| 2020-05-29 11:42:23 | 4TH REVIEW FBC-2017 MECHANICAL |
| | PERMIT-18100526 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE SHOW THAT THE O.A. CALCULATIONS COMPLIES WITH |
| | ZONE AIR DISTRIBUTION EFFECTIVENESS. FBC M |
| | 403.3.1.1.1.2 |
| | |
| | 2) PLEASE UPDATE ALL SHEETS SHOWING THE EXHAUST FAN AND |
| | FD FOR THE TRASH ROOMS ON ALL FLOORS. |
| | FBC FS 107.2.1 |
| | |
| | 3) SHEET M2.01N PLEASE VERIFY THAT THE O.A. INTAKE |
| | OPENING FOR THE 48X24 LOUVER IS AT LEAST 10? FROM THE |
| | NEWLY ADDED EXHAUST TERMINATION FOR THE TRASH AREA. FBC |
| | M 401.2 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |