2019-04-18 15:07:33****CORRECTIONS****
 W.P.B. PERMIT: 18100540
 REVIEWED: APRIL 18, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,5TH EDITION (2014)
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 107.2.1 FBC[B]DRAWINGS STATE THAT THEY ARE AT 80
 PERCENT.
  -A FULL REVIEW CANNOT BE PROVIDED UNTIL 100% PLANS ARE
 PROVIDED. THIS REVIEW IS BASED ON THE 80 PERCENT PLANS
 PROVIDED. WHEN RE-UPLOADING PLEASE ADD DIGITAL
 REPRESENTATION OF SEAL AND REMOVE 80% DESIGNATION.
  
 2) 107.2.1 FBC[AMENDED] PLACE A DIGITALLY CREATED IMAGE
 OF YOUR SEAL AND THE FOLLOWING SENTENCES WHERE AN
 ORIGINAL SIGNATURE WOULD APPEAR IF THE ITEM WERE BEING
 PHYSICALLY SIGNED DATED AND SEALED. THE SENTENCES CAN
 BE PART OF THE DIGITAL SIGNATURE CUSTOM APPEARANCE
 AVAILABLE IN THE SIGNING TOOL, OR THEY CAN BE PLACED ON
 THE DOCUMENT OUTSIDE OF THE DIGITAL SIGNATURE BLOCK.
 THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY
 [LICENSEE, RA, OR LS] ON THE DATE AND/OR TIME STAMP
 SHOWN USING A DIGITAL SIGNATURE.
  -SEE SIGNATURE REVIEW. CONTACT PERMIT LIBRARIAN OR
 BUILDING PLANS EXAMINER FOR OPTIONS TO SATISFY 107.2.1.
  
 3) 107.3.4.1 FBC[AMENDED] DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  -PLEASE PROVIDE A LIST OF DEFERRED SUBMITTALS SO THAT
 I WILL NOT ASK FOR ITEMS THAT WILL BE SUPPLIED AT A
 LATER DATE, OR INDICATE WHICH PAGE A LIST CAN BE FOUND.
  
 4) 107.3.4.1 FBC[AMENDED] PRODUCT APPROVALS. PRODUCT
 APPROVALS ARE PROVIDED FOR WINDOWS, DOORS AND ROOFING.
  A. PLEASE INCULDE ON WINDOW AND DOOR SCHEDULES WHICH
 APPROVAL APPLIES TO EACH OPENING.
  B. NOTE ON ROOFING PLANS WHAT ROOF TYPE EACH AREA WILL
 RECEIVE. IF THESE APPROVALS WILL LIKELY CHANGE YOU MAY
 WANT TO DO ROOFING AS A DEFERRED SUBMITTAL. CHANGING
 ROOF SYSTEMS LATER MAY REQUIRE REVISION IF NOT
 SPECIFIED UP FRONT AS A DEFERRED SUBMITTAL.
  
 5) 107.3.5 FBC[AMENDED] MIN REVIEW CRITERIA. FLOOR
 PLANS FOR ALL RESIDENTIAL LEVELS ARE INCOMPLETE
 (ESPECIALLY ABOVE PODIUM LEVELS). MISSING WALL TYPES,
 DIMENSIONS, DOOR TYPES, OPENING SCHEDULES FINISHES AND
 DETAILS AS APPLICABLE.
  
 6) 107.3.5 FBC[AMENDED] MIN REVIEW CRITERIA.COMPLETE
 ADDING WALL TYPES FOR SOUND CONTROL BETWEEN PUBLIC
 AREAS AND OTHER WALLS AS APPLICABLE.
  
 7) 107.3.5 FBC[AMENDED]ARE BALCONIES SEPARATED? IF SO
 PROVIDE DETAILS.
  
 8) 107.3.5 FBC[AMENDED]SHEET A1.602 ENLARGED
 BATHROOMS.
  -TOILETS DO NOT SHOW UP ON THIS SHEET AND I THINK
 COLUMNS ARE TURNED OFF AS WELL. IS THIS SHEET GOING TO
 BE DIMENSIONED AND CLEAR SPACES SHOWN FOR ADA
 CLEARANCES?
  
 9) 107.3.5 FBC[AMENDED] GEOMETRY PLANS RESIDENTIAL WILL
 NEED TO BE COMPLETE BEFORE REVIEWING. A10.212 TO
 A10.255. OTHER GEOMETRY SHEETS MAT NEED TO BE COMPLETES
 AS WELL.
  
 10) 107.3.5 FBC[AMENDED] MEANS OF EGRESS
  -SHEETS A1.101, A1.202 AND ALS1.101 LOOKING AT
 REVOLVING DOORS IT APPEARS THAT A SMALL REVOLVING DOOR
 IS ON TOP OF LARGER REVOLVING DOOR IN TWO DOORS INTO
 HOTEL LOBBY. ALSO , THIS SMALLER REVOLVE APPEARS OVER
 DOUBLE DOORS NEAR VALET DROP OFF.
  
 11) 107.3.5 FBC[AMENDED] WHERE IS SAYS VALET DROP-OFF
 THERE IS A DIRECTION ARROW THAT MAKES IT APPERAR TO BE
 A ROADWAY. I DON'T SEE THE ARROW ON OTHER SHEETS, SO
 CHECK IF IT SHOULD BE REMOVED.
  
 12) 107.3.5 FBC[AMENDED]SOME DOORS HAVE NUMBERS LIKE
 267, 262 AND OTHERS ARE NOT NUMBERED. THE NUMBERS DO
 NOT CORESPOND TO NUMBERING SYSTEM ON THE DOOR
 SCHEDULE.
  -PLEASE TELL ME HOW THE DOORS CORESPOND TO THE DOOR
 SCHEDULE.
  
 13) ON ALL LIFE SAFETY SHEETS THE COLUMN LAYER DOESN'T
 SHOW UP ON DRAWINGS. IT MAKES THE PLANS TO APPEAR AS IF
 THERE ARE SPACES BETWEEN AREAS.
  A. PLEASE SHOW COLUMNS ON ALL LIFE SAFETY SHEET. ALSO,
 SHEET ALS1.114 AT ELEVATOR LOBBY IN RESIDENTIAL SIDE
 WITH THREE ELEVATOR BANKS LOOKS LIKE WALLS INSTEAD OF
 DOORS.
  B. SAME COMMENT FOR PLAN SHEETS A1.240 - A1.255 AND
 A1.260 - A1.272. PLEASE SHOW COLUMNS ON ALL SHEETS.
  
 14) 107.3.5 FBC[AMENDED] SHEET ALS1.114 CHECK UNIT A4
 OCCUPANCY SIZE AND COUNT
  A. ADJUST SQ. FOOTAGE OF UNIT AS 5,205 SF IS NOT
 CORRECT FOR THE UNIT.
  B. ADJUST OCCUPANCY COUNT TOTALS AS NEEDED.
  
 15) 107.3.5 FBC[AMENDED] SHEET A1.602SHOW DIMENSIONS ON
 ENLARGED BATHROOM PLANS.
  
  
 16) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA. THIS
 IS FOR ALL LIFE SAFETY SHEETS
  A. ADD MAX COMMON PATH AND MAX TRAVEL DISTANCE FOR R-1
 AND R-2 TO ALS1.100 COMPLIANCE SUMMARY
  ADD STAIR 10 AND 12 DATA TO EXIT CAPACITY TABLE. IS
 THERE A STAIRWAY 11?
  B. STAIR 12 MERGES WITH STAIR 6. STAIR DATA SHOULD
 INCLUDE ACTUAL LOAD AT EACH STAIR AND ANY MERGING
 SHOULD BE INCLUDED IN THE TOTAL.
  C. CHECK ALL EXIT CAPACITY TABLES FOR DOOR CAPACITY
 BASED ON .2 INCHES PER OCCUPANT AND THE DOOR WIDTH
 NEEDS TO BE CLEAR WIDTH.
  D. COLUMNS DON?T SHOW ON THE PLAN LIFE SAFETY PLANS.
 PLEASE SHOW COLUMNS ON ALL PLANS.
  E. IT?S NOT CLEAR WHAT THE COMMON PATH OF TRAVEL IS
 AND WHAT THE MAX TRAVEL DISTANCE WILL BE FOR THE
 RESIDENTIAL. COMMON PATH OF TRAVEL WOULD BE FROM MOST
 REMOTE POINT IN UNIT TO THE COORIDOR WHERE 2 EXIT
 OPTIONS ARE PROVIDED.
  F. PROVIDE OCCUPANT LOAD FOR SEPARATE OCCUPANCIES (R-2
 AND S-2), EXITS REQUIRED, EXITS PROVIDED AND OCCUPANT
 LOAD AT EACH EXIT IN ADDITION TO THE LIMITING CAPACITY
 PROVIDED.
  G. ALL LIFE SAFETY SHEETS AND ALL FP SHEETS NEED TO BE
 COORDINATED. STANDPIPES APPEAR TO BLOCK PATH OF EGRESS
 AT GROUND FLOORS AND EGRESS DOORS DON?T LINE UP WITH
 EXTENDED WALLS AT CURTAIN WALL.
  
 17) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA.
 ALS1.101
  A. REVIEW PLACEMENT EXIT SIGN .WHERE DOES THE EXIT
 SIGN NEXT TO TRUCKS EGRESS?
  B. TOILETS DON?T SHOW ON THE PLAN, THEN THEY DON?T
 SHOW ON THE ENLARGED A1602
  C. REVOLVING DOORS OVERLAPPING AND DIFFERENT SIZES.
  D. STAIRWAY 11 SAYS 6IN. STANDPIPE, BUT IT IS 8 IN. ON
 FP.201.B
  E. LABEL FPL VAULT. ALSO LABEL FPL ON OTHER APPLICABLE
 SHEETS.
  F. WHAT ARE THE 2 WALL AREAS THAT LOOK LIKE OPENINGS
 IN FPL VAULT? LOUVERS?
  
 18) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA.
 ALS1.102
  A. ROOM TAG MISSING ON SHEET ALS1.102, A1.102 AND
 A1.208 (PLUS OTHER APPLICABLE SHEETS)
  B. ADD EXIT SIGN TO STAIR 6 FROM GARAGE TO EXIT STAIR.
  
 19) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA.
 ALS1.103
  A. ADD EXIT SIGN TO STAIR 6 FROM GARAGE TO EXIT STAIR.
  B. REVIEW DATA TAG ON UNITS S1.3 (TWO UNITS SHOW
 SAME). SAYS NOT ENCLOSED AND 0 OCCUPANTS.
  
 20) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA.
 ALS1.104
  -REVIEW DATA TAG ON UNIT S1.2. SAYS NOT ENCLOSED AND 0
 OCCUPANTS.
  
 21) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA.
 ALS1.105
  -REVIEW DATA TAG ON UNIT S1.2. SAYS NOT ENCLOSED AND 0
 OCCUPANTS.
  
 22) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA.
 ALS1.106
  -UPDATE PER TYPICAL COMMENTS.
  
 23) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA.
 ALS1.107
  A. IS LEVEL 7 SHARED BY HOTEL AND RESIDENTIAL?
  B. POOL DECK OCCUPANT LOAD SHOWS ZERO.
  C. 1011.6 FBC[B] STAIRWAY LANDINGS. CHECK EGRESS DOOR
 SWING FROM POOL DECK INTO STAIR 5 IS IT TOO FAR INTO
 STAIRWAY PATH OF EGRESS?
  D.1003.5 FBC[B] ELEVATION CHANGE. DOES EXIT FROM
 RESIDENT LOBBY TO STAIR 2 HAVE STEPS? PLEASE REVIEW
  E. HOW DO STEPS WORK AT 2 ND EGRESS FROM RESIDENT
 LOUNGE? (SEE SECTION A4.200)
  F. 1003.5 FBC[B] REVIEW EGRESS AT BALLROOM TO STAIR 8.
 DOES THIS EGRESS USE STAIRS FOR EGRESS?
  G. CHECK EGRESS FROM BALLROOM TERRACE. THE BALLROOM
 ELEVATION IS 2 FEET LOWER THAN RESIDENTIAL DECK. HOW
 DOES EGRESS FROM BALLROOM TO STAIR 7 WORK WITH
 ELEVATION DIFFERENCE?
  H. SHEET A5.104 CHECK DOOR ELEVATION FOR STAIR 2 AT
 7TH LEVEL. THE DOOR IS POSITIONED TWO FEET HIGHER
 BECAUSE THERE ARE STEPS DOWN TO GET TO STAIR 2 AND IT
 LOOKS TO BE SET AT ELEVATION OF POOL DECK AND
 RESIDENTIAL LOUNGE.
  I. CAPACITY SHOWN IN TABLE DOESN?T EXCEED THE AMOUNT
 OF OCCUPANTS ON LEVEL AND IT ISN?T CLEAR WHICH EXITS
 SERVE WHICH OCCUPANTS.
  J. PROVIDE EGRESS BASED ON OCCUPANCY REQUIRED WIDTH
 AND PROVIDED. THE TABLES PROVIDED ARE BASED ON
 CAPACITY, BUT OCCUPANCY NEEDS TO BE LOOKED AT BY AREA
 SERVED.
  K. REVIEW EGRESS FROM TENNIS AND TERRACE AREAS. TENNIS
 COURTS AND TERRACES REQUIRES 292 INCHES OF EGRESS FOR
 1457 OCCUPANTS. STAIR 5 AND 9 STATE (2) 40 INCH DOORS
 FOR 160 INCHES AND STAIRWAY 10 MAY PROVIDE ADDITIONAL
 80 (ADD DATA TO CHART AND THE LOAD FROM LEVEL 8 GETS
 ADDED INTO LEVEL 7 FOR 1005.6 FBC[B] CONVERGENCE).
 TOTAL IS NOW 240, SO 52 INCHES WOULD STILL NEED TO BE
 SUPPLIED WITHIN THE MAX TRAVEL DISTANCE. THERE IS PATH
 GOING TO RESIDENTIAL STAIR, BUT THE DOOR IS 32 INCHES
 AND THE DOOR WOULD NEED TO BE UNLOCKED FROM EGRESS
 SIDE. STAIR 2 ALSO HAS RESIDENTIAL AND POOL AREA
 APPLIED TO THE EGRESS WIDTH OF STAIR 2.
  
 24) 107.3.5 FBC[AMENDED] PLEASE REVIEW HOW MANY
 OCCUPANTS CONTRIBUTE TO EACH EXIT AND CALCULATE TOTAL
 FOR EACH EXIT. CURRENT LIFE SAFETY SEEMS TO LOOK AT
 ENTIRE FLOOR AND BASED ON CAPACITY, BUT EACH FLOOR
 NEEDS MORE DETAIL AS TO HOW MANY OCCUPANTS, NUMBER OF
 EXITS REQUIRED AND CONVERGENCE.
  -SHOW HOW CONVERGENCE IS HANDLED FROM STAIR 10 LEVEL 8
 TO LEVEL 7.
  
 25) 107.3.5 FBC[AMENDED] SHEET ALS1.110 SUITE 12-10
 DOESN?T SHOW OCCUPANT LOAD. PLEASE ADD TO FLOOR COUNT.
  
 26) 107.3.5 FBC[AMENDED] THE REFLECTED CEILING PLANS
 (RCP) DO NOT APPEAR TO BE COMPLETE. PLEASE SUBMIT
 COMPLETED RCP PLANS FOR SECOND REVIEW.
  
 27) 107.3.5 FBC[B] MISSING LS FOR RESIDENTIAL FLOORS 8,
 9, 10 AND 11. THEY HAVE A DIFFERENT CONFIGURATION THAN
 FLOORS 13-30.
  -PROVIDE LIFE SAFTY SHEET FOR EACH FLOOR
 CONFIGURATION.
  
 28) 107.3.5 FBC[AMENDED] SHEET ALS1.111 REMOVE WALL AT
 EGRESS 90 MINUTE DOOR.
  
 29) 107.3.5 FBC[AMENDED] SHEET ALS1.112 OCCUPANT
 SCHEDULE LOAD EXCEEDS EXIT CAPACITY TABLE, AND ROOM
 LABELS DO NOT MATCH SCHEDULE LOADS.
  
 30) 107.3.5 FBC[AMENDED] SHEET ALS1.112 PLANTERS APPEAR
 TO BLOCK ROOF DRAINS.
  
 31) 107.3.5 FBC[B] THE HOTEL LEVEL , AND BUSINESS
 ABOVE, RELY ON TWO INTERIOR STAIRWAYS FOR EGRESS.
  A. BOTH INTERIOR STAIRWAY DOORS ON THE LEVEL OF EXIT
 DISCHARGE ARE SWINGING IN. PLEASE REVIEW THIS AS EACH
 EXIT WILL SERVE MORE THAN 50 PERSONS.
  B. IS THE INTENT TO EGRESS FROM STAIRWAY 4 AT 2ND
 LEVEL AND TRANSFER TO STAIRWAY 11?
  
 32) 107.3.5 FBC[A] COVERED MULTIFAMILY DWELLINGS FOR
 FIRST OCCUPANCY AFTER MARCH 13, 1991, SHALL BE DESIGNED
 AND CONSTRUCTED TO HAVE AT LEAST ONE BUILDING ENTRANCE
 ON AN ACCESSIBLE ROUTE UNLESS IT IS IMPRACTICAL TO DO
 SO BECAUSE OF THE SITE.
  A. SHOW ACCESSIBLE PATH FOR RESIDENTIAL UNITS.
  
 1986 ANSI [A117.1] IF A DESIGNER OR BUILDER CHOOSES TO
 FOLLOW AN ACCESSIBILITY STANDARD OTHER THAN THE 1986
 ANSI A117.1 STANDARD, OR A MORE RECENT VERSION OF THE
 ANSI A117.1, SUCH AS THE 1992 CABO/ANSI, THAT CARE BE
 TAKEN TO ENSURE THE STANDARD USED IS AT LEAST
 EQUIVALENT TO OR STRICTER THAN THE 1986 ANSI A117.1
 STANDARD.
 FHA AND ADA ARE BEING USED, BUT IT IS NOT CLEAR WHICH
 CODE APPLIES TO MIXED USE OCCUPANCIES. PLEASE PROVIDE A
 SUMMARY OF EACH OCCUPANCY AND IF ADA OR FHA IS BEING
 APPLIED.
  -WHAT STANDARD IS BEING USED TO INCORPORATE FAIR
 HOUSING GUIDELINES?
  
 WALKS THAT ARE PART OF ACCESSIBLE ROUTES BECOME RAMPS
 WHEN THEIR SLOPE EXCEEDS 5% (1 IN 20). HANDRAILS ARE
 NOT REQUIRED ON WALKS WITH SLOPES BETWEEN 0% AND 5%,
 BUT THEY ARE REQUIRED ON THOSE STEEPER THAN 5% AND UP
 TO 8.33% (1 IN 12)
  B. CLEARLY INDICATE ANY RAMPS ON PLANS. LEVEL 7 FOR
 EXAMPLE HAS 2 FOOT DIFFERENCE BETWEEN POOL DECK AND
 BALLROOM. RAMPS WILL AFFECT EGRESS AND PATH OF TRAVEL.
  
 IN DWELLING UNITS CONTAINING MORE THAN ONE BATHROOM, IF
 SPECIFICATION A IS SELECTED AS THE BASIS FOR DESIGNING
 A BATHROOM, ALL BATHROOMS IN THE DWELLING UNIT ALSO
 MUST COMPLY WITH THE A SPECIFICATIONS. IF SPECIFICATION
 B IS SELECTED, ONLY ONE BATHROOM IN THE DWELLING UNIT
 MUST MEET THOSE REQUIREMENTS ALL BATHROOMS AS DEFINED
 IN THE GUIDELINES MUST:
 1. BE ON AN ACCESSIBLE ROUTE (REQUIREMENT 4),
 2. HAVE 32-INCH NOMINAL CLEAR WIDTH DOORWAYS
 (REQUIREMENT 3)
 3. HAVE SWITCHES, OUTLETS, AND CONTROLS IN ACCESSIBLE
 LOCATIONS (REQUIREMENT 5)
 4. HAVE REINFORCING AROUND TOILETS, TUBS, AND SHOWERS
 (REQUIREMENT 6)
 5. MEET REQUIREMENT 7, SPECIFICATION A OR B:
 POWDER ROOMS MUST:
 1. BE ON AN ACCESSIBLE ROUTE (REQUIREMENT 4),
 2. HAVE 32-INCH NOMINAL CLEAR WIDTH DOOR-WAYS
 (REQUIREMENT 3), AND
 3. HAVE SWITCHES, OUTLETS, AND CONTROLS IN ACCESSIBLE
 LOCATIONS (REQUIREMENT 5). EXCEPTION WHEN THE POWDER
 ROOM IS THE ONLY TOILET FACILITY ON THE ENTRY LEVEL OF
 A MULTI-STORY UNIT IN A BUILDING WITH ONE OR MORE
 ELEVATORS, IT MUST, IN ADDITION TO REQUIREMENTS 3, 4,
 AND 5, MEET THE REINFORCING SPECIFICATIONS OF
 REQUIREMENT 6 AND THE MANEUVERING AND CLEAR FLOOR
 SPECIFICATIONS OF REQUIREMENT 7.
 101.4.1 FBC[CE] MIXED OCCUPANCY. WHERE A BUILDING
 INCLUDES BOTH RESIDENTIAL AND COMMERCIAL OCCUPANCIES,
 EACH OCCUPANCY SHALL BE SEPARATELY CONSIDERED AND MEET
 THE APPLICABLE PROVISIONS OF FLORIDA BUILDING CODE,
 ENERGY CONSERVATION?COMMERCIAL PROVISIONS OR FLORIDA
 BUILD.
  C. PROVIDE DOCUMENTS TO SHOW COMPLIANCE WITH FBC
 ENERGY FOR EACH OCCUPANCY.
  
 33) 208.1 FBC[A] SHEET A0.102 PARKING. PLEASE INDICATE
 ON THE PLANS WHICH PARKING SPOTS ARE SHARED. IF ANY
 SPOTS ARE NOT TO BE SHARED THEN THEY SHOULD NOT BE
 INCLUDED IN THE SHARED PARKING TABLE.
  A. IF ALL SPOTS ARE SHARED AS INDICATED, PROVIDE
 DETAILS OF HOW TANDEM AND LIFT SPOTS ARE USABLE BY ALL
 OCCUPANCIES.
  B. WHICH OCCUPANCIES ARE SERVED BY VALET AND WHERE DO
 THEY PARK?
  
 34) 206.1 FBC[A] GENERAL. ACCESSIBLE ROUTES SHALL BE
 PROVIDED IN ACCORDANCE WITH 206 AND SHALL COMPLY WITH
 CHAPTER 4.
 208.3.1 FBC[A] LOCATION. WHERE PARKING SERVES MORE THAN
 ONE ACCESSIBLE ENTRANCE, PARKING SPACES COMPLYING WITH
 502 SHALL BE DISPERSED AND LOCATED ON THE SHORTEST
 ACCESSIBLE ROUTE TO THE ACCESSIBLE ENTRANCES.IF THERE
 ARE MULTIPLE ENTRANCES FOR MULTIPLE RETAIL STORES THE
 PARKING SPACES MUST BE DISPERSED TO PROVIDE PARKING AT
 THE NEAREST ACCESSIBLE ENTRANCE. IN PARKING FACILITIES
 THAT DO NOT SERVE A PARTICULAR BUILDING OR FACILITY,
 PARKING SPACES COMPLYING WITH 502 SHALL BE LOCATED ON
 THE SHORTEST ACCESSIBLE ROUTE TO AN ACCESSIBLE
 PEDESTRIAN ENTRANCE OF THE PARKING FACILITY.
  -CURRENT PARKING DOES NOT MEET FBC[A] 208.2.3.1.
 PLEASE PROVIDE REVISED PARKING AND SHOW ACCESSIBLE PATH
 FROM EACH SPACE TO OCCUPANCY SERVED. EACH OCCUPANCY
 SHOULD HAVE REQUIRED NUMBER SPACES AND ACCESSIBLE PATH
 LEADING TO THEM.
  
 35) 224.1.2 FBC[A] GUEST ROOM DOORS AND
 DOORWAYS.ENTRANCES, DOORS, AND DOORWAYS PROVIDING USER
 PASSAGE INTO AND WITHIN GUEST ROOMS THAT ARE NOT
 REQUIRED TO PROVIDE MOBILITY FEATURES COMPLYING WITH
 806.2 SHALL COMPLY WITH 404.2.3.
 A. 224.2, 224.3, 224.4, 224.5 AND 224.6.3 TRANSIENT
 LODGING GUEST ROOMS. THIS IS ISN?T READY FOR REVIEW, SO
 PLEASE LOOK AT ALL SECTIONS OF CODE. FOR INSTANCE,
 GENERAL FLOOR PLAN A1.244 SHOWING FLOORS 12-16 DOESN?T
 PROVIDE ENOUGH INFO THE SATISFY DISPERSION. THAT IS
 WHERE A MATRIX WOULD HELP TO SEE THAT THE ROOMS ARE
 BEING DISPERSED AND THAT ALL ROOMS ARE ACCOUNTED FOR.
  B. ADD MATRIX TO SHOW COMPLIANCE WITH FBC [A] 224.2,
 224.3, 224.4, 224.5 AND 224.6.3 ACCORDING TO THE AMOUNT
 OF ROOMS ON SHEET A0.102 THERE SHOULD BE 11 ROOMS WITH
 MOBILITY FBC[A] 806.2, 17 ROOMS WITH COMMUNICATION
 FBC[A]806.3 AND 10 ADDITIONAL ROOMS WITH SPECIAL
 ACCESSIBLE FEATURES FBC[A] 806.4. AT LEAST ONE, BUT NO
 MORE THAN 10% OF THE ROOMS TO COMPLY WITH MOBILITY CAN
 ALSO BE USED TO COMPLY WITH COMMUNICATION FEATURES.
 THAT WOULD MEAN THAT ONE ROOM CAN BE USED TO SATISFY
 BOTH.
  
 36) 401.2 FBC[CE] APPLICATION. COMMERCIAL BUILDINGS
 SHALL COMPLY WITH ONE OF THE FOLLOWING:
 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1,
 EXCLUDING SECTION 9.4.1.1(G) OF THE STANDARD.
 2. THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN
 ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH
 SECTION C406 AND TENANT SPACES SHALL COMPLY WITH
 SECTION C406.1.1.
 3. THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING
 ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT
 OF THE STANDARD REFERENCE DESIGN BUILDING.
  
 37) 402.1 FBC[A] PROVIDE ACCESSIBLE ROUTE FROM PARKING
 LOT. IN ADDITION TO ACCESSIBLE ENTRANCES REQUIRED BY
 SECTIONS 1105.1.1 THROUGH 1105.1.7 (PARKING GARAGE
 ENTRANCES, ENTRANCES FROM TUNNELS OR ELEVATED WALKWAYS,
 RESTRICTED ENTRANCES, ENTRANCES FOR INMATES OR
 DETAINEES, SERVICE ENTRANCES AND ENTRANCES TO TENANT
 SPACES, DWELLING UNITS AND SLEEPING UNITS), AT LEAST 60
 PERCENT OF ALL PUBLIC ENTRANCES SHALL BE ACCESSIBLE.
 SEE THE EXCEPTIONS FOR ENTRANCES TO AREAS NOT REQUIRED
 TO BE ACCESSIBLE AND LOADING/SERVICE ENTRANCES THAT ARE
 NOT THE ONLY TENANT SPACE ENTRANCE.
  -PROVIDE DETAILS ON PLANS TO SHOW HOW DROP OFF AREAS
 MEET FBC[A] 502 FOR PASSENGER LOADING ZONES AT HOTEL
 AND RESIDENTIAL LOBBY. LENGTH, WIDTH AND MARKINGS.
  
 38) 403.3.2 FBC[B] WATER SUPPLY TO REQUIRED FIRE PUMPS.
 REQUIRED FIRE PUMPS SHALL BE SUPPLIED BY CONNECTIONS TO
 NO FEWER THAN TWO WATER MAINS LOCATED IN DIFFERENT
 STREETS. SEPARATE SUPPLY PIPING SHALL BE PROVIDED
 BETWEEN EACH CONNECTION TO THE WATER MAIN AND THE
 PUMPS. EACH CONNECTION AND THE SUPPLY PIPING BETWEEN
 THE CONNECTION AND THE PUMPS SHALL BE SIZED TO SUPPLY
 THE FLOW AND PRESSURE REQUIRED FOR THE PUMPS TO
 OPERATE.
  -IS THIS ACCOUNTED FOR ON CIVIL AND PLUMBING PLANS?
 PLEASE STATE WHICH SHEETS.
  
 39) 403.5.4 FBC[B] SMOKEPROOF ENCLOSURES. EVERY
 REQUIRED EXIT STAIRWAY SERVING FLOORS MORE THAN 75 FEET
 (22 860 MM) ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT
 VEHICLE ACCESS SHALL BE A SMOKEPROOF ENCLOSURE IN
 ACCORDANCE WITH SECTIONS 909.20 AND 1022.10.
  
 40) 407.4.1 FBC[A] CAR DIMENSIONS. INSIDE DIMENSIONS OF
 ELEVATOR CARS AND CLEAR WIDTH OF ELEVATOR DOORS SHALL
 COMPLY WITH TABLE 407.4.1.
  -PLEASE ADD CAB DIMENSIONS ON PLANS.
  
 41) 704.9 FBC[B] IMPACT PROTECTION. WHERE THE FIRE
 PROTECTIVE COVERING OF A STRUCTURAL MEMBER IS SUBJECT
 TO IMPACT DAMAGE FROM MOVING VEHICLES, THE HANDLING OF
 MERCHANDISE OR OTHER ACTIVITY, THE FIRE PROTECTIVE
 COVERING SHALL BE PROTECTED BY CORNER GUARDS OR BY A
 SUBSTANTIAL JACKET OF METAL OR OTHER NONCOMBUSTIBLE
 MATERIAL TO A HEIGHT ADEQUATE TO PROVIDE FULL
 PROTECTION, BUT NOT LESS THAN 5 FEET FROM THE FINISHED
 FLOOR. EXCEPTION: CORNER PROTECTION IS NOT REQUIRED ON
 CONCRETE COLUMNS IN OPEN OR ENCLOSED PARKING GARAGES.
  -VERIFY IF COLUMNS IN PARKING GARAGE ARE SUBJECT TO
 704.9 IMPACT PROTECTION.
  
 42) 803.1 GENERAL. PROVIDE INTERIOR FINISH SCHEDULES.
  A. SUPPLY MORE DEVELOPED PLANS TO SHOW BUILT INS AND
 FURNITURE LAYOUTS.
  B. ADD FURNITURE PLAN TO ROOMS TO VERIFY ADA AND
 EGRESS COMPLIANCE.
  
 43) 806.1 FBC[B] GENERAL REQUIREMENTS. IN OCCUPANCIES
 IN GROUPS A, E, I AND R-1 AND DORMITORIES IN GROUP R-2,
 CURTAINS, DRAPERIES, HANGINGS AND OTHER DECORATIVE
 MATERIALS SUSPENDED FROM WALLS OR CEILINGS SHALL MEET
 THE FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA 701
 IN ACCORDANCE WITH SECTION 806.2 OR BE NONCOMBUSTIBLE.
  -ADD TO DEFERRED SUBMITTAL LIST IF APPLICABLE.
  
 44) 909.3 FBC[B] SPECIAL INSPECTION AND TEST
 REQUIREMENTS. IN ADDITION TO THE ORDINARY INSPECTION
 AND TEST REQUIREMENTS WHICH BUILDINGS, STRUCTURES AND
 PARTS THEREOF ARE REQUIRED TO UNDERGO, SMOKE CONTROL
 SYSTEMS SUBJECT TO THE PROVISIONS OF SECTION 909 SHALL
 UNDERGO SPECIAL INSPECTIONS AND TESTS SUFFICIENT TO
 VERIFY THE PROPER COMMISSIONING OF THE SMOKE CONTROL
 DESIGN IN ITS FINAL INSTALLED CONDITION. THE DESIGN
 SUBMISSION ACCOMPANYING THE CONSTRUCTION DOCUMENTS
 SHALL CLEARLY DETAIL PROCEDURES AND METHODS TO BE USED
 AND THE ITEMS SUBJECT TO SUCH INSPECTIONS AND TESTS.
 SUCH COMMISSIONING SHALL BE IN ACCORDANCE WITH
 GENERALLY ACCEPTED ENGINEERING PRACTICE AND, WHERE
 POSSIBLE, BASED ON PUBLISHED STANDARDS FOR THE
 PARTICULAR TESTING INVOLVED.
  
 45) 909.4 FBC[B] ANALYSIS. A RATIONAL ANALYSIS
 SUPPORTING THE TYPES OF SMOKE CONTROL SYSTEMS TO BE
 EMPLOYED, THEIR METHODS OF OPERATION, THE SYSTEMS
 SUPPORTING THEM AND THE METHODS OF CONSTRUCTION TO BE
 UTILIZED SHALL ACCOMPANY THE SUBMITTED CONSTRUCTION
 DOCUMENTS AND SHALL INCLUDE, BUT NOT BE LIMITED TO, THE
 ITEMS INDICATED IN SECTIONS 909.4.1 THROUGH 909.4.6.
  
 46) 909.20.5 FBC[B] STAIR PRESSURIZATION ALTERNATIVE.
 WHERE THE BUILDING IS EQUIPPED THROUGHOUT WITH AN
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 903.3.1.1, THE VESTIBULE IS NOT REQUIRED, PROVIDED THAT
 INTERIOR EXIT STAIRWAYS ARE PRESSURIZED TO A MINIMUM OF
 0.10 INCHES OF WATER (25 PA) AND A MAXIMUM OF 0.35
 INCHES OF WATER (87 PA) IN THE SHAFT RELATIVE TO THE
 BUILDING MEASURED WITH ALL STAIRWAY DOORS CLOSED UNDER
 MAXIMUM ANTICIPATED CONDITIONS OF STACK EFFECT AND WIND
 EFFECT.
  -PLEASE PROVIDE RATIONAL ANALYSIS FOR ALL SMOKE
 CONTROL SYSTEMS STATING HOW HOISTWAYS AND STAIRWAYS
 WILL MEET THE CODE REQUIREMENTS.
  
 47) 1006.2.1 FBC TABLE[B] MAXIMUM COMMON PATH OF EGRESS
 TRAVEL DISTANCE.
  -ADD ROWS TO SHEET ALS1.100 TABLE A7.6 TO SHOW DATA
 FOR R OCCUPANCIES.
  
 48) 1006.2.1 FBC TABLE[B] HOW MANY EXITS ARE PROVIDED
 ON RESIDENTIAL (R-2) FLOORS? LIFE SAFETY SHEETS APPEAR
 TO USE ONE EXIT WITH ELEVATOR LOBBY CONNECTING TWO
 SIDES.
  -ADJUST LIFE SAFETY TO STATE HOW MANY EXITS ARE
 REQUIRED, HOW MANY PROVIDED AND MARK EXIT SIGNS AND
 EGRESS PATHS FOR THE REQUIRED NUMBER OF EXITS.
  
 49) 1006.1 ILLUMINATION REQUIRED. THE MEANS OF EGRESS,
 INCLUDING THE EXIT DISCHARGE, SHALL BE ILLUMINATED AT
 ALL TIMES THE BUILDING SPACE SERVED BY THE MEANS OF
 EGRESS IS OCCUPIED.
  -SEE 1006.1 FOR EXCEPTIONS
  
 50) 1006.3 EMERGENCY POWER FOR ILLUMINATION. THE POWER
 SUPPLY FOR MEANS OF EGRESS ILLUMINATION SHALL NORMALLY
 BE PROVIDED BY THE PREMISES? ELECTRICAL SUPPLY. IN THE
 EVENT OF POWER SUPPLY FAILURE, AN EMERGENCY ELECTRICAL
 SYSTEM SHALL AUTOMATICALLY ILLUMINATE ALL OF THE
 FOLLOWING AREAS: (SEE 1006.3 FOR AREAS)
  -PLEASE PROVIDE ELECTRICAL SHEET NUMBERS THAT SHOW THE
 INFORMATION TO MEET 1006.1 AND 1006.3
  
 51) 1010.1.2.1 FBC[B] DIRECTION OF SWING. PIVOT OR
 SIDE-HINGED SWINGING DOORS SHALL SWING IN THE DIRECTION
 OF EGRESS TRAVEL WHERE SERVING A ROOM OR AREA
 CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS OR A
 GROUP H OCCUPANCY.
  A. SHEET A1.201 THE DOOR LEADING OUT OF STAIR 3
 BETWEEN 267 AND 262. IS THIS DOOR SUPPOSE TO SWING IN.
 PLEASE VERIFY THE DIRECTION OF EGRESS AND IT ALSO NEEDS
 A DOOR NUMBER.
  B. SHEET A1.202 THE DOOR LEADING OUT OF STAIR 4
 LABELED 267 . IS THIS DOOR SUPPOSE TO SWING IN. PLEASE
 VERIFY THE DIRECTION OF EGRESS AND IS IT SUPPOSED TO
 HAVE THE SAME DOOR NUMBER AS A DOOR IN STAIR 3?
  C. SHEET A1.204 THE DOOR LEADING OUT OF STAIR 2
 LABELED 262 SWINGS OUT INTO CORRIDOR 01-40. THEN EGRESS
 CONTINUES OUT TO DOOR 291 WHICH IN TURN SWINGS IN.
 PLEASE REVIEW DIRECTION OF EGRESS. ALSO, DOORS IN A
 SERIES WOULD NEED 48 INCHES BETWEEN THEM FROM OPEN
 POSITION (FBC ACCESSIBILITY 404.2.6)
  
 52) 1013.2 FBC[B] FLOOR-LEVEL EXIT SIGNS IN GROUP R-1.
 WHERE EXIT SIGNS ARE REQUIRED IN GROUP R-1 OCCUPANCIES
 BY SECTION 1013.1, ADDITIONAL LOW-LEVEL EXIT SIGNS
 SHALL BE PROVIDED IN ALL AREAS SERVING GUEST ROOMS IN
 GROUP R-1 OCCUPANCIES AND SHALL COMPLY WITH SECTION
 1013.5.
  -ADD FLOOR-LEVEL SIGNS TO LIFE SAFTEY PLANS FOR HOTEL
 FLOORS WITH R-1 UNITS (LEVELS 9-16)
  
 53) 1014.6 FBC[B] HANDRAIL EXTENSIONS. HANDRAILS SHALL
 RETURN TO A WALL, GUARD OR THE WALKING SURFACE OR SHALL
 BE CONTINUOUS TO THE HANDRAIL OF AN ADJACENT FLIGHT OF
 STAIRS OR RAMP RUN. WHERE HANDRAILS ARE NOT CONTINUOUS
 BETWEEN FLIGHTS, THE HANDRAILS SHALL EXTEND
 HORIZONTALLY NOT LESS THAN 12 INCHES BEYOND THE TOP
 RISER AND CONTINUE TO SLOPE FOR THE DEPTH OF ONE TREAD
 BEYOND THE BOTTOM RISER. AT RAMPS WHERE HANDRAILS ARE
 NOT CONTINUOUS BETWEEN RUNS, THE HANDRAILS SHALL EXTEND
 HORIZONTALLY ABOVE THE LANDING 12 INCHES MINIMUM BEYOND
 THE TOP AND BOTTOM OF RAMP RUNS. THE EXTENSIONS OF
 HANDRAILS SHALL BE IN THE SAME DIRECTION OF THE FLIGHTS
 OF STAIRS AT STAIRWAYS AND THE RAMP RUNS AT RAMPS.
  -DETAIL 1/A5.121 AND 1/A5.122 SHOW HOW RAILING
 EXTENSIONS WORK. ALL STAIR SECTIONSA5.101 TO A5.118
 SHOW 12 INCH HORIZONTAL PROJECTION FROM FIRST TREAD
 HEIGHT. PLEASE HAVE DETAIL AND SECTION MATCH SO WE CAN
 SEE HOW THIS AFFECTS WHERE BOTTOM HANDRAILS MEET DOOR
 FRAMES.
  
 54) 1015.6 DAY CARE MEANS OF EGRESS. DAY CARE
 FACILITIES, ROOMS OR SPACES WHERE CARE IS PROVIDED FOR
 MORE THAN 10 CHILDREN THAT ARE 2 1/2 YEARS OF AGE OR
 LESS, SHALL HAVE ACCESS TO NOT LESS THAN TWO EXITS OR
 EXIT ACCESS DOORWAYS.
  -DAYCARE 2 EXITS NEEDED? PLEASE STATE THE AGE AND
 AMOUNT OF CHILDREN ANTICIPATED AT THE DAYCARE.
  
 55) 1022.5 PENETRATIONS. PENETRATIONS INTO AND OPENINGS
 THROUGH INTERIOR EXIT STAIRWAYS AND RAMPS ARE
 PROHIBITED EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT
 AND DUCTWORK NECESSARY FOR INDEPENDENT VENTILATION OR
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE INTERIOR
 EXIT STAIRWAY AND RAMP AND TERMINATING AT A STEEL BOX
 NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 714. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT INTERIOR EXIT STAIRWAYS AND RAMPS.
  -HVAC COMMON FEEDING STAIRS FROM MAIN (SEE STAIRS AT
 VAV-2)-INDEPENDENT SYSTEMS TO FEED STAIRWAYS? PLEASE
 REVIEW PENETRATIONS INTO INTERIOR STAIRWAYS AND PROVIDE
 INDEPENDENT SYSTEMS AS REQUIRED IN 1022.5.
  
 56) 1022.8 FBC[B] DISCHARGE IDENTIFICATION. AN INTERIOR
 EXIT STAIRWAY AND RAMP SHALL NOT CONTINUE BELOW ITS
 LEVEL OF EXIT DISCHARGE UNLESS AN APPROVED BARRIER IS
 PROVIDED AT THE LEVEL OF EXIT DISCHARGE TO PREVENT
 PERSONS FROM UNINTENTIONALLY CONTINUING INTO LEVELS
 BELOW. DIRECTIONAL EXIT SIGNS SHALL BE PROVIDED AS
 SPECIFIED IN SECTION 1011.
  A. IF STAIRWAY 4 AT 2 ND LEVEL TRANSFERS TO STAIRWAY
 11 THAN 1022.8 APPLIES.
  B. REVIEW EGRESS PATH TO STAIR 11. DOUBLE DOORS
 SWINGING INTO PATH AND WIDTH OF 90 DEGREE TURN.
  
 57) 1022.9 FBC[B] SIGNAGE. GENERAL COMMENT.
  A. 1022.9 FBC[B] STAIRWAY IDENTIFICATION SIGNS.
  B. 1022.9.1 FBC[B] SIGNAGE REQUIREMENTS.
  
 58) 1022.10.2 FBC[B] ENCLOSURE ACCESS. ACCESS TO THE
 STAIRWAY WITHIN A SMOKEPROOF ENCLOSURE SHALL BE BY WAY
 OF A VESTIBULE OR AN OPEN EXTERIOR BALCONY.
 EXCEPTION: FBC[B] ACCESS IS NOT REQUIRED BY WAY OF A
 VESTIBULE OR EXTERIOR BALCONY FOR STAIRWAYS USING THE
 PRESSURIZATION ALTERNATIVE COMPLYING WITH SECTION
 909.20.5.
  
 59) 1022.10 FBC[B] SMOKEPROOF ENCLOSURES AND
 PRESSURIZED STAIRWAYS AND RAMPS. WHERE REQUIRED BY
 SECTION 403.5.4 OR 405.7.2, INTERIOR EXIT STAIRWAYS AND
 RAMPS SHALL BE SMOKEPROOF ENCLOSURES OR PRESSURIZED
 STAIRWAYS OR RAMPS IN ACCORDANCE WITH SECTION 909.20.
 1022.10.1 FBC[B] TERMINATION AND EXTENSION. A
 SMOKEPROOF ENCLOSURE OR PRESSURIZED STAIRWAY SHALL
 TERMINATE AT AN EXIT DISCHARGE OR A PUBLIC WAY. THE
 SMOKEPROOF ENCLOSURE OR PRESSURIZED STAIRWAY SHALL BE
 PERMITTED TO BE EXTENDED BY AN EXIT PASSAGEWAY IN
 ACCORDANCE WITH SECTION 1022.3. THE EXIT PASSAGEWAY
 SHALL BE WITHOUT OPENINGS OTHER THAN THE FIRE DOOR
 ASSEMBLY REQUIRED BY SECTION 1022.3.1 AND THOSE
 NECESSARY FOR EGRESS FROM THE EXIT PASSAGEWAY. THE EXIT
 PASSAGEWAY SHALL BE SEPARATED FROM THE REMAINDER OF THE
 BUILDING BY 2-HOUR FIRE BARRIERS CONSTRUCTED IN
 ACCORDANCE WITH SECTION 707 OR HORIZONTAL ASSEMBLIES
 CONSTRUCTED IN ACCORDANCE WITH SECTION 711, OR BOTH.
  -SEE 1022.10.1 FOR EXCEPTIONS
  
 60) 1024.1 FBC[B] GENERAL. APPROVED LUMINOUS EGRESS
 PATH MARKINGS DELINEATING THE EXIT PATH SHALL BE
 PROVIDED IN HIGH-RISE BUILDINGS OF GROUP A, B, E, I, M,
 AND R-1 OCCUPANCIES IN ACCORDANCE WITH SECTIONS 1024.1
 THROUGH 1024.5.
 EXCEPTION: LUMINOUS EGRESS PATH MARKINGS SHALL NOT BE
 REQUIRED ON THE LEVEL OF EXIT DISCHARGE IN LOBBIES THAT
 SERVE AS PART OF THE EXIT PATH IN ACCORDANCE WITH
 SECTION 1027.1, EXCEPTION 1
  
 61) 1024.2 FBC[B] MARKINGS WITHIN EXIT COMPONENTS.
 EGRESS PATH MARKINGS SHALL BE PROVIDED IN INTERIOR EXIT
 STAIRWAYS, INTERIOR EXIT RAMPS AND EXIT PASSAGEWAYS, IN
 ACCORDANCE WITH SECTIONS 1024.2.1 THROUGH 1024.2.6.
  -ADD DETAILS TO SHOW COMPLIANCE WITH 1024.2.1 THROUGH
 1024.2.6
  
 62) 1207 FBC[B] PROVIDE FLOORING SUBMITTAL FOR SOUND
 CONTROL, OR ADD TO THE DEFERRED SUBMITTAL LIST.
  -PLEASE ADVISE, WHAT FLOORING AND UNDERLAYMENT ARE
 PROPOSED? PLEASE ADVISE VIA EMAIL. IF THE UNDERLAYMENT
 PRODUCT PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST
 REPORTS ON FILE, THE FOLLOWING REPORTS ARE REQUIRED:
 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM
 EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45
 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90. PENETRATIONS OR OPENINGS IN
 CONSTRUCTION ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES;
 RECESSED CABINETS; BATHTUBS; SOFFITS; OR HEATING,
 VENTILATING OR EXHAUST DUCTS SHALL BE SEALED, LINED,
 INSULATED OR OTHERWISE TREATED TO MAINTAIN THE REQUIRED
 RATINGS. THIS REQUIREMENT SHALL NOT APPLY TO DWELLING
 UNIT ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE
 SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF
 NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN
 ACCORDANCE WITH ASTM E 492.
 FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  -MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 63) 1012.9 FBC[B] INTERMEDIATE HANDRAILS. STAIRWAYS
 SHALL HAVE INTERMEDIATE HANDRAILS LOCATED IN SUCH A
 MANNER THAT ALL PORTIONS OF THE STAIRWAY MINIMUM WIDTH
 OR REQUIRED CAPACITY ARE WITHIN 30 INCHES (762 MM) OF A
 HANDRAIL. ON MONUMENTAL STAIRS, HANDRAILS SHALL BE
 LOCATED ALONG THE MOST DIRECT PATH OF EGRESS TRAVEL.
  -CHECK COMPLIANCE WITH 1012.9 AT BALLROOM STEPS.
  
 64) 1210.2 FBC[B] FINISH MATERIALS. WALLS, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.2.1 THROUGH 1210.2.4.
  
 65) 1210.2.1 FBC[B] FLOORS AND WALL BASES. IN OTHER
 THAN DWELLING UNITS, TOILET, BATHING AND SHOWER ROOM
 FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH FLOORS
 WITH WALLS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 VERTICAL BASE THAT EXTENDS UPWARD ONTO THE WALLS NOT
 LESS THAN 4 INCHES (102 MM).
  
 66) 1210.2.2 FBC[B] WALLS AND PARTITIONS. WALLS AND
 PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4
 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE. EXCEPTION: THIS SECTION DOES NOT APPLY TO THE
 FOLLOWING BUILDINGS AND SPACES: SEE 1210.2.2 FOR
 EXCEPTIONS.
  
 67) 3006.3 FBC[B] HOISTWAY OPENING PROTECTION. WHERE
 SECTION 3006.2 REQUIRES PROTECTION OF THE ELEVATOR
 HOISTWAY DOOR OPENING, THE PROTECTION SHALL BE PROVIDED
 BY ONE OF THE FOLLOWING:
  -(SEE OPTIONS 1-4 FROM FBC 3007.6.4) HOW IS PROTECTION
 PROVIDED FOR ELEVATORS 8, 9 AND 10? ALSO, P-15, P-16,
 P-06 AND P-07
  
 68) 3001 FBC[B] PROVIDE DETAILS OF FREIGHT ELEVATOR.
 A. TYPE OF ELEVATOR AND REFERRENCED STANDARDS.
  B. HOW IS MACHINE ROOM ACCESSED?
  
 69) 3006.3 FBC[B] PRESSURIZATION. THE ELEVATOR MACHINE
 ROOM, CONTROL ROOMS OR CONTROL SPACE WITH OPENINGS INTO
 A PRESSURIZED ELEVATOR HOISTWAY SHALL BE PRESSURIZED
 UPON ACTIVATION OF A HEAT OR SMOKE DETECTOR LOCATED IN
 THE ELEVATOR MACHINE ROOM, CONTROL ROOM OR CONTROL
 SPACE.
  -PROVIDE PRESSURIZATION ANALYSIS.
  
 70) 3005.1 FBC[B] ACCESS. AN APPROVED MEANS OF ACCESS
 SHALL BE PROVIDED TO ELEVATOR MACHINE ROOMS, CONTROL
 ROOMS, CONTROL SPACES AND MACHINERY SPACES.
  -HOW ARE MACHINE ROOMS ACCESSED FOR P-06, P-07, P-16,
 P-17 AND FREIGHT ELEVATORS?
  
 71) 3005.3 FBC[B] PRESSURIZATION. THE ELEVATOR MACHINE
 ROOM, CONTROL ROOMS OR CONTROL SPACE WITH OPENINGS INTO
 A PRESSURIZED ELEVATOR HOISTWAY SHALL BE PRESSURIZED
 UPON ACTIVATION OF A HEAT OR SMOKE DETECTOR LOCATED IN
 THE ELEVATOR MACHINE ROOM, CONTROL ROOM OR CONTROL
 SPACE.
  
 72) 3006 FBC[B] GENERAL COMMENT. THIS COMMENT APPLIES
 TO ALL OTHER ELEVATOR DRAWINGS. AT THIS STAGE THEY MAY
 LACK COMPLETION, SO FURTHER REVIEW WILL BE REQUIRED
 UPON RESUBMITTAL.
  -ELEVATORS P-06 AND 07. HOW DO YOU ACCESS MACHINE
 ROOMS?
  
 73) 3306.1 FBC[B] PROTECTION REQUIRED. PEDESTRIANS
 SHALL BE PROTECTED DURING CONSTRUCTION, REMODELING AND
 DEMOLITION ACTIVITIES AS REQUIRED BY THIS CHAPTER AND
 TABLE 3306.1. SIGNS SHALL BE PROVIDED TO DIRECT
 PEDESTRIAN TRAFFIC.
  -AS THE BUILDING CONSTRUCTION INCREASES THE SIDEWALK
 PROTECTION WILL NEED TO MEET REQUIREMENTS BELOW.
  -SEE 3306.1 TO 3306.9 FOR REQUIREMENTS TO PROVIDE
 WALKWAYS, BARRIERS AND COVERED WALKWAYS.
  
 74) 3007.7.4 FBC[B] LOBBY SIZE. EACH ENCLOSED FIRE
 SERVICE ACCESS ELEVATOR LOBBY SHALL BE NOT LESS THAN
 150 SQUARE FEET (14 M2) IN AN AREA WITH A MINIMUM
 DIMENSION OF 8 FEET (2440 MM).
  -ALS1.114 FIRE LOBBY ON FLOORS 12-30 IS UNDERSIZED.
 CORRIDOR 01-40 ON ALS1.101. GROUND LEVEL FIRE SERVICE
 AND FREIGHT ARE SHOWING ELEVATOR LOBBIES. THIS ARE NOT
 REQUIRED AT EXIT LEVEL AND THE FIRE SERVICE WOULD NOT
 PROVIDE 150 SQ. FT. PLEASE REVIEW THIS AND COORDINATE
 IF FREIGHT IS PRESSURIZED, OR IF LOBBY REQUIRED AT
 LEVEL 7.
  
 75) 3007.7.1 ACCESS. DOOR CONFIGURATION TWO 90 SWINGING
 INTO EXIT STAIR FROM FIRE SERVICE LOBBY.
  -EXIT DOOR FROM FIRE LOBBY WOULD BLOCK EXIT DOOR FROM
 CORRIDOR. PLEASE REVIEW CONFIGURATION AND POSSIBLE. CAN
 SWING FROM FIRE LOBBY BE CHANGED BASED ON 1010.1.2.1
 FBC[B] DIRECTION OF SWING?
  
 76) 3007.7.4 FBC[B] LOBBY SIZE. REGARDLESS OF THE
 NUMBER OF FIRE SERVICE ACCESS ELEVATORS SERVED BY THE
 SAME ELEVATOR LOBBY, THE ENCLOSED FIRE SERVICE ACCESS
 ELEVATOR LOBBY SHALL BE NOT LESS THAN 150 SQUARE FEET
 (14 M2) IN AN AREA WITH A DIMENSION OF NOT LESS THAN 8
 FEET (2440 MM).
  A. FIRE LOBBIES THAT SERVE RESIDENTIAL FIRE SERVICE
 ACCESS ELEVATORS DO NOT MEET THE MINIMUM SIZE REQUIRED
 IN 3007.7.4. PLEASE REVIEW AND ADJUST ACCORDINGLY.
  B. FIRE LOBBY S1 AT EXIT LEVEL IS UNDER SIZED AND FIRE
 LOBBY ISN'T REQUIRED ON EXIT LEVEL. PLEASE REVIEW AND
 ADJUST.
  PLEASE REVIEW TO MEET 3007.7.4
  
 77) 3006.2 FBC[B] HOISTWAY OPENING PROTECTION REQUIRED
 . PROTECTION OF ELEVATOR HOISTWAY DOOR OPENINGS IS NOT
 REQUIRED AT THE LEVEL(S) OF EXIT DISCHARGE, PROVIDED
 THE LEVEL(S) OF EXIT DISCHARGE IS EQUIPPED WITH AN
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 903.3.1.1.
  
 78) 3007.6.2 LOBBY ENCLOSURE. THE FIRE SERVICE ACCESS
 ELEVATOR LOBBY SHALL BE ENCLOSED WITH A SMOKE BARRIER
 HAVING A FIRE-RESISTANCE RATING OF NOT LESS THAN 1
 HOUR, EXCEPT THAT LOBBY DOORWAYS SHALL COMPLY WITH
 SECTION 3007.6.3. EXCEPTION: ENCLOSED FIRE SERVICE
 ACCESS ELEVATOR LOBBIES ARE NOT REQUIRED AT THE LEVELS
 OF EXIT DISCHARGE.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS.
 FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE
 REQUIRED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  