| Plan Review Notes For Permit 18100526 |
| Permit Number |
18100526 |
|
| Review Stop |
SIGNATURE |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2020-06-10 13:22:39 | SOME SHEETS ARE NOT DIGITALLY SIGNED/SEALED. SOME SHOW | | | INVALID SIGNATURES. SOME SHEETS HAVE A DIGITAL | | | SIGNATURE FROM AN ENGINEER THAT IS SELF-CERTIFIED, | | | WHICH IS NOT PERMITTED BY FBPE. PER THE WPB AMENDMENTS | | | TO THE FBC, EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED | | | (AND SEALED FOR DESIGN PROFESSIONALS) BY THE PERSON | | | RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A | | | DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY | | | VERIFICATION. PROVIDE CORRECTION. WPB FBC 107.1; FS | | | 471/481 |
|