Plan Review Notes
Plan Review Notes For Permit 18100526
Permit Number 18100526
Review Stop P
Sequence Number 6
Notes
Date Text
2021-02-19 16:59:3102/19/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET P1.01, PLEASE PROVIDE UNDER CODES THE YEAR,
 PLUMBING, AND ACCESSIBILITY REFERENCED USED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 101.4 REFERENCED CODES.
  
 2. ON SHEET P1.01;
  
 A. IN STAFF LOCKERS, THE LAYOUT AND THE ISOMETRIC DO
 NOT MATCH, AND THERE IS AN EXTRA SHOWER. PLEASE CORRECT
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. THE ISOMETRIC DRAWING SHOWS A DIFFERENT LAYOUT THAN
 P2.01. THE NORTH SIDE HAS A DIFFERENT LAYOUT FOR THE
 SANITARY THEY SHOULD MATCH. TOO MANY DETAILS TO
 MENTION, AND THE VERSIONS ARE DIFFERENT LAYOUTS. PLEASE
 CHANGE PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. THERE ARE TWO OUTSIDE SINKS NEXT TO THE BBQS IN THE
 POOL AREA THAT ARE NOT SHOWN ON THIS PAGE, AND THEY ARE
 SHOWN IN P2.01N AND S. PLEASE ADD OR MAKE A REFERENCE
 NOTE FOR THEM PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. ON SHEETS P1.02 AND P1.03;
  
 A. THE NORTH SIDE STORAGE ROOM THAT HAS A CONDENSATE IS
 NOT LABELED. PLEASE LABEL PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. ON THE SAME PAGES, CONDENSATE WAS ADDED FOR
 MINI-SPLIT SYSTEMS, BUT THERE IS NO DETAIL SHOWN FOR
 THE RISERS ON THE CONDENSATE ISOMETRIC AND NO STACK
 REFERENCE. PLEASE PROVIDE PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. ON SHEET P1.02, THE DOMESTIC WATER PUMP ROOM DOES
 NOT SHOW THE PUMP OR A FLOOR DRAIN AS IT WAS ON VERSION
 ONE. PLEASE SHOW OR CLARIFY PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 5. ON SHEET P2.00, PLEASE REMOVE THE HATCHES FOR THE
 OUTER DECK AREA ON THE TRELLIS AS THEY DO DARKEN THE
 PLANS AND CAN NOT MAKE OUTLINE OR NUMBER PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. PLEASE PROVIDE AN ISOMETRIC
 DRAWING FOR SANITARY, GREASE WASTE, AND WATER FOR AN
 OUTSIDE BEACH CLUB. IF THE BAR'S SINK AND AMENITIES ARE
 SHOWN, PLEASE ADD TO THE DRAWING PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 6. ON SHEET 2.01N;
  
 A. THE LEASING OFFICE SINK IS NOT SHOWN ON THE P4.01N
 ISOMETRIC DRAWING, AND PLEASE LABEL THAT ROOM AS WELL
 PER THE WPB AMENDMENTS TO THE FBC SEC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. THERE IS A SECOND SINK SHOWN ON SHEET P4.01N
 ISOMETRIC. IT IS LABELED AS A HAND SINK WITH AN AIR
 ADMITTANCE VALVE. PLEASE REMOVE OR SHOW ON PLANS PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 C. PIPES WERE MOVED IN GRID E-F/3-2, AND ALL THE DETAIL
 IS IN THE STAIRS, WHICH ARE HARD TO READ PLEASE MOVE TO
 A BETTER LOCATION FOR FIELD CLARITY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 D. IN THAT SAME DRAWING, PLEASE LABEL THE RESTROOM NEXT
 TO STAIRS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 E. THE 8? UP IN THE PACKAGE ROOM WAS MOVED, AND IT DOES
 NOT REFLECT P4.01N. PLEASE CHANGE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 F. THE MECHANICAL ROOM IS LABELED, BUT THE WORDS ARE
 HARD TO SEE. PLEASE MOVE, AND IN THE THREE BATHROOMS IN
 THAT AREA, INCLUDING THE OTHER ROOM, PLEASE LABEL PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 G. THERE SEEMS TO BE A REFRIGERATOR IN THE LEASING
 OFFICE. IF SO, PLEASE LABEL, AND IF EQUIPPED WITH AN
 ICE MAKER, IT MUST BE EQUIPPED WITH AN IN-LINE VACUUM
 BREAKER THAT COMPLIES WITH ASSE 1024 PER THE 2017 FBC
 SEC. 608.13.10.
  
 H. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2017 FBC BUILDING SEC. 1210.2.2 AND 2017 FBC SEC. P
 310.3. PLEASE MAKE A NOTE ON THIS SHEET.
  
 I. PLEASE LABEL THE ELEVATORS PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 J. PLEASE PROVIDE SPEC ON THE STEAM UNIT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 K. ON-GRID P-F/4, THERE IS A STORM DRAIN THAT NEEDS TO
 BE PROTECTED FROM A VEHICLE. THIS MAY GO UP SERVAL
 FLOORS OR MOVE IT TO THE OTHER COLUMN PER THE 2017 FBC
 P305.7 PROTECTION OF THE PLUMBING SYSTEM COMPONENTS.
  
 L. THERE IS A DRAIN FOR THE POOL SHOWER ON P2.01S AND
 DOESN?T SHOW IT ON THIS ONE; APPARENTLY, IT IS MISSING.
 PLEASE ADD OR CLARIFY IF ONE IS NOT REQUIRED PER DESIGN
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 M. THERE IS A SPA AND A RESTROOM ADDED, AND IT WILL
 REQUIRE TO COMPLY WITH THE 2017 FLORIDA ACCESSIBILITY
 CODE. PLEASE PROVIDE ARCHITECTURAL PLANS AND PLUMBING
 PLANS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. ON SHEET P2.01N CLG;
  
 A. THE STAIRWELL AND OTHER AREAS HAVE RISER AND HAVE
 LABELS ON TOP OF EACH OTHER IN DETAIL, AND THEY ARE
 HARD TO READ. PLEASE MOVE FOR FIELD CLARITY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. PLEASE LABEL ALL RESTROOMS AND
 ROOMS AS WELL. IF THE REFRIGERATOR HAS AN ICEMAKER,
 PLEASE ADDRESS THE COMMENT FIVE LETTER G. FOR WATER.
  
 B. PLEASE LABEL THE RESTROOM SPA AREA AND SHOW THE
 STEAMER AND ITS SHUTOFF VALVE PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 C. IN THE STAFF LOCKER ROOM, THERE ARE TWO SHOWERS.
 PLEASE SHOW THE SHOWER VALVES' LOCATION AND HEADS PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 8. ON SHEET P2.02S, PLEASE PROVIDE GRID LETTERS ON TOP
 AND ANY OTHER PAGE THAT CONTINUE. PLEASE CORRECT OR ADD
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. SOME GIRDS ARE
 ON TOP OF OTHER VERBIAGE OR STRUCTURE. PLEASE MOVE FOR
 FIELD CLARITY.
  
 9. ON SHEET P2.01S;
  
 A. PLEASE ADDRESS THE SAME COMMENT AS P2.01N IF THEY
 APPLY PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. HOT WATER LINES IN THE MULTI-PURPOSE ROOM UNDER-SLAB
 NOT IN CONDITION SPACE NEED TO BE INSULATED WITH A
 MINIMUM R-3 PER THE 2017 FBC SEC. RE 403.5.3.
  
 C. THERE IS A NOTE 7 FOR NON-PORTABLE WATER. IS THERE A
 DETAIL OR INFORMATION ON ITS WHEREABOUTS? IT IS GOING
 TO THE COOLING TOWER, AND CAN YOU PLEASE TELL ME WHERE
 IT'S COMING FROM AND IF THERE IS ANY TYPE OF BACKFLOW
 DEVICE. THE PREVIOUS VERSION TWO REFERRED TO IRRIGATION
 WATER. PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. IN THE BATHROOM'S FITNESS ROOM, THE VENT NEEDS TO BE
 BETWEEN THE TWO-FLOOR DRAINS PER THE 2017 FBC P 1002.1
 FIXTURE TRAPS. PLEASE LABEL ALL FIXTURES IN THAT AREA,
 WC, FD, LAV, AND DF.
  
 E. THE 3? THAT FEED THE HAND SINK IN THE POOL AREA HAS
 A 2? UP ON THE ISOMETRIC, AND IT LOOKS TO BE IN A
 DIFFERENT WALL. THE ONE ON THIS PAGE IS ON A WALL BUT
 HAS NO LABEL, PURPOSE, OR DESTINATION. PLEASE CORRECT
 AND CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 G. IN THE PACKAGE LOCKER, THERE IS A SANITARY RISER
 GOING UP, AND THIS PAGE SAYS IT IS AN 8? 888 FU, AND ON
 ISO, IT SAYS 6? 922 FU. PLEASE CORRECT AND CLARIFY PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 I. THERE IS A RISER IN THE HALLWAY IN FRONT OF THE
 ELEVATOR, NUMBER 11, WITHOUT SIZE OR TOTAL FIXTURE
 UNIT. PLEASE ADD PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 K. IN THE MECHANICAL ROOM, THERE IS A 6? 260 DFU NOT
 LABEL. PLEASE ADD PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 J. PLEASE LABEL THE SECOND FD AND THE MECHANICAL ROOM
 AND THE JANITORS MOP SINK LABEL SIZE OF PIPE AND
 FIXTURE UNITS PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 K. ITEM 45 BACKWATER VALVE IS CONNECTED TO AND WHERE IT
 CONTINUES? PLEASE CLARIFY OR ADD A NOTE PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 10. ON SHEET P2.01S CLG;
  
 A. THERE IS LETTERING ON A VEHICLE. PLEASE MOVE THEM
 AND ANY OTHER VERBIAGE OR NUMBER ON TOP OF OTHERS LIKE
 WALLS, FIXTURES, AND APPARATUSES ON THIS PLUMBING
 SECTION FOR CLARITY. THERE ARE TOO MANY TO MENTION PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 B. THE SUPPERS ARE NOT SHOWN IN THIS VERSION AS THEY
 ARE IN PREVIOUS, SO PLEASE ADD PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 11. ON SHEET P2.06S;
  
 A. THIS PAGE AND ALL OTHERS THAT FOLLOW THE GRID LETTER
 ARE CUT OFF. PLEASE MOVE THE LETTER FOR ALL, AND THERE
 ARE TOO MANY TO MENTION PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. ON KEYNOTES # 6, IT REFERS TO HOT WATER LINES, AND
 THEY ARE SANITARY LINES. PLEASE CHANGE OR CLARIFY PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 C. ON KEYNOTE # 8 IS IN PENTHOUSE THREE, AND NO
 KEYNOTE. PLEASE PROVIDE OR CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 D. THE GIRD LETTERS ARE CUT OFF ON THE BOTTOM. PLEASE
 MOVE AND CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 12. ON SHEET P2.06N;
  
 A. KEYNOTE #7 REFERS TO WATER LINES, BUT IT POINTS TO
 SANITARY. PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. KEYNOTE #8 NOT FOUND IN THIS SHEET, PLEASE LOCATE OR
 DELETE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. ON PH-2, WATER LINES ARE GOING TO TUB, PLEASE ADD A
 NOTE FOR UNDER SLAB AND ADD TO THE OTHER PENTHOUSES IF
 APPLICABLE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. ON THE SIDE THAT SHOWS THE POOL TO THE GROUND, THE
 LAYOUT IS DIFFERENT, AND THE SINK AND BBQ SEEM TO BE IN
 A DIFFERENT LOCATION. PLEASE DELETE TO PREVENT
 CONFUSION AS THIS LOOKS LIKE A DIFFERENT POOL DESIGN
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 E. STACK SN/32 AND 35 COULD NOT BE LOCATED ON THE
 ISOMETRIC. PLEASE PROVIDE THEM PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 13. ON SHEET P2.06NA;
  
 A. PLEASE REMOVE THE OLD POOL'S SILHOUETTE PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. ON KEYNOTE #18, IT REFERS TO A POOL DRAIN, AND IT IS
 MISSING A TRAP PRIMER; PLEASE SHOW THE TP PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 14. ON SHEET 206SA;
  
 A. THERE IS A PIPE IN THE HALLWAY IT HAS PP, AND I
 COULD NOT FIND IT ON THE PLUMBING SYMBOL &
 ABBREVIATIONS. PLEASE ADD TO IT. PLEASE REMOVE THE
 SILHOUETTE OF THE OLD POOL PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 B. PLEASE REMOVE THE SILHOUETTE OF THE OLD POOL PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. ON NOTE # 27 COULD NOT FIND IT ON THE SHEET. PLEASE
 CLARIFY LOCATION PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 15. ON SHEET P2.07N;
  
 A. RESTROOMS WERE ADDED, AND THEY ARE NOT SHOWN ON THE
 ISOMETRIC. PLEASE ADD TO THE PLUMBING RISER DIAGRAM PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13)
 COMMERCIAL PLUMBING.
  
 B. PLEASE PUT A NOTE ON WHERE BACKFLOW IS REQUIRED AND
 TYPE E.I. BOILER, COOLING TOWER, ETC. THERE IS A PIPE
 IN THE HALLWAY IT HAS PP, AND I COULD NOT FIND IT ON
 THE PLUMBING SYMBOL & ABBREVIATIONS.
  
 C. PLEASE REMOVE THE SILHOUETTE OF THE OLD POOL PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 D. THERE IS SEVERAL HOSE BIBB WITHOUT SHUT-OFF VALVES (
 BY STAIRWELL, POOL, RESTROOM), AND THEY ARE REQUIRED
 PER THE 2017 FBC 606.2 LOCATION OF SHUTOFF VALVES.
  
 E. PLEASE LABEL HOSE BIBB IN THE RESTROOM AND SHOW
 SHUTOFF PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 F. PLEASE LABEL THE RESTROOM AND ALL OTHER ROOMS WITH
 PLUMBING APERTURES PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 G. POOL CALLS FOR AUTOFILL; HOW IS IT PROTECTED FROM
 BACKFLOW PROTECTION. PLEASE CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 16. ON SHEET P2.07S, PLEASE REFER TO P2.07N.
  
 17. ON SHEET P208N AND P207S, THERE SEEM TO BE WALLS
 MISSING AND INFORMATION. PLEASE REFER TO VERSION 1 TO
 MATCH THE DRAWING FOR CLARIFICATION PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 18. ON SHEETS, P4.01N AND P5.01S, THE 4?, 3? HD, AND 6?
 FFD DRAINS DO NOT SHOW A TRAP PRIMER. PLEASE ADD PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 19. ON SHEET, P4.02N DOES NOT MATCH THE PH-1 LAYOUT FOR
 SN/2. PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 20. ON SHEET 403N, STACK S/16A AND B IN PH-2 ARE
 MISSING. PLEASE REFER TO P2.06N AND PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 21. ON SHEET 404N, THE STACK SN/28 HAS TWO SANITARY
 BRANCHES MISSING; PLEASE REFER TO PH-2 AND CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 NOTE: STACK SN/32 AND 35 COULD NOT BE LOCATED ON THE
 ISOMETRIC; PLEASE PROVIDE PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 22. ON SHEET P4.05N;
  
 A. THE BOOSTER PUMPS PER MANUFACTURERS SPECIFICATION
 FOR MAINTENANCE PURPOSES A BY-BASS VALVE WILL BE
 REQUIRED. PLEASE CHANGE OR CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. DRAIN PAN SHALL BE RODENT PROTECTED GOING OUTSIDE
 STRUCTURE PER THE 2017 FBC FBC P 304.4. PLEASE SPECIFY
 HOW, SCREEN OR MESH?
  
 23. ON SHEET P4.06N;
  
 A. THERE IS A SHUTOFF VALVE MISSING ON HOSE BIBBS.
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. THE CONDENSATE AIR RELIEF CAP SHALL NOT BE IN THE
 WALL CAVITY AS IT HAS NEGATIVE OR POSITIVE PRESSURE FOR
 A VENT TO WORK PER THE 2017 FBC PLUMBING DEFINITION OF
 A VENT SYSTEM. A PIPE OR PIPES INSTALLED TO PROVIDE A
 FLOW OF AIR TO OR FROM A DRAINAGE SYSTEM OR TO PROVIDE
 A CIRCULATION OF AIR WITHIN SUCH SYSTEM TO PROTECT TRAP
 SEALS FROM SIPHONAGE AND BACKPRESSURE. PLEASE MOVE OUT
 OF THE WALL, AND IF IN A PLENUM, IT SHALL BE CPVC FOR
 THE FLAME INDEX.
  
 C. RN/1,4,5 AND 7 FOR CONDENSATE AT THE TOP FLOOR HAS A
 6 FOR A NOTE, AND IT SHOULD BE A 7. PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 D. CPVC HOT RISER FIRST FLOOR HAS A NINE, AND IT SHOULD
 BE AN EIGHT. PLEASE CORRECT PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 24. ON SHEET P4.01N, THE CONDENSATE SPILL PIPE CAN NOT
 DISCHARGE INTO THE SANITARY SYSTEM PER THE CITY OF WEST
 PALM BEACH UTILITIES DEPARTMENT. PLEASE RUN INTO THE
 SANITARY SYSTEM.
  
 25. ON SHEET P4.08N IS MISSING A CLEAN-OUT ON STACK P.
 PLEASE ADD PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 26. ON SHEET P409N, PLEASE PROVIDE CLEANOUT FOR GDS/6
 AT BASE PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 27. ON SHEET P4.10N; PLEASE PROVIDE DETAIL FOR
 PERFORATED CAPS, REFER TO COMMENT 23 B. PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 28. ON SHEET P5.01S;
  
 A. THE 6? FFD AND THE TWO-FLOOR DRAINS IN THE
 MECHANICAL ROOM AREA ARE MISSING THE TRAP PRIMERS.
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. PLEASE LABEL THE SECOND FD IN THE MECHANICAL ROOM,
 AND THE JANITORS MOP SINK LABEL SIZE OF PIPE AND
 FIXTURE UNITS PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 29. ON SHEET P.502S;
  
 A. THE WASHING MACHINE IS ON A DOUBLE SANITARY TEE.
 PLEASE CORRECT PER THE 2017 FBC 706.3 INSTALLATION OF
 FITTINGS.
  
 B. THERE IS AN X IN SEVERAL LOCATIONS, AND ON THE SIDE
 OF SS/1 IS AN RFI-84 IN A TRIANGLE WITH AN X. PLEASE
 PROVIDE THESE NOTES AND MAKE REFERENCE IN THE KEY NOTE
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. THE STACK SS/2 DOES NOT MATCH THE PH-4 REFER TO
 P2.06S. PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. THE STACK SS/11, 12, AND 15 IN PH-2 AND FOUR ARE
 MISSING THE MASTER BATHROOM GROUP REFER TO P2.06S.
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 E. THE STACK SS/32 IS NOT SHOWN OR PROVIDE ON THIS
 DRAWING AND REFERS TO P2.06S. PLEASE CORRECT PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 30. ON SHEET P5.03S;
  
 A. THE STACK SS/25 IN THE KITCHEN IS LABELED AS A LAV
 REFER TO P2.06S. PLEASE CORRECT PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 B. IN THE SAME STACK, IT HAS TWO BRANCHES THAT ARE NOT
 SHOWN. PLEASE REFER TO P2.06S AND CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 31. ON SHEET P5.05S;
  
 A. IT DOES NOT SHOW THE TRASH COMPACTOR GOING UP LIKE
 ON P4.05N. PLEASE SHOW PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 IT IS RECOMMENDED BUT NOT A REQUIREMENT THAT THE FIRST
 FLOOR WHERE THE BUCKET IS HAS A HOSE BIBB FOR
 MAINTENANCE PURPOSES.
  
 B. THE TWO BOOSTER PUMPS PER MANUFACTURER SPECIFICATION
 FOR MAINTENANCE PURPOSES REQUIRE BY-BASS VALVES. PLEASE
 CHANGE OR CLARIFY PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. PLEASE PROVIDE THE ON P1.00 THE SP, IRR, AND HWR IN
 THE PLUMBING SYMBOLS & ABBREVIATION PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 D. NOTE 35, PLEASE ADD ICEMAKER SHALL BE EQUIPPED WITH
 AN IN-LINE VACUUM BREAKER THAT COMPLIES WITH ASSE 1024
 PER THE 2017 FBC SEC. 608.13.10.
  
 32. ON SHEET A0.200, PLEASE REMOVE ANY DETAIL OF
 ACCECIBITLY THAT DOES NOT PERTAIN TO THIS PROJECT PER
 THE WPB AMENDMENT TO FBC SEC. 107.2.1.3 QUALITY OF
 BUILDING PLANS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  