CORRECTION. WPB FBC 107.2.1; NEC 215.2, 240.4, |
| | 310.15(B)(16) |
| | 37. SHEET E.615, PANEL N2H1 IS SHOWN AS AN 400 AMP |
| | PANEL WITH A LOAD OF 1959 AMPS. PROVIDE CLARIFICATION |
| | AND/OR CORRECTION. WPB FBC 107.2.1; NEC 215.2, 240.4, |
| | 310.15(B)(16) |
| | 38. SHEET E.622, PANEL N4H7E IS SHOWN AS AN 225 AMP |
| | PANEL WITH A LOAD OF 277 AMPS. PROVIDE CLARIFICATION |
| | AND/OR CORRECTION. WPB FBC 107.2.1; NEC 215.2, 240.4, |
| | 310.15(B)(16) |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |