Plan Review Notes
Plan Review Notes For Permit 18100540
Permit Number 18100540
Review Stop G
Sequence Number 1
Notes
Date Text
2019-04-09 10:28:301ST REVIEW: 18100540
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
  
 1. SHT. P-700 SHOW ON THE ISOMETRIC DRAWING THE PIPING
 UP TO THE CONNECTION OF EVERY GAS APPLIANCE INCLUDING
 VALVES, REGULATOR AND DRIP LEG OR PROVIDE A DETAIL FOR
 EACH APPLIANCE OR GROUP WITH A CORRESPONDING TAG TO THE
 OVERALL ISOMETRIC. PER WPB AMEND TO FBC 107.2.1
 2. SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF
 VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE
 THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER
 2017 FBC-FUEL GAS SECS. 502 THRU 505 OR 2017 FBC-RES.
 SEC.G2426 THROUGH G2439.
 3. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR
 2017 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES
 DRYERS).
 4. SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1.
 5. SUBMIT MANUFACTURER?S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS.
 REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON
 THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING
 INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR
 CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017
 FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1.
 6. SHOW DISTANCE BETWEEN 2ND STAGE REGULATOR AND
 APPLIANCE SIZE AND TYPE OF PIPE. PER WPB AMEND TO FBC
 107.2.1
 7. GAS SYSTEM # 3 SHALL BE MARKED FOR REFERENCE ONLY OR
 PROVIDE PIPE SIZE, TYPE, LENGTH OF RUN AND BTU LOAD.
 PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017
 FBC-R SEC. G2413.4.1, G2413.4.2.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  