2020-03-11 09:14:02BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 18100540
 BUILDING PERMIT 30 STORY BLDG W/ TWO TOWERS
 1 ST REVIEW: APRIL 18, 2019
 2 ND REVIEW: MARCH 2, 2020
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,5TH EDITION (2014)
 FBC[AMENDED] = 2014 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 107.5.3 FBC[AMENDED]PLEASE UPDATE SHEET A0.102 SITE
 DATA. THE DIAGRAM IN THE UPPER RIGHT CORNER DOESN'T
 REFLECT THE CHANGES IN ROOMS SHOWN IN THE PLANS.
 COMPARE SHEET A1.500 FOR SUITE AND UNIT COUNTS.
  
 A) AS A GENERAL COMMENT, PLEASE LOOK IN PROJECTDOX AND
 NOTE IF SOME SHEETS MAY NOT HAVE BEEN REPLACED FOR
 SECOND REVIEW. EITHER UPLOAD REVISED SHEETS, LEAVE IT
 DIDN'T CHANGE OR REQUEST IT TO BE DELETED.
  
 B) LEVEL 8 - SHEET A1.260. IS THE COLUMN LAYER TURNED
 OFF? ALSO, MISSING UNIT NUMBER ABOVE UNIT B1 08-22
 THIS SHEET WAS NOT REVISED FROM FIRST REVIEW SO I THINK
 IT REFLECTS OLD LAYOUT. PLEASE UPLOAD NEW LEVEL 8
 RESIDENTIAL SHEET.
  
 C) LEVEL 13-14 - 08 UNITS EACH FLOOR . SHEET A1.265
 SAYS LEVEL 13-14, BUT THEN THE NEXT SHEET IS LEVEL 14.
 PLEASE ADJUST TITLE BLOCK TO STATE LEVEL 13 ONLY.
  
 D) LEVEL 14 - 08 UNITS. SHEET A1.266 IS THE COLUMN
 LAYER TURNED OFF? ALSO, MISSING UNIT NUMBERS.
  
 E) LEVEL 3 - MISSING SUITE NUMBER NEXT TO SUITE 7.1 ON
 SHEET A1.103. LOOKS LIKE IT SHOULD BE SUITE 8.
  
 F) LEVEL 9 - MISSING SUITE NUMBER NEXT BETWEEN SUITE
 1.3B AND 1.3D ON SHEET A1.109
  
 G) LEVEL 16 - SUITE 2B ADA LOOKS LIKE WALL WAS LEFT
 BETWEEN ENTRY AND SLEEPING AREA.
  
 H) LEVEL 17, I CAN'T FIND OFFICE LEVEL FLOOR PLAN. I DO
 SEE RCP AND LIFE SAFETY. PLEASE CHECK IF IT WAS LOADED
 INTO PROJECT DOX.
  
 2) 107.5.3 FBC[AMENDED]SHEET 03.052 - A1.240 - HOTEL
 TOWER FLOOR PLAN - LEVEL 8 HAS NOT BEEN UPDATED. PLEASE
 UPLOAD A NEW VERSION, OR REQUEST IT BE DELETED FROM THE
 FOLDER. LEVEL EIGHT IS SHOWN ON PODIUM LEVEL 8 DRAWING
 03.014 - A1.108 - PODIUM FLOOR PLAN AND IN QUADRANT
 PAGES AS WELL.
 3) 107.5.3 FBC[AMENDED]PLEASE ADD COMMUNICATION SYMBOL
 TO SUITE 4.2B ON SHEET A1.243
 ROOM SUMMARY SHEET STATES LEVEL 12-15 AS COMMUNICATION.
 PLEASE ADD SYMBOL TO THOSE ROOMS AS WELL.
 ADD BOTH SYMBOLS TO SUITE 2.B ON SHEET A1.246
 PLEASE LOOK AT MOBILITY FEATURES DATA LAST LINE WHERE
 IT SAYS LEVEL 8-16 SUITE 4.2B. I DO SEE THAT THERE IS
 ADA ON LEVEL 16. ADD SYMBOLS AND CORRECT WHERE IT
 STATES 8-16 OR SHOW THAT LEVEL 8-15 SUITE 4.2B ARE ADA
 SUITES.
  
 4) 224.5 FBC[A]DISPERSION. GUEST ROOMS REQUIRED TO
 PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 AND
 GUEST ROOMS REQUIRED TO PROVIDE COMMUNICATION FEATURES
 COMPLYING WITH 806.3 SHALL BE DISPERSED AMONG THE
 VARIOUS CLASSES OF GUEST ROOMS, AND SHALL PROVIDE
 CHOICES OF TYPES OF GUEST ROOMS, NUMBER OF BEDS, AND
 OTHER AMENITIES COMPARABLE TO THE CHOICES PROVIDED TO
 OTHER GUESTS.WHERE THE MINIMUM NUMBER OF GUEST ROOMS
 REQUIRED TO COMPLY WITH 806 IS NOT SUFFICIENT TO ALLOW
 FOR COMPLETE DISPERSION, GUEST ROOMS SHALL BE DISPERSED
 IN THE FOLLOWING PRIORITY: GUEST ROOM TYPE, NUMBER OF
 BEDS, AND AMENITIES. AT LEAST ONE GUEST ROOM REQUIRED
 TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL
 ALSO PROVIDE COMMUNICATION FEATURES COMPLYING WITH
 806.3. NOT MORE THAN 10 PERCENT OF GUEST ROOMS REQUIRED
 TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL
 BE USED TO SATISFY THE MINIMUM NUMBER OF GUEST ROOMS
 REQUIRED TO PROVIDE COMMUNICATION FEATURES COMPLYING
 WITH 806.3.
 -ONLY 10 PERCENT OF REQUIRED ROOMS CAN SHARE
 COMMUNICATION AND MOBILITY. PLEASE SHOW COMMUNICATION
 ROOMS ONLY SHARE IN ONE SUITE.
 -PLEASE VERIFY THAT ROOMS ARE EVENLY DISTRIBUTED FOR
 ROOM TYPES AND PRICE RANGE.
  
 5) 806.4 FBC[A]HOTEL,MOTEL AND CONDOMINIUM SPECIAL
 ACCESSIBILITY FEATURES. THIS SECTION DOES NOT RELIEVE
 THE OWNER OF THE RESPONSIBILITY OF PROVIDING ACCESSIBLE
 ROOMS IN CONFORMANCE WITH SECTION 224 AND 806 OF THIS
 CODE. IN ALL BUILDINGS, STRUCTURES AND FACILITIES
 LICENSED AS A HOTEL, MOTEL OR RESORT CONDOMINIUM
 PURSUANT TO CHAPTER 509, F.S., A NUMBER OF ROOMS
 EQUALING AT LEAST 5 PERCENT OF THE GUEST ROOMS MINUS
 THE TOTAL NUMBER OF REQUIRED (ACCESSIBLE) ROOMS
 REQUIRED BY TABLE 224.2 SHALL PROVIDE THE FOLLOWING
 ADDITIONAL SPECIAL ACCESSIBILITY FEATURES:
 (I) GRAB RAILS IN BATHROOMS AND TOILET ROOMS WHICH
 COMPLY WITH SECTION 604.5.
 (II) ALL BEDS IN DESIGNED ACCESSIBLE GUEST ROOMS SHALL
 BE OPEN-FRAME TYPE THAT ALLOWS THE PASSAGE OF LIFT
 DEVICES.
 (III)WATER CLOSETS THAT COMPLY WITH SECTION 604.4.
 -SHOW WHICH ROOMS COMPLY WITH 806.4
  
 6) 224.1 ADVISORY FBC[A]ARE THERE NON-TRANSIENT ROOMS
 (MORE THAN 30 DAY STAY)?
 IF SO, THOSE ROOMS MAY FALL UNDER THE FAIRHOUSING
 GUIDELINES IN ADDITION TO ACCESSIBILITY FBC 2017 6 TH
 EDITION.
  
 FAIRHOUSING REVIEW:
 7) 1986 ANSI [A117.1] IF A DESIGNER OR BUILDER CHOOSES
 TO FOLLOW AN ACCESSIBILITY STANDARD OTHER THAN THE 1986
 ANSI A117.1 STANDARD, OR A MORE RECENT VERSION OF THE
 ANSI A117.1, SUCH AS THE 1992 CABO/ANSI, THAT CARE BE
 TAKEN TO ENSURE THE STANDARD USED IS AT LEAST
 EQUIVALENT TO OR STRICTER THAN THE 1986 ANSI A117.1
 STANDARD.
 -WHAT STANDARD IS BEING APPLIED FOR COMPLIANCE WITH
 FAIR HOUSING? YOU CAN USE GUIDELINES THAT FALL WITHIN
 THE SAFE HARBOR FOR COMPLIANCE?
  
 A) IT WOULD BE HELPFUL TO ADD A MATRIX OF ROOMS ON
 SHEET A1.500 WHICH BATHROOM SPEC IS BEING USED AND
 APPLY THE FOLLOWING FOR SPEC A AND B
  
 SPECIFICATION A:
 IF SPECIFICATION A IS USED IT APPLIES TO ALL BATHROOMS,
 AND ALL FIXTURES IN THOSE BATHROOMS MUST BE USABLE.
 SPECIFICATION B:
 IF SPECIFICATION B IS USED, IT APPLIES TO ONE BATHROOM,
 AND ONLY ONE OF EACH TYPE OF FIXTURE MUST BE USABLE;
 ADDITIONAL BATHROOMS IN THE UNIT ARE EXEMPT ONLY FROM
 MANEUVERING AND CLEAR FLOOR SPACE REQUIREMENTS AT
 FIXTURES.
  
 B) PLEASE ADD TO FAIRHOUSING NOTES ON SHEET A1.528.
 THIS SAYS ALL BATHROOMS TO BE SPEC A. PLEASE ADJUST
 NOTE SINCE BOTH SPEC ARE BEING USED.
  
 C) ADD NOTE FOR USABLE HARDWARE.
 REQUIREMENT 3 - USABLE DOORS. THE DOORS IN COMMON
 SPACES AND THE SIDE ENTERING INTO DWELLING UNITS NEED
 TO HAVE USABLE HARDWARE THAT CAN BE USED WITHOUT TIGHT
 GRASPING OR TWISTING.
 -TYPICALLY THE HARDWARE WOULD BE A LEVER TYPE. THIS
 TYPE OF HARDWARE WOULD NOT BE REQUIRED ONCE INSIDE THE
 UNIT. YOU MAY WANT TO CLARIFY HARDWARE ON THE DOOR
 SCHEDULE.
  
 D) DOOR SCHEDULE ON SHEET A6.104 IS DISTORTED AND
 INFORMATION IS NOT LEGIBLE. PLEASE ADJUST AND POPULATE
 AS NEEDED.
  
 E) SHOW ACCESSIBLE ROUTES FOR EACH UNIT TYPE.
  
 F) ADD DETAIL OF HOW ACCESS IS GAINED AT RESIDENTIAL
 BALCONY. IS THERE ELEVATION CHANGE TO MEET FAIRHOUSING
 MAX OF 4 INCHES TOP OF THRESHOLD?
  
 LIFE SAFETY:
  
 8) 3006.2 FBC[B]SHEET A1.107 SHOWS NO ELEVATOR LOBBY ON
 LEVEL 7 AT ELEVATORS 8, 9 AND 10. IF REQUIRED PLEASE
 SHOW THE DOORS.
 1024.4 FBC[B]TERMINATION. EXIT PASSAGEWAYS ON THE LEVEL
 OF EXIT DISCHARGE SHALL TERMINATE AT AN EXIT DISCHARGE.
 EXIT PASSAGEWAYS
 ON OTHER LEVELS SHALL TERMINATE AT AN EXIT.
 EXIT DISCHARGE. THAT PORTION OF A MEANS OF EGRESS
 SYSTEM BETWEEN THE TERMINATION OF AN EXIT AND A PUBLIC
 WAY.
  
 9) 3005.5 FBC[B]SHUNT TRIP. WHERE ELEVATOR HOISTWAYS,
 ELEVATOR MACHINE ROOMS, CONTROL ROOMS AND CONTROL
 SPACES CONTAINING ELEVATOR CONTROL EQUIPMENT ARE
 PROTECTED WITH AUTOMATIC SPRINKLERS, A MEANS INSTALLED
 IN ACCORDANCE WITH SECTION 21.4 OF NFPA 72 SHALL BE
 PROVIDED TO DISCONNECT AUTOMATICALLY THE MAIN LINE
 POWER SUPPLY TO THE AFFECTED ELEVATOR PRIOR TO THE
 APPLICATION OF WATER. THIS MEANS SHALL NOT BE
 SELF-RESETTING. THE ACTIVATION OF AUTOMATIC SPRINKLERS
 OUTSIDE THE HOISTWAY, MACHINE ROOM, MACHINERY SPACE,
 CONTROL ROOM OR CONTROL SPACE SHALL NOT DISCONNECT THE
 MAIN LINE POWER SUPPLY.
  
 10) 3006.2 FBC[B]HOISTWAY OPENING PROTECTION REQUIRED.
 ELEVATOR HOISTWAY DOOR OPENINGS SHALL BE PROTECTED IN
 ACCORDANCE WITH SECTION 3006.3 WHERE AN ELEVATOR
 HOISTWAY CONNECTS MORE THAN THREE STORIES, IS REQUIRED
 TO BE ENCLOSED WITHIN A SHAFT ENCLOSURE IN ACCORDANCE
 WITH SECTION 712.1.1 AND ANY OF THE FOLLOWING
 CONDITIONS APPLY:
 5. THE BUILDING IS A HIGH RISE AND THE ELEVATOR
 HOISTWAY IS MORE THAN 75 FEET (22 860 MM) IN HEIGHT.
 THE HEIGHT OF THE HOISTWAY SHALL BE MEASURED FROM THE
 LOWEST FLOOR TO THE HIGHEST FLOOR OF THE FLOORS SERVED
 BY THE HOISTWAY.
 -IS THE PRE FUNCTION AREA OPEN AIR? IT IS HARD TO TELL
 BUT IT APPREARS TO BE COVERED BY RESIDENTIAL ABOVE.
 -FREIGHT ELEVATOR DOES NOT HAVE ELEVATOR LOBBY ON THE 8
 TH FLOOR. PLEASE REVIEW 3006.2 FOR OPENING PROTECTION
 ON SHAFT MORE THAN 75 FEET.
  
 11) 107.5.3 FBC[AMENDED]ADD SCALE TO LIFE SAFETY PLANS.
 I THINK IT IS 1/16 SCALE.
 ALSO, IS THERE A LIFE SAFETY SHEET FOR THE PARK ABOVE
 THE TENNIS PAVILION? PLEASE PROVIDE OR LET ME KNOW
 WHICH SHEET I CAN FIND IT.
  
 12) 1004 FBC[B]PLEASE PROVIDE TOTAL OCCUPANT LOAD FOR
 EACH EGRESS DOOR AT GRADE WHERE THE DOOR PROVIDES
 EGRESS FROM MULTIPLE AREAS. FOR EXAMPLE EGRESS DOORS IN
 HOTEL LOBBY PICKUP THE STAIRS AND OTHER AREAS FROM
 FIRST LEVEL USES. I AM LOOKING FOR DATA TAG LIKE WAS
 USED AT STAIRWAY DOORS.
  
 13) 1025.1 FBC[B]GENERAL. APPROVED LUMINOUS EGRESS PATH
 MARKINGS DELINEATING THE EXIT PATH SHALL BE PROVIDED IN
 HIGH-RISE BUILDINGS OF GROUP A, B, E, I, M, AND R-1
 OCCUPANCIES IN ACCORDANCE WITH SECTIONS 1025.1 THROUGH
 1025.5.
 -ST4 AND ST3 FROM R-1 LEVELS TO MEET 1025.1 FOR
 LUMINOUS MARKINGS.
  
 14) 1013.2 FBC[B] FLOOR-LEVEL EXIT SIGNS IN GROUP R-1.
 WHERE EXIT SIGNS ARE REQUIRED IN GROUP R-1 OCCUPANCIES
 BY SECTION 1013.1, ADDITIONAL LOW-LEVEL EXIT SIGNS
 SHALL BE PROVIDED IN ALL AREAS SERVING GUEST ROOMS IN
 GROUP R-1 OCCUPANCIES AND SHALL COMPLY WITH SECTION
 1013.5.
 -ADD LOW LEVEL EXIT SIGNS AS REQUIRED, OR STATE WHICH
 PAGE THIS INFORMATION CAN BE FOUND.
  
 15) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA. THIS
 IS FOR ALL LIFE SAFETY SHEETS
 A. ADD MAX COMMON PATH AND MAX TRAVEL DISTANCE FOR R-1
 AND R-2 TO ALS1.100 COMPLIANCE SUMMARY FOR FLORIDA
 BUILDING CODE IN ADDITION TO THE PROVIDED NFPA. THE
 MORE RESTRICTIVE CODE WILL APPLY.
 B. SHOW MAXIMUM PATH OF TRAVEL ON ALL L.S. PLANS.
 CURRENTLY, L.S. SHEETS SHOW PATH OF TRAVEL DISTANCE OR
 TOTAL DISTANCE. PLANS SHOULD SHOW BOTH COMMON PATH OF
 TRAVEL AND EXIT ACCESS TRAVEL DISTANCE. THIS SHOULD BE
 DONE FOR WORST CASE IN EACH GENERAL AREA.
  
 16) 1003.5 FBC[B] ELEVATION CHANGE. DOES EXIT FROM
 RESIDENT LOBBY TO STAIR 2 HAVE STEPS? PLEASE REVIEW
 -HOW DO STEPS WORK AT EGRESS FROM RESIDENT LOUNGE TO
 STAIR ST2? PLEASE REVIEW 1003.5 FOR CHANGE IN ELEVATION
 IN PATH OF EGRESS.
  
 17) 1012.9 FBC[B] INTERMEDIATE HANDRAILS. STAIRWAYS
 SHALL HAVE INTERMEDIATE HANDRAILS LOCATED IN SUCH A
 MANNER THAT ALL PORTIONS OF THE STAIRWAY MINIMUM WIDTH
 OR REQUIRED CAPACITY ARE WITHIN 30 INCHES (762 MM) OF A
 HANDRAIL. ON MONUMENTAL STAIRS, HANDRAILS SHALL BE
 LOCATED ALONG THE MOST DIRECT PATH OF EGRESS TRAVEL.
 -CHECK COMPLIANCE WITH 1012.9 AT BALLROOM STEPS.
  
 18) 713.13.4 CHUTE DISCHARGE ROOM. WASTE OR LINEN
 CHUTES SHALL DISCHARGE INTO AN ENCLOSED ROOM SEPARATED
 BY FIRE BARRIERS WITH A FIRE RESISTANCE RATING NOT LESS
 THAN THE REQUIRED FIRE RATING OF THE SHAFT ENCLOSURE
 AND CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR
 HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH
 SECTION 711, OR BOTH. OPENINGS INTO THE DISCHARGE ROOM
 FROM THE REMAINDER OF THE BUILDING SHALL BE PROTECTED
 BY OPENING PROTECTIVES HAVING A FIRE PROTECTION RATING
 EQUAL TO THE PROTECTION REQUIRED FOR THE SHAFT
 ENCLOSURE. DOORS SHALL BE SELF- OR AUTOMATICCLOSING
 UPON THE DETECTION OF SMOKE IN ACCORDANCE WITH SECTION
 716.5.9.3. WASTE CHUTES SHALL NOT TERMINATE IN AN
 INCINERATOR ROOM. WASTE AND LINEN ROOMS THAT ARE NOT
 PROVIDED WITH CHUTES NEED ONLY COMPLY WITH TABLE 509.
 -DOUBLE DOORS TO TRASH ROOM AT BASE LEVEL SHOW 90
 MINUTE RATING, BUT 713.13.4 REQUIRES SAME LEVEL OF
 PROTECTION FOR OPENINGS IN DISCHARGE ROOM EQUAL TO THE
 SHAFT ENCLOSURE (2 HOURS).
  
 19) 420.3 FBC[B]HORIZONTAL SEPARATION AND FBC[B] 602
 FLOOR ASSEMBLIES SEPARATING DWELLING UNITS IN THE SAME
 BUILDINGS, FLOOR ASSEMBLIES SEPARATING SLEEPING UNITS
 IN THE SAME BUILDING AND FLOOR ASSEMBLIES SEPARATING
 DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES
 CONTIGUOUS TO THEM IN THE SAME BUILDING SHALL BE
 CONSTRUCTED AS HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH
 SECTION 711.
 -602 FBC[B]SHEET A7.310 HAS CEILING ASSEMBLIES. PLEASE
 SHOW THE RATED ASSEMBLY FOR CEILINGS SEPARATING
 DWELLING AND SLEEPING UNITS AS STATED IN LIFE SAFETY
 COMPLIANCE SUMMARY ALS1.100.
  
 20) 713.13.3 FBC[B]CHUTE ACCESS ROOMS. ACCESS OPENINGS
 FOR WASTE OR LINEN CHUTES SHALL BE LOCATED IN ROOMS OR
 COMPARTMENTS ENCLOSED BY NOT LESS THAN 1-HOUR FIRE
 BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR
 HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH
 SECTION 711, OR BOTH. OPENINGS INTO THE ACCESS ROOMS
 SHALL BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE
 PROTECTION RATING OF NOT LESS THAN 3/4 HOUR. DOORS
 SHALL BE SELF- OR AUTOMATIC-CLOSING UPON THE DETECTION
 OF SMOKE IN ACCORDANCE WITH SECTION 716.5.9.3.
 -LIFE SAFETY SHEETS SHOW CHUTE ACCESS DOORS AS NOT
 RATED (NR). THESE ACCESS DOORS ARE REQUIRED TO HAVE A
 3/4 HOUR RATING PER 713.13.3.
 - ADD DOOR TAG TO THE DOORS LEADING TO THE TRASH CHUTE
 OR TELL ME WHAT SHEETS THER ARE ON. I WAS LOOKING ON
 QUADRANT SHEETS WHERE THE OTHER TAGS FOR COMMON SPACE
 DOORS WERE LOCATED.
  
 DEFERRED SUBMITTALS
 21) 107.3.4.1 FBC[AMENDED]PLEASE PROVIDE A LIST OF
 DEFERRED SUBMITTALS ON PLANS SO THAT I WILL NOT ASK FOR
 ITEMS THAT WILL BE SUPPLIED AT A LATER DATE, OR
 INDICATE WHICH PAGE A LIST CAN BE FOUND.
 THESE ARE THE ONES I BELIEVE WE WILL NEED, BUT THIS IS
 NOT A COMPLETE LIST.
 A) COMPONENT & CLADDING PRODUCT APPROVALS (COMPLY WITH
 PRESSURES SHOWN ON SHEET S0.0.5)
 B) CURTAIN WALL SUBMITTAL (COMPLY WITH PRESSURES SHOWN
 ON SHEET S0.0.5)
 C) FENESTRATION SHOP DRAWINGS TO INCLUDE ALL WINDOWS,
 DOORS, TRANSOMS, SLIDERS, LOUVERS AND MULL BARS.
 D) FLOORING UNDERLAYMENT WITH THREE REPORTS:
 1. 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND
 SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF
 NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED,
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E90.
 2. 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR
 BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR
 NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN
 ACCORDANCE WITH ASTM E492.
 3. 603.1 FBC[B] ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
 E) RAILINGS AND GUARDRAILS. INCLUDES BALCONIES, STAIRS
 AND COMMON SPACES.
 F) PARKING GARAGE VEHICLE BARRIER PER 406.4.2 FBC[B]
 G) FIRE SPRAY
 H) 806.1 FBC[B] GENERAL REQUIREMENTS. CURTAINS,
 DRAPERIES, HANGINGS AND OTHER DECORATIVE MATERIALS
 SUSPENDED FROM WALLS OR CEILINGS SHALL MEET THE FLAME
 PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 IN
 ACCORDANCE WITH SECTION 806.2 OR BE NONCOMBUSTIBLE.
 I) LIGHTWIEGHT CONCRETE.
 J) WINDOW WASHING EQUIPMENT ATTACHMENTS/LOCATIONS AT
 ROOF.
 K) E.F.I.S. IF APPLICABLE
 L) LIGHTING CONTROLS PER ENERGY CODE C405.2 LIGHTING
 CONTROLS (MANDATORY) C405.5 EXTERIOR LIGHTING
 (MANDATORY)
 M) FINAL GYM EQUIPMENT LAYOUT WITH ACCESSIBILTY
 REQUIREMENTS PROVIDED.
 PRODUCT APPROVALS FOR ROOFING ARE PROVIDED, BUT NO
 SELECTIONS ARE MADE AND IT IS NOT CLEAR WHICH AREA OF
 ROOF RECEIVE.
 ROOFING CAN BE ADDED TO DEFERRED SUBMITTAL LIST.
  
 22) ALSO, PROVIDE PRODUCT APPROVAL FOR ROOF INSULATION
 AND ATTACHMENT.
 OTHER PRODUCT APPROVALS WERE SUBMITTED FOR DOORS, BUT
 THEY WERE NOT STAMPED AS REVIEWED. AS PART OF
 FENESTRATION PACKAGE PROVIDE ALL PRODUCT APPROVALS WITH
 INDICATION THAT THEY WERE REVIEWED BY THE DESIGNER OF
 RECORD.
  
 23) ENERGY CODE REVIEW:
 A) THIS BUILDING WAS BROUGHT IN UNDER 2014 CODE CYCLE.
 PLEASE REVISE TO THAT CODE DATE, OR PROVIDE LETTER OF
 COMPLIANCE THAT CURRENT CODES ARE EQUIVALENT.
 B) C407.2.1 ROOF/CEILING THERMAL ENVELOPE. SECTIONS FOR
 ROOFING AND DOORS SHOW NO DATA. PLEASE INCLUDE THOSE
 VALUES IN THE ENERGY CALCULATIONS.
 C) IN SECTION FOR WALLS THE ASSEMBLY STATES 6 INCH
 INSULATION. WHERE IS THAT ASSEMBLY BEING USED ON THE
 BUILING?
  
 ACCESSIBILITY REVIEW:
 24) 803.1 FBC[A] GENERAL. DRESSING, FITTING, AND LOCKER
 ROOMS SHALL COMPLY WITH 803.
 803.2 FBC[A] TURNING SPACE. TURNING SPACE COMPLYING
 WITH 304 SHALL BE PROVIDED WITHIN THE ROOM.
 803.3 FBC[A] DOOR SWING. DOORS SHALL NOT SWING INTO THE
 ROOM UNLESS A CLEAR FLOOR OR GROUND SPACE COMPLYING
 WITH 305.3 IS PROVIDED BEYOND THE ARC OF THE DOOR
 SWING.
 803.4 FBC[A] BENCHES. A BENCH COMPLYING WITH 903 SHALL
 BE PROVIDED WITHIN THE ROOM.
 903.4 FBC[A] BACK SUPPORT. THE BENCH SHALL PROVIDE FOR
 BACK SUPPORT OR SHALL BE AFFIXED TO A WALL. BACK
 SUPPORT SHALL BE 42 INCHES LONG MINIMUM AND SHALL
 EXTEND FROM A POINT 2 INCHES MAXIMUM ABOVE THE SEAT
 SURFACE TO A POINT 18 INCHES MINIMUM ABOVE THE SEAT
 SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES MAXIMUM FROM
 THE REAR EDGE OF THE SEAT MEASURED HORIZONTALLY.
  
 25) 236.1 FBC[A]GENERAL. AT LEAST ONE OF EACH TYPE OF
 EXERCISE MACHINE AND EQUIPMENT SHALL COMPLY WITH 1004.
  
 1004.1 FBC[A]CLEAR FLOOR SPACE. EXERCISE MACHINES AND
 EQUIPMENT SHALL HAVE A CLEAR FLOOR SPACE COMPLYING WITH
 305 POSITIONED FOR TRANSFER OR FOR USE BY AN INDIVIDUAL
 SEATED IN A WHEELCHAIR. CLEAR FLOOR OR GROUND SPACES
 REQUIRED AT EXERCISE MACHINES AND EQUIPMENT SHALL BE
 PERMITTED TO OVERLAP.
  
 ADVISORY 1004.1 FBC[A]CLEAR FLOOR SPACE. ONE CLEAR
 FLOOR OR GROUND SPACE IS PERMITTED TO BE SHARED BETWEEN
 TWO PIECES OF EXERCISE EQUIPMENT.TO OPTIMIZE SPACE USE,
 DESIGNERS SHOULD CAREFULLY CONSIDER LAYOUT OPTIONS SUCH
 AS CONNECTING ENDS OF THE ROW AND CENTER AISLE SPACES.
 THE POSITION OF THE CLEAR FLOOR SPACE MAY VARY GREATLY
 DEPENDING ON THE USE OF THE EQUIPMENT OR MACHINE. FOR
 EXAMPLE, TO PROVIDE ACCESS TO A SHOULDER PRESS MACHINE,
 CLEAR FLOOR SPACE NEXT TO THE SEAT WOULD BE APPROPRIATE
 TO ALLOW FOR TRANSFER. CLEAR FLOOR SPACE FOR A BENCH
 PRESS MACHINE DESIGNED FOR USE BY AN INDIVIDUAL SEATED
 IN A WHEELCHAIR, HOWEVER, WILL MOST LIKELY BE CENTERED
 ON THE OPERATING MECHANISMS.
  
 26) 1009.1 GENERAL. WHERE PROVIDED, POOL LIFTS, SLOPED
 ENTRIES, TRANSFER WALLS, TRANSFER SYSTEMS, AND POOL
 STAIRS SHALL COMPLY WITH 1009.
 -IF POOL LIFTS ARE PRVIDED PLEASE ADD DETAILS TO THE
 ADA DETAIL SHEET.
 ALSO, ADD ANY ADDITIONAL DETAILS IF APPLICABLE TO ADA
 DETAILS FOR THE POOLS.
  
 27) 405.8 FBC[A]HANDRAILS.RAMP RUNS WITH A RISE GREATER
 THAN 6 INCHES (150 MM) SHALL HAVE HANDRAILS COMPLYING
 WITH 505.
 -SHEET ALS1.107 SHOWS RAMP FROM PRE-FUNCTION UP TO
 ELEVATORS AND STAIR ST8. WILL THERE BE RAILS PROVIDE
 THE RAMP AS REQUIRED? ALSO, IS THE WALKWAY FROM RAMP TO
 STAIR 8 GOING TO HAVE RAIL OR IS IT OPEN FROM ABOVE TO
 PRE-FUNCTION?
  
 CHAPTER 4 ? HIGHRISE
 28) 403.5.3.1 FBC[B]STAIRWAY COMMUNICATION SYSTEM. A
 TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS SYSTEM
 CONNECTED TO AN APPROVED CONSTANTLY ATTENDED STATION
 SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH FLOOR IN
 EACH STAIRWAY WHERE THE DOORS TO THE STAIRWAY ARE
 LOCKED.
 -WILL THE DOORS BE LOCKED FROM THE STAIRWAY SIDE? IF SO
 PLEASE ADD COMMUNICATION SYSTEM AS REQUIRED IN
 403.5.3.1
  
 29) 1022.8 FBC[B] DISCHARGE IDENTIFICATION. AN INTERIOR
 EXIT STAIRWAY AND RAMP SHALL NOT CONTINUE BELOW ITS
 LEVEL OF EXIT DISCHARGE UNLESS AN APPROVED BARRIER IS
 PROVIDED AT THE LEVEL OF EXIT DISCHARGE TO PREVENT
 PERSONS FROM UNINTENTIONALLY CONTINUING INTO LEVELS
 BELOW. DIRECTIONAL EXIT SIGNS SHALL BE PROVIDED AS
 SPECIFIED IN SECTION 1011.
 -IF STAIRWAY 4 AT 2 ND LEVEL TRANSFERS TO STAIRWAY 11
 THAN 1022.8 APPLIES.
  
 30) 403.3.1 FBC[B]NUMBER OF SPRINKLER RISERS AND SYSTEM
 DESIGN. EACH SPRINKLER SYSTEM ZONE IN BUILDINGS THAT
 ARE MORE THAN 420 FEET (128 000 MM) IN BUILDING HEIGHT
 SHALL BE SUPPLIED BY NO FEWER THAN TWO RISERS. EACH
 RISER SHALL SUPPLY SPRINKLERS ON ALTERNATE FLOORS. IF
 MORE THAN TWO RISERS ARE PROVIDED FOR A ZONE,
 SPRINKLERS ON ADJACENT FLOORS SHALL NOT BE SUPPLIED
 FROM THE SAME RISER.
 -PLEASE SEE HOW THIS APPLIES TO OFFICE TOWER ONLY AND
 UPDATE FS DRAWINGS AS APPLICABLE.
  
 -PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW EACH
 COMMENT IS BEING ADDRESSED.
 -FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F 8-5) TO
 DISCUSS COMMENTS, OR E-MAIL ANYTIME [email protected]
  
  
  