| | APPROVED WITH EXCEPTIONS - PROVISO |
| | |
| | 1) PROPERTY TO BE REPLATTED PRIOR TO ISSUANCE OF THE |
| | FIRST C.O. PER SECTION 6(2)(E)(II) OF RESOLUTION NO. |
| | 185-18 (THE "DEVELOPMENT ORDER"). |
| | |
| | 2) THE PROPERTY IS LOCATED IN AN AE FLOOD ZONE WITH A |
| | BASE FLOOD ELEVATION OF 7' NAVD88. THE CITY'S FLOOD |
| | ORDINANCE REQUIRES A 2' FREEBOARD WHICH MAKES THE |
| | DESIGN FLOOD ELEVATION FOR THIS PROJECT 9.0'. ALL |
| | EQUIPMENT SERVICING THE BUILDING IS REQUIRED TO BE AT |
| | OR ABOVE 9' NAVD. ELEVATION CERTIFICATES WILL BE |
| | REQUIRED TO SHOW COMPLIANCE WITH THE CITY'S FLOOD |
| | POLICY. THE CITY REQUIRES THREE ELEVATION CERTIFICATES. |
| | FIRST, A PRECONSTRUCTION ELEV. CERT. BASED ON THE |
| | CONSTRUCTION DRAWING. SECOND, A CONSTRUCTION ELEV. |
| | CERT. BASED ON THE LOWEST FLOOR FORMS. THIRD A FINAL |
| | ELEV. CERT. BASED ON THE FINISHED BUILDING. PLEASE |
| | SUBMIT THE PRECONSTRUCTION ELEVATION CERTIFICATE AT |
| | THIS TIME. THE CITY'S FLOOD ORDINANCE ARTICLE XVII - |
| | FLOOD PREVENTION AND CONTROL SEC. 94-546 - PROVISIONS |
| | FOR FLOOD HAZARD REDUCTION. |
| | |
| | 3) THE RESIDENTIAL ACTIVE USE ROOMS LOCATED IN THE |
| | PARKING GARAGE ARE CURRENTLY SHOWN AS SHELLS. PER THE |
| | RESPONSE LETTER, THE ACTUAL USE OF THESE ROOMS, THE |
| | BATHROOM REQUIREMENTS AND ANY OTHER REQUIREMENTS WILL |
| | BE ADDRESSED AT A LATER DATE. FBC 107 |
| | |
| | 4) A HOLD WILL BE PLACED ON THE C.O. UNTIL THE ART IN |
| | PUBLIC PLACES REQUIREMENT HAS BEEN ADDRESSED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |