Plan Review Notes
Plan Review Notes For Permit 18100540
Permit Number 18100540
Review Stop P
Sequence Number 1
Notes
Date Text
2019-04-09 10:07:161ST REVIEW: 18100540
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: DUE TO THE FACT THAT THESE PLANS ARE
 INCOMPLETE I AM NOT ABLE TO DETERMINE CODE COMPLIANCE
 AT THIS TIME. I HAVE REVIEWED THE INFORMATION PROVIDED
 AND COMMENTED, WHEN A COMPLETE SET OF DESIGN DOCUMENTS
 ARE PROVIDE PLEASE ADDRESS THESE COMMENTS.I WILL THEN
 BE ABLE TO COMPLETE A MORE COMPREHENSIVE REVIEW.
  
 1. PLEASE INDICATE ON THE PLAN WHICH DESIGN DOCUMENT
 WAS USED TO DETERMINE COMPLIANCE TO THE FHA SUCH AS THE
 FHA DESIGN MANUAL OR THE FHA GUIDE LINES FOUND IN THE
 BACK OF THE FBC ACCESSIBILITY BOOK. PER WPB AMEND TO
 FBC 107.2.1
 2. PLEASE CLARIFY ON THE PLAN THAT THE RESIDENTIAL
 UNITS AND AND COMMON AREAS FOR THOSE UNITS SHALL COMPLY
 WITH FHA AND ANSI A117.1-1986.
 3. PLEASE CLARIFY ON THE PLAN THAT ALL OTHER
 OCCUPANCY'S OTHER THAN THE RESIDENTIAL UNITS SHALL
 COMPLY WITH THE 2017 6TH EDITION FLORIDA BUILDING CODE
 ACCESSIBILITY NOT ADA
 4. PLEASE PROVIDE A MATRIX CHART FOR THE RESIDENTIAL
 UNITS SHOWING WHICH BATHROOMS ARE COMPLYING WITH FHA
 AND WHAT DESIGN SPEC IS BEING USED. PER WPB AMENDS TO
 FBC 107.2.1
 5. PLEASE PROVIDE A PLUMBING FIXTURE COUNT BREAK DOWN
 FOR THE BUSINESS, ASSEMBLY AND MERCANTILE OCCUPANCY'S
 PER FBC PL TABLE 403.1
 6. PROVIDE BREAK DOWN OF ACCESSIBLE AND NON ACCESSIBLE
 ROOMS FOR THE HOTEL. PER WPB AMENDS TO FBC 107.2.1
 7. SHT. A0.202 SOME OF THE DETAILS ARE CONFUSING THEY
 ARE COMBINING FHA WITH ADA THESE CODES DO NOT MATCH UP
 AND THE PROJECT SHALL COMPLY WIH THE FBC ACC NOT ADA
 PLEASE CLARIFY. PER WPB AMENDS TO FBC 107.2.1
 8. THE MENS BATHROOM SHALL HAVE URINALS PLEASE PROVIDE
 FIXTURE BREAKDOWN FOR ALL THE POOLS COMPLYING WITH FBC
 PL TABLE 403.6
 9. SHT. A1.505 SUITE 1.2 PROVIDE DIMENSIONS OF THE
 SHOWER. PER WPB AMENDS TO FBC 107.2.1
 10.SHT. A1.510 - A1.528 THE FHA SPEC DESIGNATION IS
 MISSING FROM SOME OF THE BATHROOMS EACH RESIDENTIAL
 UNIT SHALL BE DESIGNATED SPEC A OR B FOR THE BATHROOMS.
 PER FHA
 11.SHT. A1.510 - A1.528 SOME OF THE CLEAR FLOOR SPACE
 AND LOCATION OF GRAB BAR BACKING LOCATION ARE MISSING
 THESE SHALL BE SHOWN ON ALL ENLARGED FLOOR PLANS WHERE
 THEY ARE REQUIRED. PER WPB AMENDS TO FBC 107.2.1
 12. SHT. A1.527 + A1.600 DETAIL 13 THE WING WALL NEXT
 TO THE TOILET SHALL NOT EXTEND MORE THAN 24" FROM REAR
 WALL THIS REQUIREMENT IS FOR ALL FHA COMPLIANT
 BATHROOMS. PER FHADM REQ. #7 PG 7.43
 13. SHOW THE DEPTH OF THE LAVATORY'S IN ALL FHA
 COMPLIANT BATHROOMS. PER FHADM REQ. #7 PG 7.43
 14. SHT. A1.600 DETAIL #11 IS SHOW MULTIPLE SHOWER
 LAYOUTS ON TOP OF EACH OTHER PLEASE CLARIFY AND SHOW
 DIMENSIONS. PER WPB AMEND TO FBC 107.2.1
 15. SHT. A1.600 - A1.602 SHOW ALL DIMENSIONS OF THE
 BATHROOMS. PER WPB AMEND TO FBC 107.2.1
 16. SHT. A1.524 A1.600 DETAIL #7 SHOW CLEAR FLOOR
 SPACE. PER WPB AMEND TO FBC 107.2.1
 17. SHT. A1.600+601 SOME OF THE DETAILS ARE SHOW DOUBLE
 FIXTURE OVERLAPPING PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
 18. SHT A1.521 THE CLEAR FLOOR SPACE AT THE KITCHEN IS
 OVERLAPPING THE SINK AND CABINETS PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
 19. SHT A1.602 SHOW ALL CLEAR FLOOR SPACE WITH
 DIMENSIONS FOR ACCESSIBLE TOILET, LAVATORY'S, URINALS
 AND SHOWER AND WATER FOUNTAINS. PER WPB AMEND TO FBC
 107.2.1 AND FBC ACC CH6
 20. SHT A1.602 SHOW DIMENSIONS FOR THE STALL AND
 SHOWER. PER WPB AMEND TO FBC 107.2.1
 21. SHT. A1.602 DETAIL #2 IN THE ACCESSIBLE STALL THE
 SHOWER IS ENCROACHING INTO THE CLEAR FLOOR SPACE OF THE
 TOILET SPACE IT SHALL COMPLY WITH FBC ACC 604.3.1
 22. SHT A1.602 THE TRANSFER SHOWER SHALL HAVE A SEAT.
 PER FBC ACC 608.4
 23. IN THE PLUMBING FIXTURE BREAKDOWN PLEASE INDICATE
 COMPLIANCE WITH POTTY PARITY. PER FBC ACC 403.1.3
 24. SHT. A1.602 PLEASE LABEL ALL ENLARGED BATHROOM
 GROUPS WITH THE ROOM NUMBER AND MENS OR WOMENS. PER WPB
 AMEND TO FBC 107.2.1
 25. PROVIDE ENLARGED BATHROOM DETAILS FOR ALL COMMON
 AREA IN ALL THE DIFFERENT OCCUPANCY I FOUND THESE
 MISSING, 07-55, 07-27, 07-61, 07-60, 08-28, 08-21,
 08-38, 08-39, 08-21. PER WPB AMEND TO FBC 107.2.1
 26. PROVIDE DIMENSIONS FOR THE ROOF SCUPPERS MAIN AND
 EMERGENCY SCUPPERS. PER WPB AMEND TO FBC 107.2.1
 27. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTILLATION
 GUIDES FOR THE LIQUID APPLIED WATERPROOF MEMBRANE FOR
 THE SHOWER PANS IT SHALL COMPLY WITH FBC PL 417.5.2.6
 AND ANSI A118.10
 28. SHT. A7.502 ON THE DEPRESSION DETAIL THE HYDRO BAN
 SHALL BE PITCHED TO TH SHOWER DRAIN FLANGE UNDER THE
 MORTAR BED AND SEAL TO THE BOTTOM FLANGE UNDER THE
 CLAMPING RING. PER FBC PL 417.5.2
 29. IN THE RESIDENTIAL COMMON AREA LOUNGE AND SCREENING
 ROOM AND RESIDENTIAL POOL IT DOES NOT APPEAR TO BE ANY
 COMMON BATHROOMS PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
 30. PLEASE INDICATE ON THE PLAN ALL WORK SHALL COMPLY
 WITH 2017 6TH EDITION FLORIDA BUILDING CODE , PLUMBING,
 FUEL GAS, MECHANICAL, ACCESSIBILITY AND FHA
 31. SHT P-100 WHAT IS THE 2'X 2' SAND PIT LOCATED NEAR
 GRID LINES B+8. PER WPB AMEND TO FBC 107.2.1
 32. SHT. P'S LABEL AND TAG ALL RISERS ON ALL FLOOR
 PLANS. PER WPB AMEND TO FBC 107.3.5.1.3(13)
 33. ON SANITARY FLOOR PLAN SHOW ALL COMMON AREA
 BATHROOMS OR NOTE WHERE ENLARGED PLAN CAN BE FOUND. PER
 WPB AMEND TO FBC 107.2.1
 34. PLEASE IDENTIFY WHAT THE IWS IS SERVING. PER WPB
 AMEND TO FBC 107.2.1
 35. SHT P 107B SHOWS AN AAV THESE TYPE OF VENTS ARE
 ONLY ALLOWED TO SERVE FIXTURES THAT ARE NO MORE THAN 4
 BRANCH INTERVALS FROM THE TOP OF THE VENT STACK UNLESS
 A RELIEF VENT IS PROVIDED PLEASE CLARIFY . PER FBC PL
 918.3.1
 36. SHT. P-109 IF PONDING CAN OCCUR ON THIS LEVEL
 OVERFLOW DRAINS WILL BE REQUIRED FOR THE PD. PER FBC PL
 1108.1
 37. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS FOR ALL
 PUMPS AND VALVES INCLUDING MIXING VALVE AND PRESSURE
 REDUCING.PER WPB AMEND TO FBC 107.2.1
 38. PROVIDE COMPLETE COLLECTION ISOMETRIC DRAWING FOR
 ALL UNDER GROUND PLUMBING PLEASE SEPARATE EACH
 DIFFERENT SYSTEM FOR CLARITY AND INCLUDE SIZING DFU
 LOADS SGFT DRAINED. WPB AMEND TO FBC 107.3.5.1.3(13)
 39. A WYE STAINER IS REQUIRED AT ALL PRESSURE REDUCING
 VALVES PLEASE SHOW ON ALL DETAILS AND ISOMETRIC
 DRAWING. PER FBC PL 604.8
 40. PLACE NOTE ON PLAN SHUT OFF VALVES FOR STACKABLE
 WASHING MACHINES IN THE RESIDENCIAL UNITS SHALL BE
 ACCESSIBLE. PER FBC PL 606.3
 41. IN PUBLIC BATHROOMS TEMPERED WATER SHALL BE
 DELIVERED FROM LAVATORIES AND GROUP WASH FIXTURES
 LOCATED IN PUBLIC TOILET FACILITIES PROVIDED FOR
 CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER SHALL
 BE DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3. PER FBC PL 416.5
 42. THE ENLARGED PLUMBING FLOOR PLANS APPEAR TO HAVE
 TAGS ON THE STACKS THAT ARE INCOMPLETE PLEASE MAKE SURE
 ALL STACKS ARE LABBELED AND TAGED TO MATHCH THE
 ISOMETRIC DRAWING AND FULL FLOOR PLANS. PER WPB AMEND
 TO FBC 107.2.1
 43. SHT. P-701 I CAN NOT DETERMINE CODE COMPLIANCE ON
 THIS PAGE PLEASE SPLIT RISER AND ORIENT THE DRAWING SO
 THE BOTTOM OF THE BUILDING MATCHES UP TO THE BOTTOM OF
 THE PLAN SHEET.PER WPB AMEND TO FBC 107.2.1
 44. SHT. P-701 PLEASE LABEL THE UNIT BRANCHES .PER WPB
 AMEND TO FBC 107.2.1
 45. PROVIDE COMPLETE STORM ISOMETRIC WITH SQFT AND
 SLOPE OF THE PIPE. PER WPB AMEND TO FBC 107.3.5.1.3(13)
 46. SHT. P-703 ONLY 1 FIXTURE IS ALLOWED UPSTREAM OF
 THE WET VENT ON THE BATHROOM GROUP SS/2 . PER FBC PL
 912.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]