Plan Review Notes
Plan Review Notes For Permit 18100540
Permit Number 18100540
Review Stop E
Sequence Number 1
Notes
Date Text
2019-03-29 10:23:07CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 BE ADVISED THAT A COMPLETE REVIEW WAS NOT POSSIBLE AT
 THIS TIME. THE PLANS PROVIDED STATE THEY ARE 80%
 DOCUMENTS, BUT IT APPEARS THE ELECTRICAL PORTION IS
 LESS THAN THAT. SOME PAGES, SUCH AS E.502A, E.502B,
 E.503, E.504A, AND E.504B ARE BLANK. OTHER PAGES THAT
 STATE THEY ARE FOR LIGHTING AND POWER ARE MISSING
 LIGHTING IN KEY AREAS, NOT EVEN SHOWING THE REQUIRED
 MEANS OF EGRESS ILLUMINATION PER FBC 1008.2.1, AND NOT
 SHOWING CIRCUIT NUMBERS AND KEY INFORMATION ON POWER
 ITEMS. THEREFORE, THE NEXT REVIEW WILL LIKELY CONTAIN
 COMMENTS FOR CORRECTION THAT ARE NOT ADDRESSED IN THIS
 REVIEW.
  
 1. SHEET E.201B, PROVIDE GFCI PROTECTION FOR ALL
 RECEPTACLE OUTLETS IN KITCHEN. NEC 210.8(B)(2)
 2. SHEET E.202A, PROVIDE GFCI PROTECTION FOR ALL
 RECEPTACLE OUTLETS IN BATHROOM. NEC 210.8(B)(1)
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE AND DOWNSTREAM PANELS, INCLUDING INFORMATION
 FROM THE POWER COMPANY STATING WHAT THE AVAILABLE SHORT
 CIRCUIT CURRENT IS FOR THE SERVICE TO CONFIRM THE
 STATED AIC RATING OF THE SERVICE EQUIPMENT AND
 DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 5. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FOR RESIDENTIAL
 AREAS, A MINIMUM OF 75 PERCENT OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICACY LAMPS. FBC EC C405.1, C405.4.2
 6. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
 7. PROVIDE VOLTAGE DROP CALCULATIONS TO COMPLY WITH
 CODE. FBC EC C405.6.3
 8. PROVIDE BLOCK NOTE INDICATING COMPLIANCE: ?WITHIN 30
 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD
 DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDE TO
 THE BUILDING OWNER, INCLUDING: 1. A SINGLE LINE DIAGRAM
 OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM AND 2.
 FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR ALL
 DISTRIBUTION.? FBC EC C405.6.4.1
 9. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL
 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE
 OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR
 PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS,
 CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE
 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR
 FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC
 EC C405.6.1
 10. FOR POOL ROOM EQUIPMENT SHOWN ON SHEETS E.205C AND
 E.207A, PROVIDE ENCLOSURE TYPES DESIGNED TO PROTECT
 AGAINST CORROSIVE ENVIRONMENTS. NEC TABLE 110.28
 11. SHEET E.207D, PROVIDE GFCI RECEPTACLE OUTLET FOR
 POOL PER CODE. NEC 680.22(A)
 12. PROVIDE GFCI PROTECTION FOR ALL ELECTRIC WATER
 COOLERS. NEC 422. 5, 422.52
 13. PROVIDE GFCI PROTECTION FOR DISHWASHERS IN DWELLING
 UNITS. NEC 210.8(D)
 14. SHEET E.218 AND E.405, PANEL SWBNHR DOES NOT APPEAR
 TO HAVE THE PROPER CLEARANCE TO ALLOW FOR ONE ENTRANCE
 TO AND EGRESS FROM THIS SPACE. ADDITIONAL INFORMATION
 IS NEEDED TO CONFIRM AS THERE IS NO PANEL SCHEDULE FOR
 THIS PANEL, OR ANY PERTINENT INFORMATION SUPPLIED.
 PROVIDE CLARIFICATION AND/OR CORRECTIONS AS NEEDED. NEC
 110.26(C)
 15. NOTE 5 ON SHEETS E.301, E.302, E.303, AND NOTE 8 ON
 SHEETS E.304, E.305, E.306, E.307, E.308, AND E.309 DO
 NOT PROVIDE AFCI PROTECTION TO CODE. ALL BRANCH
 CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12
 16. SHEET E.505, FEEDER FROM GDP-GEN2 TO ATS ER IS
 SHOWN AS A 400 AMP FEEDER. HOWEVER, THIS IS FED FROM A
 600 AMP BREAKER. THE ATS IS ONLY RATED FOR 400 AMPS PER
 DESCRIPTION ON PLAN. PROVIDE CLARIFICATION AND/OR
 CORRECTIONS AS NEEDED. NEC 110.3, 310.15(B)(16), 701.4,
 701.5
 17. PROVIDE GROUND FAULT PROTECTION PER NEC 230.95.
 18. SHEETS E.506 AND E.803, SPECIFY WIRES SIZES FOR
 GROUNDING SYSTEM TO CONFIRM CODE COMPLIANCE. NEC 250;
 WPB FBC 107.2.1
 19. PROVIDE ACCURATE LOAD CALCULATION FOR ALL SERVICES.
 NEC 220; WPB FBC 107.2.1
 20. SHEET E.601, METER CENTER LOAD SUMMARY SHOWS A
 TOTAL LOAD FOR MC-1 AS 1,064,094 VA, WITH A DEMAND LOAD
 OF 330,120 VA. BUT THE FEEDER TO MC-1 SHOWS A LOAD OF
 840,000 VA AND A DEMAND LOAD OF 294,000, WITH A
 DIFFERENT NUMBER OF UNITS SPECIFIED. THERE ARE SIMILAR
 PROBLEMS WITH OTHER FEEDER CALCULATIONS. ALL DATA
 SHOULD BE CONSISTENT. PROVIDE CORRECTION. WPB FBC
 107.2.1 NEC 220
 21. THE LOAD CALCULATION PROVIDED FOR HOTEL GUEST ROOM
 SUITES USES THE LOAD CALCULATION METHOD FROM NEC
 220.82. FOR THE DEMAND FACTORS IN THIS SECTION TO BE
 USED, IT MUST BE A 120/240 OR 120/208 THREE WIRE
 (SINGLE PHASE) FEEDER WITH A MINIMUM AMPACITY OF 100
 AMPS. THE LOAD CALCULATION SHOWS THIS AS THREE PHASE.
 THE PANEL SCHEDULE ON SHEET E.603 SHOWS THE PANELS AS
 SINGLE PHASE. PROVIDE CLARIFICATIONS AND CORRECTIONS AS
 NEEDED. NEC 220; WPB FBC 107.2.1
 22. GUEST ROOM FEEDER DEMAND USES 480 VOLT, 3 PHASE FOR
 TOTAL DEMAND CALCULATIONS WHILE OTHER CALCULATIONS ARE
 AT 208 VOLT, 3 PHASE. PROVIDE CLARIFICATIONS AND/OR
 CORRECTIONS AS NEEDED. NEC 220; WPB FBC 107.2.1
 23. PROVIDE COMPLETED PANEL SCHEDULE FOR EACH PANEL,
 INDICATING ANY NEW OR ALTERED CIRCUITS, THE WIRE AND
 BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR GFCI
 PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE. MANY
 PANELS SCHEDULES PROVIDED ARE BLANK OR HAVE LIMITED
 INFORMATION. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4
 24. PROVIDE DETAILS OF SELECTIVE COORDINATION PER NEC
 700.28 AND 701.27.
 25. PROVIDE DETAILS OF ARC ENERGY REDUCTION PER NEC
 240.87
 26. PER NEC 230.72(B), THE DISCONNECTS FOR EMERGENCY
 SYSTEMS SHALL BE LOCATED REMOTELY FROM NORMAL POWER
 SYSTEMS. IT APPEARS FROM THIS DESIGN THAT THE NORMAL
 POWER FEEDERS AND THE EMERGENCY POWER FEEDERS ARE FED
 FROM THE SAME SWITCH BOARDS. PROVIDE CLARIFICATION
 AND/OR CORRECTION AS NEEDED. NEC 230.72(B)
 27. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER