| 2019-04-09 10:07:16 | 1ST REVIEW: 18100540 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: DUE TO THE FACT THAT THESE PLANS ARE |
| | INCOMPLETE I AM NOT ABLE TO DETERMINE CODE COMPLIANCE |
| | AT THIS TIME. I HAVE REVIEWED THE INFORMATION PROVIDED |
| | AND COMMENTED, WHEN A COMPLETE SET OF DESIGN DOCUMENTS |
| | ARE PROVIDE PLEASE ADDRESS THESE COMMENTS.I WILL THEN |
| | BE ABLE TO COMPLETE A MORE COMPREHENSIVE REVIEW. |
| | |
| | 1. PLEASE INDICATE ON THE PLAN WHICH DESIGN DOCUMENT |
| | WAS USED TO DETERMINE COMPLIANCE TO THE FHA SUCH AS THE |
| | FHA DESIGN MANUAL OR THE FHA GUIDE LINES FOUND IN THE |
| | BACK OF THE FBC ACCESSIBILITY BOOK. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | 2. PLEASE CLARIFY ON THE PLAN THAT THE RESIDENTIAL |
| | UNITS AND AND COMMON AREAS FOR THOSE UNITS SHALL COMPLY |
| | WITH FHA AND ANSI A117.1-1986. |
| | 3. PLEASE CLARIFY ON THE PLAN THAT ALL OTHER |
| | OCCUPANCY'S OTHER THAN THE RESIDENTIAL UNITS SHALL |
| | COMPLY WITH THE 2017 6TH EDITION FLORIDA BUILDING CODE |
| | ACCESSIBILITY NOT ADA |
| | 4. PLEASE PROVIDE A MATRIX CHART FOR THE RESIDENTIAL |
| | UNITS SHOWING WHICH BATHROOMS ARE COMPLYING WITH FHA |
| | AND WHAT DESIGN SPEC IS BEING USED. PER WPB AMENDS TO |
| | FBC 107.2.1 |
| | 5. PLEASE PROVIDE A PLUMBING FIXTURE COUNT BREAK DOWN |
| | FOR THE BUSINESS, ASSEMBLY AND MERCANTILE OCCUPANCY'S |
| | PER FBC PL TABLE 403.1 |
| | 6. PROVIDE BREAK DOWN OF ACCESSIBLE AND NON ACCESSIBLE |
| | ROOMS FOR THE HOTEL. PER WPB AMENDS TO FBC 107.2.1 |
| | 7. SHT. A0.202 SOME OF THE DETAILS ARE CONFUSING THEY |
| | ARE COMBINING FHA WITH ADA THESE CODES DO NOT MATCH UP |
| | AND THE PROJECT SHALL COMPLY WIH THE FBC ACC NOT ADA |
| | PLEASE CLARIFY. PER WPB AMENDS TO FBC 107.2.1 |
| | 8. THE MENS BATHROOM SHALL HAVE URINALS PLEASE PROVIDE |
| | FIXTURE BREAKDOWN FOR ALL THE POOLS COMPLYING WITH FBC |
| | PL TABLE 403.6 |
| | 9. SHT. A1.505 SUITE 1.2 PROVIDE DIMENSIONS OF THE |
| | SHOWER. PER WPB AMENDS TO FBC 107.2.1 |
| | 10.SHT. A1.510 - A1.528 THE FHA SPEC DESIGNATION IS |
| | MISSING FROM SOME OF THE BATHROOMS EACH RESIDENTIAL |
| | UNIT SHALL BE DESIGNATED SPEC A OR B FOR THE BATHROOMS. |
| | PER FHA |
| | 11.SHT. A1.510 - A1.528 SOME OF THE CLEAR FLOOR SPACE |
| | AND LOCATION OF GRAB BAR BACKING LOCATION ARE MISSING |
| | THESE SHALL BE SHOWN ON ALL ENLARGED FLOOR PLANS WHERE |
| | THEY ARE REQUIRED. PER WPB AMENDS TO FBC 107.2.1 |
| | 12. SHT. A1.527 + A1.600 DETAIL 13 THE WING WALL NEXT |
| | TO THE TOILET SHALL NOT EXTEND MORE THAN 24" FROM REAR |
| | WALL THIS REQUIREMENT IS FOR ALL FHA COMPLIANT |
| | BATHROOMS. PER FHADM REQ. #7 PG 7.43 |
| | 13. SHOW THE DEPTH OF THE LAVATORY'S IN ALL FHA |
| | COMPLIANT BATHROOMS. PER FHADM REQ. #7 PG 7.43 |
| | 14. SHT. A1.600 DETAIL #11 IS SHOW MULTIPLE SHOWER |
| | LAYOUTS ON TOP OF EACH OTHER PLEASE CLARIFY AND SHOW |
| | DIMENSIONS. PER WPB AMEND TO FBC 107.2.1 |
| | 15. SHT. A1.600 - A1.602 SHOW ALL DIMENSIONS OF THE |
| | BATHROOMS. PER WPB AMEND TO FBC 107.2.1 |
| | 16. SHT. A1.524 A1.600 DETAIL #7 SHOW CLEAR FLOOR |
| | SPACE. PER WPB AMEND TO FBC 107.2.1 |
| | 17. SHT. A1.600+601 SOME OF THE DETAILS ARE SHOW DOUBLE |
| | FIXTURE OVERLAPPING PLEASE CLARIFY. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | 18. SHT A1.521 THE CLEAR FLOOR SPACE AT THE KITCHEN IS |
| | OVERLAPPING THE SINK AND CABINETS PLEASE CLARIFY. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | 19. SHT A1.602 SHOW ALL CLEAR FLOOR SPACE WITH |
| | DIMENSIONS FOR ACCESSIBLE TOILET, LAVATORY'S, URINALS |
| | AND SHOWER AND WATER FOUNTAINS. PER WPB AMEND TO FBC |
| | 107.2.1 AND FBC ACC CH6 |
| | 20. SHT A1.602 SHOW DIMENSIONS FOR THE STALL AND |
| | SHOWER. PER WPB AMEND TO FBC 107.2.1 |
| | 21. SHT. A1.602 DETAIL #2 IN THE ACCESSIBLE STALL THE |
| | SHOWER IS ENCROACHING INTO THE CLEAR FLOOR SPACE OF THE |
| | TOILET SPACE IT SHALL COMPLY WITH FBC ACC 604.3.1 |
| | 22. SHT A1.602 THE TRANSFER SHOWER SHALL HAVE A SEAT. |
| | PER FBC ACC 608.4 |
| | 23. IN THE PLUMBING FIXTURE BREAKDOWN PLEASE INDICATE |
| | COMPLIANCE WITH POTTY PARITY. PER FBC ACC 403.1.3 |
| | 24. SHT. A1.602 PLEASE LABEL ALL ENLARGED BATHROOM |
| | GROUPS WITH THE ROOM NUMBER AND MENS OR WOMENS. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | 25. PROVIDE ENLARGED BATHROOM DETAILS FOR ALL COMMON |
| | AREA IN ALL THE DIFFERENT OCCUPANCY I FOUND THESE |
| | MISSING, 07-55, 07-27, 07-61, 07-60, 08-28, 08-21, |
| | 08-38, 08-39, 08-21. PER WPB AMEND TO FBC 107.2.1 |
| | 26. PROVIDE DIMENSIONS FOR THE ROOF SCUPPERS MAIN AND |
| | EMERGENCY SCUPPERS. PER WPB AMEND TO FBC 107.2.1 |
| | 27. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTILLATION |
| | GUIDES FOR THE LIQUID APPLIED WATERPROOF MEMBRANE FOR |
| | THE SHOWER PANS IT SHALL COMPLY WITH FBC PL 417.5.2.6 |
| | AND ANSI A118.10 |
| | 28. SHT. A7.502 ON THE DEPRESSION DETAIL THE HYDRO BAN |
| | SHALL BE PITCHED TO TH SHOWER DRAIN FLANGE UNDER THE |
| | MORTAR BED AND SEAL TO THE BOTTOM FLANGE UNDER THE |
| | CLAMPING RING. PER FBC PL 417.5.2 |
| | 29. IN THE RESIDENTIAL COMMON AREA LOUNGE AND SCREENING |
| | ROOM AND RESIDENTIAL POOL IT DOES NOT APPEAR TO BE ANY |
| | COMMON BATHROOMS PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | 30. PLEASE INDICATE ON THE PLAN ALL WORK SHALL COMPLY |
| | WITH 2017 6TH EDITION FLORIDA BUILDING CODE , PLUMBING, |
| | FUEL GAS, MECHANICAL, ACCESSIBILITY AND FHA |
| | 31. SHT P-100 WHAT IS THE 2'X 2' SAND PIT LOCATED NEAR |
| | GRID LINES B+8. PER WPB AMEND TO FBC 107.2.1 |
| | 32. SHT. P'S LABEL AND TAG ALL RISERS ON ALL FLOOR |
| | PLANS. PER WPB AMEND TO FBC 107.3.5.1.3(13) |
| | 33. ON SANITARY FLOOR PLAN SHOW ALL COMMON AREA |
| | BATHROOMS OR NOTE WHERE ENLARGED PLAN CAN BE FOUND. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | 34. PLEASE IDENTIFY WHAT THE IWS IS SERVING. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | 35. SHT P 107B SHOWS AN AAV THESE TYPE OF VENTS ARE |
| | ONLY ALLOWED TO SERVE FIXTURES THAT ARE NO MORE THAN 4 |
| | BRANCH INTERVALS FROM THE TOP OF THE VENT STACK UNLESS |
| | A RELIEF VENT IS PROVIDED PLEASE CLARIFY . PER FBC PL |
| | 918.3.1 |
| | 36. SHT. P-109 IF PONDING CAN OCCUR ON THIS LEVEL |
| | OVERFLOW DRAINS WILL BE REQUIRED FOR THE PD. PER FBC PL |
| | 1108.1 |
| | 37. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS FOR ALL |
| | PUMPS AND VALVES INCLUDING MIXING VALVE AND PRESSURE |
| | REDUCING.PER WPB AMEND TO FBC 107.2.1 |
| | 38. PROVIDE COMPLETE COLLECTION ISOMETRIC DRAWING FOR |
| | ALL UNDER GROUND PLUMBING PLEASE SEPARATE EACH |
| | DIFFERENT SYSTEM FOR CLARITY AND INCLUDE SIZING DFU |
| | LOADS SGFT DRAINED. WPB AMEND TO FBC 107.3.5.1.3(13) |
| | 39. A WYE STAINER IS REQUIRED AT ALL PRESSURE REDUCING |
| | VALVES PLEASE SHOW ON ALL DETAILS AND ISOMETRIC |
| | DRAWING. PER FBC PL 604.8 |
| | 40. PLACE NOTE ON PLAN SHUT OFF VALVES FOR STACKABLE |
| | WASHING MACHINES IN THE RESIDENCIAL UNITS SHALL BE |
| | ACCESSIBLE. PER FBC PL 606.3 |
| | 41. IN PUBLIC BATHROOMS TEMPERED WATER SHALL BE |
| | DELIVERED FROM LAVATORIES AND GROUP WASH FIXTURES |
| | LOCATED IN PUBLIC TOILET FACILITIES PROVIDED FOR |
| | CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER SHALL |
| | BE DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE |
| | LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA |
| | B125.3. PER FBC PL 416.5 |
| | 42. THE ENLARGED PLUMBING FLOOR PLANS APPEAR TO HAVE |
| | TAGS ON THE STACKS THAT ARE INCOMPLETE PLEASE MAKE SURE |
| | ALL STACKS ARE LABBELED AND TAGED TO MATHCH THE |
| | ISOMETRIC DRAWING AND FULL FLOOR PLANS. PER WPB AMEND |
| | TO FBC 107.2.1 |
| | 43. SHT. P-701 I CAN NOT DETERMINE CODE COMPLIANCE ON |
| | THIS PAGE PLEASE SPLIT RISER AND ORIENT THE DRAWING SO |
| | THE BOTTOM OF THE BUILDING MATCHES UP TO THE BOTTOM OF |
| | THE PLAN SHEET.PER WPB AMEND TO FBC 107.2.1 |
| | 44. SHT. P-701 PLEASE LABEL THE UNIT BRANCHES .PER WPB |
| | AMEND TO FBC 107.2.1 |
| | 45. PROVIDE COMPLETE STORM ISOMETRIC WITH SQFT AND |
| | SLOPE OF THE PIPE. PER WPB AMEND TO FBC 107.3.5.1.3(13) |
| | 46. SHT. P-703 ONLY 1 FIXTURE IS ALLOWED UPSTREAM OF |
| | THE WET VENT ON THE BATHROOM GROUP SS/2 . PER FBC PL |
| | 912.1 |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |