| 2018-11-29 10:08:15 | 1ST REVIEW: REVISION; DRAWING OF RECORD DATED 10/08/18 |
| | DENIED |
| | |
| | 1. RE: P.1; PROVIDE INFORMATION REQUIRED FOR CODE |
| | COMPLIANT INSTALLATION WHICH ACCURATELY REFLECT THE |
| | FIELD INSTALLATION AS FOLLOWS PER WPB PBC 107.2.1 |
| | A. SANITARY FLOOR PLAN; PROVIDE LAYOUT THAT |
| | INCORPORATES PIPING AND FITTINGS WHICH ACCURATELY |
| | REFLECT THE FIELD INSTALLATION. |
| | B. SANITARY RISER DIAGRAM; PROVIDE LAYOUT THAT |
| | INCORPORATES PIPING AND FITTINGS WHICH ACCURATELY |
| | REFLECT THE FIELD INSTALLATION. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |