2020-03-04 11:09:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED.
 12. CORRECTED.
 13. CORRECTED.
 14. CORRECTED.
 15. CORRECTED.
 16. CORRECTED.
 17. CORRECTED.
 18. SHEETS E.506 AND E.803, SPECIFY WIRES SIZES FOR
 GROUNDING SYSTEM TO CONFIRM CODE COMPLIANCE. NEC 250;
 WPB FBC 107.2.1 (THESE SHEETS SEEM TO BE A AN EXACT
 DUPLICATE, WHY ARE BOTH SHEETS NEEDED? SHEET E.506 IS
 NOT SHOWN IN THE LEGEND OF SHEETS ON E.603. ALSO, THE
 MAIN BONDING JUMPER SHOULD BE SIZED AT 12.5% OF TOTAL
 FEEDER SIZE WHEN USING PARALLEL FEEDS. PROVIDE
 CORRECTION. NEC 250.102(C)(1))
 19. PROVIDE ACCURATE LOAD CALCULATION FOR ALL SERVICES.
 NEC 220; WPB FBC 107.2.1 (LOAD CALCULATION FOR HOTEL /
 GUEST ROOMS INCLUDES 166,588 VA FOR UNITS WITHOUT
 COOKING. I ADDED THE LOAD FOR ALL OF THESE UNITS AND
 CAME UP WITH 845,034 VA. PROVIDE CLARIFICATION AND/OR
 CORRECTION.)
 20. CORRECTED.
 21. CORRECTED.
 22. CORRECTED.
 23. PROVIDE COMPLETED PANEL SCHEDULE FOR EACH PANEL,
 INDICATING ANY NEW OR ALTERED CIRCUITS, THE WIRE AND
 BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR GFCI
 PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE. MANY
 PANELS SCHEDULES PROVIDED ARE BLANK OR HAVE LIMITED
 INFORMATION. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4 (SHHET E.616, 3 PANELS SHOWS CIRCUITS BEING FED,
 BUT NO LOAD FOR THOSE CIRCUITS. PANELS N2H8, N2H9, AND
 N2H12. PROVIDE CORRECTION.)
 24. CORRECTED.
 25. CORRECTED.
 26. CORRECTED.
 27. CORRECTED.
  
 NEW COMMENTS:
  
 28. SHEET E.207D, RESTROOM 0756 AND 0757, THE
 RECEPTACLE OUTLET IS NOT GFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.8
 29. SHEET E.107D AND E.108D, THERE SHOULD BE A MINUMUM
 OF 3 FOOT CANDLES OF LIGHT AT THE POOL WATER SURFACE
 AND THE POOL WET DECK SURFACE FOR OUTDOOR POOLS, AND 10
 FOOT CANDLES FOR INDOOR POOLS. PROVIDE COMPLIANCE. FBC
 454.1.4.2
 30. SHEET E.301 AND E.303, KEYNOTE 1 SHOWS A RECEPTACLE
 OUTLET FOR A TV IN A WATERPROOF ENCLOSURE. A RECEPTACLE
 OUTLET IS NOT PERMITTED IN THE TUB OR SHOWER SPACE.
 PROVIDE CORRECTION. NEC 406.9(C)
 31. SHEETS E.306, 307, 308, 309, 310, AND 311 ALL SHOW
 INCORRECT WIRING OF BATHROOM CIRCUITS IN MODELS C1, D2,
 B3.1, D3, D1, E1, B5, D4, AND B6. THERE MAY BE SOME
 THAT I MISSED. A MINIMUM OF ONE 20 AMPERE BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
 WHEN AN INDIVIDUAL CIRCUIT IS RAN TO A BATHROOM AND
 THIS CIRCUIT IS USED FOR LIGHTING AND RECEPTACLE
 OUTLETS, THIS CIRCUIT CANNOT BE USED IN ANOTHER
 BATHROOM. IF THE CIRCUIT IS USED ONLY FOR THE
 RECEPTACLE OUTLETS, IT CAN BE USED TO FEED OTHER
 RECEPTACLE OUTLETS IN A DIFFERENT BATHROOM. SEVERAL
 LOCATIONS SHOW CIRCUIT 14 OR 26, SOMETIMES BOTH, BEING
 USED FOR LIGHTING AND RECEPTACLE OUTLETS IN MULTILPLE
 BATHROOMS. PROVIDE CORRECTION. NEC 210.11(C)(3)
 32. SHEET E.501 SHOWS A 1200 AMP SERVICE FOR FUTURE
 RETAIL USE. THIS DOES NOT HAVE A DESIGNATION THE SAME
 AS OTHER MAINS DO. PLEASE CLARIFY THE NAME OF THIS
 MAIN. WPB FBC 107.2.1
 33. SHEET E.502A, BUSWAY RISER HA, 11TH FLOOR
 DISCONNECT IS SHOWN AS A 300 AMP BREAKER WITH A 200 AMP
 FEEDER TO THE DOWNSTREAM PANEL. PROVIDE CLARIFICATION
 AND/OR CORRECTION. NEC 215.2, 240.4, 310.15(B)(16); WPB
 FBC 107.2.1
 34. SHEET E.603, PANEL SCHEDULE LEGEND. THE LEGEND FOR
 SHEETS E.604, E.606, E.607, E.610, E.611, E.616, AND
 E.622 DO NOT MATCH WHAT IS ON THOSE PAGES. SHEET E.506
 IS NOT IN THE LEGEND. PROVIDE CORRECTIONS. WPB FBC
 107.2.1
 35. SHEET E.614, PANEL SWBNRR IS SHOWN AS A 1000 AMP
 PANEL. THE RISER DIAGRAM SHOWS THIS AS A 2500 AMP
 PANEL. THE LOADS SPECIFIED IN PANEL SCHEDULE ARE
 DIFFERENT THAN WHAT IS SHOWN ON RISER. PROVIDE
 CLARIFICATION AND/OR CORRECTION. WPB FBC 107.2.1; NEC
 215.2, 240.4, 310.15(B)(16)
 36. SHEET E.615, PANEL DN4H1 IS SHOWN AS AN 800 AMP
 PANEL WITH A LOAD OF 945 AMPS. PROVIDE CLARIFICATION
 AND/OR CORRECTION. WPB FBC 107.2.1; NEC 215.2, 240.4,
 310.15(B)(16)
 37. SHEET E.615, PANEL N2H1 IS SHOWN AS AN 400 AMP
 PANEL WITH A LOAD OF 1959 AMPS. PROVIDE CLARIFICATION
 AND/OR CORRECTION. WPB FBC 107.2.1; NEC 215.2, 240.4,
 310.15(B)(16)
 38. SHEET E.622, PANEL N4H7E IS SHOWN AS AN 225 AMP
 PANEL WITH A LOAD OF 277 AMPS. PROVIDE CLARIFICATION
 AND/OR CORRECTION. WPB FBC 107.2.1; NEC 215.2, 240.4,
 310.15(B)(16)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746