2020-09-22 14:41:58 
 APPROVED WITH EXCEPTIONS - PROVISO
  
 1) PROPERTY TO BE REPLATTED PRIOR TO ISSUANCE OF THE
 FIRST C.O. PER SECTION 6(2)(E)(II) OF RESOLUTION NO.
 185-18 (THE "DEVELOPMENT ORDER").
  
 2) THE PROPERTY IS LOCATED IN AN AE FLOOD ZONE WITH A
 BASE FLOOD ELEVATION OF 7' NAVD88. THE CITY'S FLOOD
 ORDINANCE REQUIRES A 2' FREEBOARD WHICH MAKES THE
 DESIGN FLOOD ELEVATION FOR THIS PROJECT 9.0'. ALL
 EQUIPMENT SERVICING THE BUILDING IS REQUIRED TO BE AT
 OR ABOVE 9' NAVD. ELEVATION CERTIFICATES WILL BE
 REQUIRED TO SHOW COMPLIANCE WITH THE CITY'S FLOOD
 POLICY. THE CITY REQUIRES THREE ELEVATION CERTIFICATES.
 FIRST, A PRECONSTRUCTION ELEV. CERT. BASED ON THE
 CONSTRUCTION DRAWING. SECOND, A CONSTRUCTION ELEV.
 CERT. BASED ON THE LOWEST FLOOR FORMS. THIRD A FINAL
 ELEV. CERT. BASED ON THE FINISHED BUILDING. PLEASE
 SUBMIT THE PRECONSTRUCTION ELEVATION CERTIFICATE AT
 THIS TIME. THE CITY'S FLOOD ORDINANCE ARTICLE XVII -
 FLOOD PREVENTION AND CONTROL SEC. 94-546 - PROVISIONS
 FOR FLOOD HAZARD REDUCTION.
  
 3) THE RESIDENTIAL ACTIVE USE ROOMS LOCATED IN THE
 PARKING GARAGE ARE CURRENTLY SHOWN AS SHELLS. PER THE
 RESPONSE LETTER, THE ACTUAL USE OF THESE ROOMS, THE
 BATHROOM REQUIREMENTS AND ANY OTHER REQUIREMENTS WILL
 BE ADDRESSED AT A LATER DATE. FBC 107
  
 4) A HOLD WILL BE PLACED ON THE C.O. UNTIL THE ART IN
 PUBLIC PLACES REQUIREMENT HAS BEEN ADDRESSED.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  